IC694ALG221

IC694ALG221 4-Channel Analog Current Input Module: Precision Current Measurement

The IC694ALG221 is a 4-channel analog input module designed for current inputs. This module offers two possible input ranges:

    4 to 20 mA
    0 to 20 mA

The module comes with two range jumpers: one for channels one and two, and another for channels three and four. The conversion speed for each of the four channels is half a millisecond, providing an update rate of two milliseconds for any channel. The converted signal has a resolution of 12 bits (1 part in 4096), offering precise current measurements over either range.

The module is designed with input protection sufficient to operate with up to 200 V common-mode voltage while maintaining reduced performance. It provides electrical isolation from external noise between the field wiring and the backplane through optical isolation.

This module can be installed in any I/O slot in an RX3i system.
Isolated +24 VDC Power

If this module is installed in an RX3i Universal Backplane, an external source of isolated +24 VDC is required to power the module. This external source must be connected via the TB1 connector located on the left side of the backplane.

If the module is installed in an Expansion Backplane, the backplane power supply provides the necessary isolated +24 VDC output for the module.
LED Indicators

The Module OK LED lights up when the module’s power supply is operating correctly, providing a quick visual status check.
Technical Specifications

    Input Current Ranges: 4 to 20 mA and 0 to 20 mA
    Calibration: Factory calibrated to 4 μA per count
    Update Rate: 2 milliseconds (all four channels)
    Resolution (4-20 mA): 4 μA (1 LSB = 4 μA)
    Resolution (0-20 mA): 5 μA (1 LSB = 5 μA)
    Accuracy: 0.1% full scale + 0.1% reading
    Common Mode Voltage: 200 volts
    Linearity: Less than 1 Least Significant Bit (LSB)
    Isolation:
        Field to Backplane (optical) and to frame ground: 250 VAC continuous; 1500 VAC for 1 minute
        Common Mode Rejection: >70dB at DC; >70dB at 60Hz
        Cross-Channel Rejection: >80dB from DC to 1kHz
    Input Impedance: 250 Ohms
    Input Filter Response: 325 Hz
    Power Consumption:
        100 mA from the isolated +24 VDC supply
        25 mA from the +5 VDC bus on the backplane

Data Format

The module stores data in the PLC CPU in 16-bit 2’s complement format. The default range for each input is 4 to 20 mA, scaled so that 4 mA corresponds to a count of 0 and 20 mA corresponds to a count of 32000, with each 1000 counts representing 0.5 mA.

When a jumper is installed on the I/O terminal board, the input range for a pair of inputs is changed to 0 to 20 mA. In this range, 0 mA corresponds to a count of 0 and 20 mA corresponds to a count of 32000, with each 800 counts representing 0.5 mA.

If the current source is reversed or falls below the lower limit of the range, the module provides an input value corresponding to the low end of the range (0000H in PLC memory). If the current exceeds 20 mA, the module outputs a full-scale value (7FF8H in PLC memory).
Field Wiring

The IC694ALG221 module uses the following terminal assignments for field wiring:
Terminal    Connection
1    0-20 mA Jumper for Channels 1 and 2
2    0-20 mA Jumper for Channels 1 and 2
3    Channel 1 (+)
4    Channel 2 (+)
5    Channel 1 (-)
6    Channel 2 (-)
7    Common
8    Common
9    Shield Termination for Channel 1
10    Shield Termination for Channel 2
11    0-20 mA Jumper for Channels 3 and 4
12    0-20 mA Jumper for Channels 3 and 4
13    Channel 3 (+)
14    Channel 4 (+)
15    Channel 3 (-)
16    Channel 4 (-)
17    Common
18    Common
19    Shield Termination for Channel 3
20    Shield Termination for Channel 4

To minimize noise and capacitive loading, all field connections should use high-quality, twisted, and shielded instrumentation cables. Shields can be connected to either the COM or GND terminals. The COM terminal provides access to the analog circuit's common point, while the GND terminal connects to the backplane frame ground.

To limit common-mode voltages, each current source common line can also be tied to its associated COM terminal if the source is floating. These optional connections are shown in the wiring diagram.
Recommendations

The IC694ALG221 module is an excellent choice for applications requiring precise measurement of 4 to 20 mA and 0 to 20 mA current signals. Its fast conversion and high resolution ensure reliable, real-time performance for control systems. The module's optical isolation provides excellent protection against noise in industrial environments. For best results, use high-quality shielded cables and configure the jumpers correctly based on your input range.

>> IC694ALG221 Analog modules User manual (pdf)

++ Other 90-30 PLC modules

----------

+ Ge-Fanuc 2 Homepage

+ Ge-Fanuc Contact (for Automation Mall)

+ About Ge-Fanuc

Reminder: GE Fanuc IC694ALG221 Analog modules and other Ge-Fanuc modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 06.03.2013 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."