IC693CBL313

IC693CBL313 (8 meters / 25 feet) and IC693CBL314 (15 meters / 50 feet) Expansion Cables

General Cable Usage:

    The IC693CBL313 and IC693CBL314 cables are used to daisy-chain up to seven expansion backplanes to the main backplane in an I/O bus system.
    These cables can also be used to provide connection points for custom point-to-point connections, often utilizing the IC693CBL300 for this purpose.

Termination Requirements:

    These cables do not have built-in termination, so the last backplane in the expansion chain must be properly terminated.
    A Terminator Plug (IC693ACC307) is used to terminate the last expansion backplane in the system, ensuring stable system operation.
    The total length of the cables from the universal backplane to the last expansion backplane should not exceed 15 meters (50 feet). Exceeding this length can cause the system to malfunction.

Cable Specifications:

    Cable Type: Belden 8107 (no substitutes)
    Construction: Overall braid over foil shield, twisted-pair
    Voltage Rating: 30 volts
    Temperature Rating: 80°C (176°F)
    Wire Gauge: 24 AWG (0.22 mm²) tinned copper
    Nominal Impedance: 100 Ohms
    Velocity of Propagation: 70%

Connector Types:

    Crimp Plug: Amp 207464–1; Pin Male Connector: Amp 66506–925
    Solder Plug: Amp 747912–2
    Crimp Receptacle: Amp 207463–2; Pin Female Connector: Amp 66504–925
    Connector Shell Kit: Amp 745833–5 (metal-plated plastic with nickel over copper)

Pin Assignments and Signals: The cables carry various signals with the following pin-to-pin connections:

    Pin 16 & 17: DIODT (I/O Serial Data, Positive & Negative)
    Pin 24 & 25: DIOCLK (I/O Serial Clock, Positive & Negative)
    Pin 20 & 21: DRSEL (Remote Select Signal, Positive & Negative)
    Pin 12 & 13: DRPERR (Parity Error, Positive & Negative)
    Pin 8 & 9: DRMRUN (Remote Run Signal, Positive & Negative)
    Pin 2 & 3: DFRAME (Cycle Frame, Positive & Negative)
    Pin 1: FGND (Frame Ground for Cable Shield)
    Pin 7: 0V (Logic Ground)

Cable Assembly: For custom-length cables, the best noise immunity is achieved by using a metalized connector cover that ensures contact with the braided and foil shielding across the entire length of the cable.

Steps for Cable Assembly:

    Strip approximately 5/8 inch of insulation to expose the shield.
    Place a split-ring ferrule over the cable insulation.
    Fold the shield back over the ferrule and insulation.
    Secure the metal hood over the folded shield and clamp it tightly.
    Test the cable with an ohmmeter to ensure continuity between both connector shells.

Summary:

    The IC693CBL313 and IC693CBL314 cables are essential for connecting expansion backplanes to the main backplane.
    Proper termination of the last backplane is required, and the total cable length should not exceed 15 meters.
    Correct assembly and termination are critical for maintaining signal integrity and ensuring stable system performance.

>> IC693CBL313 Data cables User manual (pdf)

++ Other 90-30 PLC modules

----------

+ Ge-Fanuc 2 Homepage

+ Ge-Fanuc Contact (for Automation Mall)

+ About Ge-Fanuc

Reminder: IC693CBL313 and other Ge-Fanuc modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 06.03.2013 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."