IC693CBL302 I/O Bus Expansion Cable: Simplified Overview for Electricians

What Does This Cable Do?
The IC693CBL302 is a 15-meter (50-foot) I/O bus expansion cable with male connectors on both ends. It is used to connect the Serial Bus Transmitter Module (IC695LRE001) to Serial Expansion Backplanes (IC694/693CHS392 or IC694/693CHS398). Additionally, this cable helps interconnect additional expansion and remote backplanes within the system.


One key feature of this cable is that it has built-in I/O bus terminating resistors at the end of the connector. This eliminates the need for a separate termination block. However, it is only suitable for systems with one expansion backplane.

How Is This Cable Used?

    One end of the cable connects to the expansion module in the CPU baseplate, and the other end connects to a single expansion backplane.
    This cable is designed to be used in systems where there is only one expansion backplane.

Cables with Three Connectors (IC693CBL300, 301, 312, 313, 314):
These cables feature a three-connector or "wye" configuration, which allows for additional connection points and daisy-chain connections.

    For example, IC693CBL301 is a 2-meter (6-foot) cable with three connectors.
    These cables enable you to daisy-chain up to seven expansion backplanes.

Termination Requirements:

    The last expansion backplane in the daisy chain must be terminated using a Terminator Plug (IC693ACC307). Without proper termination, the system can become unstable.
    The total cable length in the system should not exceed 50 feet (15 meters).

Cable Specifications:

    Cable type: Belden 8107, 30 volts, 80°C
    Nominal impedance: 100 ohms
    24 AWG (0.22 mm²) tinned copper wire
    Connector parts: AMP 207464–1, AMP 747912–2

Pin Assignments and Signals: Each pin in the cable carries signals such as serial data, clock signals, and other control signals:

    DIODT: I/O Serial Data
    DIOCLK: I/O Serial Clock
    DRSEL: Remote Select Signal
    DRMRUN: Remote Run Signal

Each signal has positive and negative lines, so pin 2 connects to pin 2, pin 3 to pin 3, and so on.

Building and Testing the Cable:

    For the best noise immunity, a metalized connector cover should be used, which makes solid contact with the cable’s braided shield. The shielding should remain continuous across the entire length of the cable.
    After assembly, use an ohmmeter to check for continuity between the connectors to ensure proper grounding.

Summary:

    The IC693CBL302 cable is ideal for connecting a single expansion backplane to the CPU baseplate.
    Ensure that the last backplane in the system is properly terminated, and the total cable length should not exceed 15 meters.
    Proper installation and shielding are critical to avoiding system errors due to signal loss or noise interference.

>> IC693CBL302 cables User manual (pdf)

++ Other 90-30 PLC modules

----------

+ Ge-Fanuc 2 Homepage

+ Ge-Fanuc Contact (for Automation Mall)

+ About Ge-Fanuc

Reminder: IC693CBL302 and other Ge-Fanuc modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 06.03.2013 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."