Ge VAT200 fault codes 2
General Troubleshooting
Condition: Is the motor not running?
Checkpoint: Is power applied to L1(L), L2, and L3(N) terminals (is the charge indicator on)?
Solution: Is
power applied? Turn OFF the power and then turn it ON again. Make sure
the power voltage is correct. Ensure that the screws are tightly
secured.
Condition: Is there voltage between output terminals T1, T2, and T3?
Solution: Turn OFF the power and then turn it ON again.
Solution: Reduce the load to allow the motor to operate.
Condition: Is there any abnormality in the inverter?
Checkpoint: Is a forward or reverse running command given?
Solution: Check and correct the wiring according to error descriptions.
Condition: Is the analog frequency signal input?
Checkpoint: Is the wiring of the analog frequency input signal correct? Is the voltage of the frequency input correct?
Solution: Is the operating mode setting correct? Perform operations on the digital panel.
Condition: Is the motor running but in the reverse direction?
Checkpoint: Is the wiring correct for output terminals T1, T2, and T3?
Solution: Ensure that the wiring matches the motor's U, V, and W terminals. Is the wiring correct for forward and reverse signals? Check the wiring if necessary.
Condition: Can't adjust the motor speed?
Checkpoint: Is the wiring correct for analog frequency inputs?
Solution: Check the wiring if necessary. Is the operating mode setting correct? Check the operator's operating mode.
Condition: Is the motor operating speed too high or too low?
Checkpoint: Is the load too heavy?
Solution: Reduce the load. Are the motor specifications (poles, voltage...) correct? Confirm the motor specifications. Is the gear ratio correct? Confirm the gear ratio. Is the maximum output frequency setting correct? Confirm the maximum output frequency.
Condition: Is the motor speed changing unusually?
Checkpoint: Is the load too heavy?
Solution: Reduce the load. Is the load changing significantly? Minimize the change in load. Increase the capacities of the inverter and motor. Is the input power phase missing? Add an AC reactor on the power input side (if single-phase power is used). Check the wiring (if three-phase power is used).
Error Display and Solution
OC-C - Overcurrent at Constant Speed
- Cause: 1. Temporary load change 2. Temporary power change
- Solution: 1. Increase inverter capacity 2. Rerun parameter auto-tuning (0-06 = 1) 3. If the above solutions do not work, reduce stator resistance (14-0)
OV-C - OUC/ Overvoltage during Operation/Deceleration
- Cause: 1. Deceleration time setting too short or load inertia is large 2. Power voltage varies widely
- Solution: 1. Set a longer deceleration time 2. Add a brake resistor or brake module 3. Add a reactor on the power input side 4. Increase inverter capacity
Err4 - Illegal Interruption of the CPU
- Cause: External noise interference
- Solution: If it occurs many times, send it back for repair
OVSP -OUsP/ Overspeed during Operation
- Cause: 1. Motor load too large or inverter capacity too small 2. Motor parameter error (vector mode) 3. Gain too large during vector mode operation 4. Current detection circuit failure
- Solution: 1. Increase acceleration/deceleration time (3-02/3-03) 2. Enter the correct motor parameter 3. Change Stator Resistance gain and Rotor resistance gain (14-0/14-1), we recommend reducing by 50~100, up to 0 4. Send it back to GE
OC - Overcurrent during Stop
- Cause: 1. Detection circuit failures 2. Poor connection for CT signal cable
- Solution: 1. Check the noise between the power line and motor line 2. Send the inverter back for repair
OL1 - Motor Overload
- Cause: 1. Heavy load 2. Settings of 0-02, 9-08~11 are not appropriate
- Solution: 1. Increase motor capacity 2. Properly set 0-02, 9-08~11
OL2 - Inverter Overload
- Cause: Heavy load
- Solution: Increase inverter capacity
OL3 - Over Torque
- Cause: 1. Heavy load 2. Settings of 9-14, 9-15 are insufficient
- Solution: 1. Increase inverter capacity 2. Properly set 9-14, 9-15
LV-C - LU-c/Low Voltage during Operation
- Cause: 1. Power voltage too low 2. Power voltage varies widely
- Solution: 1. Improve power quality or increase 2-01 value 2. Set a longer acceleration time 3. Increase inverter capacitor 4. Add a reactor on the power input side 5. Send the inverter back for repair
OH-C - Heat Insulation Temperature Too High during Operation
- Cause: 1. Heavy load 2. Ambient temperature too high or poor ventilation
- Solution: 1. Check if there is any problem with the load 2. Increase inverter capacity 3. Improve ventilation conditions
STP0 - Stop at Zero Speed
- Cause: Occurs when the preset frequency <0.1Hz
STP1 - Direct Start Failed
- Cause: 1. If the inverter is set as external terminal control mode (1-00=1) and direct start is disabled (2-05=0001), the inverter cannot be started when the operation switch is turned to ON after power is applied, and STP1 flashes (see the descriptions for 2-05). 2. Direct start is possible when 2-05=0000.
