Overcurrent during Stop (OC-1)
- Description: Overcurrent detected during the stop phase.
- Cause: Possible power module failure or ground fault.
+ Solution: Check and replace the power module if necessary. Restore the grounded point.
Overcurrent during Constant Speed Operation (OC-2)
- Description: Overcurrent detected during constant speed operation.
- Cause: Sudden load change, power voltage drop, or unstable inverter operation.
+ Solution: Reduce load fluctuation, check power voltage, adjust settings to stabilize operation.
Overcurrent during Acceleration (OC-3)
- Description: Overcurrent detected during acceleration.
- Cause: Too rapid acceleration or load fluctuation.
+ Solution: Increase acceleration time setting, adjust torque boost voltage, and check load conditions.
Overcurrent during Deceleration (OC-4)
- Description: Overcurrent detected during deceleration.
- Cause: Short circuit or rapid load fluctuation.
+ Solution: Increase deceleration time setting and adjust settings to stabilize operation.
Overcurrent during Braking (OC-5)
- Description: Overcurrent detected during braking.
- Cause: Short circuit or rapid load fluctuation.
+ Solution: Reduce brake voltage setting and check for ground faults.
Overcurrent during ACR (OC-6)
- Description: Overcurrent detected during Automatic Current Regulation (ACR).
- Cause: Load fluctuation or short circuit.
+ Solution: Check load conditions and restore the grounded point.
Overcurrent during Pre-excitation (OC-7)
- Description: Overcurrent detected during pre-excitation.
- Cause: Short circuit or load fluctuation.
+ Solution: Restore the grounded point and check load conditions.
Overcurrent during Automatic Tuning (OC-9)
- Description: Overcurrent detected during automatic tuning.
- Cause: Short circuit or load fluctuation.
+ Solution: Increase acceleration and deceleration time settings, adjust torque stabilizing gain, and check for ground faults.
Overvoltage during Stop (OV-1)
- Description: Overvoltage detected during the stop phase.
- Cause: Power supply voltage rise or surge voltage.
+ Solution: Reduce the voltage to within the specified range and check the power system.
Overvoltage during Constant Speed Operation (OV-2)
- Description: Overvoltage detected during constant speed operation.
- Cause: Power supply voltage rise or load fluctuation.
+ Solution: Reduce the voltage to within the specified range and check load conditions.
Overvoltage during Acceleration (OV-3)
- Description: Overvoltage detected during acceleration.
- Cause: Power supply voltage rise or sudden load change.
+ Solution: Reduce the voltage to within the specified range and adjust settings to manage load changes.
Overvoltage during Deceleration (OV-4)
- Description: Overvoltage detected during deceleration.
- Cause: Large load GD² or power supply voltage rise.
+ Solution: Set the deceleration time according to the load GD² and reduce the voltage to within the specified range.
Overvoltage during Braking (OV-5)
- Description: Overvoltage detected during braking.
- Cause: Power supply voltage rise or sudden load change.
+ Solution: Reduce the voltage to within the specified range and check load conditions.
Overvoltage during ACR (OV-6)
- Description: Overvoltage detected during Automatic Current Regulation (ACR).
- Cause: Power supply voltage rise.
+ Solution: Reduce the voltage to within the specified range.
Overvoltage during Pre-excitation (OV-7)
- Description: Overvoltage detected during pre-excitation.
- Cause: Power supply voltage rise.
+ Solution: Reduce the voltage to within the specified range.
Overvoltage during Automatic Tuning (OV-9)
- Description: Overvoltage detected during automatic tuning.
- Cause: Power supply voltage rise.
+ Solution: Reduce the voltage to within the specified range.
Undervoltage (UV-n)
- Description: Undervoltage detected, possibly due to a power voltage drop, input phase failure, or instantaneous power failure.
- Cause: Power supply issues.
+ Solution: Check the power supply system and correct if necessary.