Ge VAT300 fault codes 3
Hi everyone,
Overheat (UOH.n)
- Description: Overheating detected, possibly due to cooling fan trouble, high ambient temperature, or clogged vent/heatsink.
- Cause: Inadequate cooling or high ambient temperature.
+ Solution: Replace the cooling fan if necessary, lower the ambient temperature, and clean the vent/heatsink.
Overspeed (SP-1)
- Description: Motor rotation count exceeded the overspeed setting value.
- Cause: Excessive motor speed.
+ Solution: Adjust the ASR response, increase the acceleration time setting, or change the speed setting gradually.
Speed Detection Error (SP-2)
- Description: Motor rotation speed fluctuation ratio exceeded the error level setting value.
- Cause: Speed detection error.
+ Solution: Check the encoder wiring.
Speed Deviation Error (SP-3)
- Description: Difference between the motor rotation speed command value and detected value exceeds the error detection setting value.
- Cause: Speed deviation error.
+ Solution: Check the encoder wiring and adjust the speed command and S-pattern characteristics setting.
Reverse Run Detection Error (SP-4)
- Description: Motor rotated in the reverse direction of the speed command and exceeded the error detection setting value.
- Cause: Reverse run error.
+ Solution: Check whether the motor ran in reverse due to the load and check the ASR torque limiter setting values.
Encoder Initialization Error 1 (SP-5)
- Description: Encoder initialization error occurred during PM motor control.
- Cause: Encoder signal abnormality.
+ Solution: Check the encoder selection and wiring.
Encoder Initialization Error 2 (SP-6)
- Description: Encoder initialization error occurred during PM motor control.
- Cause: Encoder signal abnormality.
+ Solution: Check the encoder wiring and improve the installation environment regarding noise.
Fuse Blown (FUSE)
- Description: Main circuit fuse is disconnected.
- Cause: Wiring issue, foreign debris, short-circuit, or ground fault.
+ Solution: Check the main circuit input/output wiring and replace the fuse if blown.
Parallel Unit Signal Cutoff (BPFLT)
- Description: Connection signal was disconnected when using a parallel machine.
- Cause: Wiring or connector issue.
+ Solution: Check the wiring and connector.
Automatic Tuning Abnormal Completion (TT-n)
- Description: Automatic tuning completed abnormally.
- Cause: Motor may not be connected correctly, or parameters may not be set correctly.
+ Solution: Check the connection, parameter settings, and separate the load and machine if necessary.
Equipment Load (OL-1)
- Description: VAT300 may have overloaded.
- Cause: Excessive load.
+ Solution: Reduce the load or increase the inverter capacity.
DBR Overload (OL-2)
- Description: The regenerative power may be excessive.
- Cause: Excessive regenerative power.
+ Solution: Increase the deceleration time and reduce the regenerative power.
Motor Overload (OL-3)
- Description: The motor may have overloaded.
- Cause: Excessive load on the motor.
+ Solution: Reduce the load or increase the motor and inverter capacity.
Grounding (GRD.n)
- Description: A ground fault may have occurred in the power cable or motor.
- Cause: Ground fault.
+ Solution: Restore the grounded point and improve the installation environment regarding noise.
I/O Error (IO-1, IO-2, IO-3, IO-4, IO-B)
- Description: I/O errors related to gate turn-off circuit, A/D converter, current detection, retry time-out, and PID settings.
- Cause: External noise, control circuit fault, or incorrect settings.
+ Solution: Look for the noise source and remove the cause. Check the control circuit and settings.
External Brake Errors (IO-C, IO-D, IO-E)
- Description: Errors related to external brake IDET, RUN, and answer signals.
- Cause: Incorrect settings or motor wiring connections.
+ Solution: Check the settings and motor wiring connections.
CPU Error (CPU-n)
- Description: Unit malfunctioning due to external noise or control circuit fault.
- Cause: External noise or control circuit fault.
+ Solution: Look for the noise source and remove the cause. Check the control circuit. Power cycle the unit.
E2PROM Data Error (DER)
- Description: Incorrect parameter setting value.
- Cause: Incorrect parameter setting.
+ Solution: Correct the parameter setting value.
Verify Check Data Error (EP.ERR.)
- Description: Error occurred during verify check in the parameter copy function using the operation panel.
- Cause: Verification error.
+ Solution: Execute the parameter copy function again.
Input Phase Failure (PHL1)
- Description: Phase failure in the AC input power supply.
- Cause: Phase failure or high load pulsation.
+ Solution: Investigate the AC input power supply and eliminate the phase failure. Check the AC input wire tightening.
Output Phase Failure (PHL2)
- Description: Primary coil of the motor may not be correct.
- Cause: Motor or wiring issue.
+ Solution: Check the motor and wire tightening state.
MC Error (MC-1)
- Description: Pre-charge magnetic contactors may not be working properly.
- Cause: Magnetic contactor failure.
+ Solution: Turn the power off and check the magnetic contactors and auxiliary contacts.