IC697BEM761

The I/O Interface Module (IC697BEM761) is designed to provide an interface between the IC697 I/O modules and the IC600 programmable controller's I/O bus. Here's an overview of the module's key features and functions:

   Interfacing with IC600 PLC: Allows IC697 I/O modules to communicate with the IC600 controller's I/O bus.
   Rack-Dependent I/O References: The I/O references for each rack are dependent on its position in the system.
   Support for Multiple Racks: Each system can support up to eight racks, allowing for significant I/O expansion.

Functions:

   IC600 and IC697 I/O Compatibility: IC600 systems can be configured to include both IC600 I/O racks and IC697 I/O racks. IC660 I/O devices can also be part of the system.
   High Capacity: Each IC697 rack can be configured with either 128 (five-slot racks) or 256 I/O references (nine-slot racks). Up to 2000 addressable points can be used in a system.
   Rack and Slot Configuration: Each I/O slot in the IC697 rack is assigned 32 discrete I/O points. With a full rack of 32-point modules, the system can handle up to 2000 I/O points.

Module Operation:

The I/O Interface Module acts as a bridge between the IC697 I/O modules and the IC600 controller. It reads and writes data to the modules in its rack and sends this data back to the IC600 CPU via the I/O bus.

   Rack Number Assignment: Each rack is assigned a unique number, set using jumpers located behind the power supply on the rack backplane. This number determines the location in the I/O table to which the rack's I/O points are mapped.
   Complementary Addressing: For systems requiring more than 2000 I/O points, complementary addressing can be used, allowing up to 2000 inputs and 2000 outputs by assigning input and output modules to corresponding slots in complementary racks.

Installation:

   The I/O Interface Module is installed in slot 1 of an IC697 rack, with slots 2 to 9 reserved for I/O modules.
   Cable Connections: The module has two 37-pin connectors for interfacing with the IC600 I/O bus. The lower connector is for upstream communication, while the upper connector handles downstream connections.

LED Indicators:

There are three LEDs on the module to indicate system health:

   Rack LED: Indicates faults within the rack.
   Module LED: Shows faults in the I/O Interface Module.
   I/O Chain LED: Signals downstream rack faults or I/O bus failures.

Troubleshooting Using LEDs:

   If all LEDs are off, this could indicate a power failure or a problem with the power supply.
   If only the Rack LED is off, the fault may be with another module in the same rack, not the I/O Interface Module.
   If the Module and Rack LEDs are off, the issue is likely with the I/O Interface Module itself.

Removing the Module:

To remove the module, follow these steps:

   Ensure the rack is powered off.
   Firmly grasp the module and disengage it from the rack by pressing the plastic clips.
   Pull the module out of the connector and slide it out of the card guide.

This module plays a critical role in expanding the I/O capabilities of an IC600 PLC system by connecting IC697 I/O modules to the IC600 I/O bus, allowing for versatile configurations in industrial automation setups.

>> GE Fanuc IC697BEM761 User manual (pdf)

++ Other 90-30 PLC modules

----------

+ Ge-Fanuc 2 Homepage

+ Ge-Fanuc Contact (for Automation Mall)

+ About Ge-Fanuc

Reminder: GE Fanuc IC697BEM761 and other Ge-Fanuc modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 06.03.2013 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."