STP2 - Keypad Emergency Stop
- Cause: 1. If the inverter is set as external control mode (1-00=0001) and the Stop button is enabled (1-03=0000), pressing the Stop button during operation will stop the inverter according to the setting of 1-05. STP2 flashes after stopping. To restart the inverter, turn the operation switch to OFF and then back to ON. 2. When the inverter is in communication mode and the Stop button is enabled (1-03=0000), pressing the Stop button during operation will stop the inverter according to the setting of 1-05, and then STP2 flashes. The PC must send a Stop command and then a Start command to restart the inverter. 3. The Stop button cannot perform the emergency stop function when 1-03=0001
E.S. - External Emergency Stop
- Cause: The inverter ramps down and then stops when the external emergency stop signal is input through the multifunction input terminal, and then E.S
- b.b. - External Base Block
- Cause: The inverter stops immediately when an external base block is input through the multifunctional input terminal, and then b.b. flashes on and off (see explanations for 5-00~5-06).
- ATER - Automatic Adjustment Errors
- Cause: 1. Automatic adjustment failed due to motor data error 2. Emergency stop of the inverter during automatic adjustment
- PDER - PID Feedback Loss
- Cause: PID feedback loss detected
- LOC - Parameters and Frequency Already Locked
- Cause: 1. Attempt to change frequency/parameter while 3-17>0000 2. Attempt to reverse while 1-02=0001
- Solution: 1. Set 3-17=0000 2. Set 1-02=0000
- Err1 - Key Operation Error
- Cause: 1. Pressing ▲ or ▼ while 1-06>0 or when running at a preset speed. 2. Attempt to change a parameter that cannot be changed during operation (see parameter list).
- Solution: 1. ▲ or ▼ can only be used to change parameters when 1-06=0 2. Change the parameter during STOP
- Err2 - Parameter Setting Error
- Cause: 1. 3-01, 3-13 ± 3-16 or 3-14 ± 3-16 or 3-15 ± 3-16 out of range 2. 3-00≤3-01 3. Setting error during automatic adjustment (e.g., 1-00 ≠ 0, 1-06 ≠ 0)
- Solution: 1. Change 3-13~3-15 or 3-16 2. Set 3-00>3-01 to 1-00=0, 1-06=0 during automatic adjustment
- Err5 - Parameter Change Not Possible in Communication
- Cause: 1. Control command is given when communication is disabled 2. Change of 13-1~13-4 function during communication
- Solution: 1. Activate before communication 2. Set the relevant parameter before communication
- Err6 - Communication Failure
- Cause: 1. Wiring error 2. Communication parameter setting error 3. Total control error 4. Incorrect communication protocol
- Solution: 1. Check hardware and wiring 2. Check function 13-1~13-4
- Err7 - Parameter Conflict
- Cause: 1. Attempt to change function 15-0 or 15-7 2. Abnormal voltage and current detection circuit
- Solution: If it is not possible to reset the inverter, return it for repair
- Err8 - Factory Setting Error
- Cause: Factory setting is made while PLC is running
- Solution: Make factory setting before stopping the PLC
- EPr1 - Parameter Setting Error Copy Unit Failed
- Cause: 1. 3-18 set to 1.2 without connecting the copy unit 2. Copy unit failed 3. KW rating mismatch between copy unit and inverter
- Solution: 1. Change 3-18 2. Replace the copy unit
- EPr2 - Parameter Mismatch
- Cause: Parameters are checked
- Solution: 1. Rewrite 2. Replace the copy unit