IC693CBL340
IC693CBL340 Interface Cable is approximately 19 inches (0.5 meters) long and is designed to connect the PTMPM Series 90-30 PLC module to the PTMIM DIN-rail mounted interface module. It is part of the IC693PTM100 assembly, which includes the PTMPM module, PTMIM interface module, and IC693CBL340 cable. This cable can also be ordered separately as a standalone item.
General Information for IC693CBL340/341 PTM Interface Cables:
These cables are specifically designed to link the PTM Processor Module (PTMPM), which is mounted on a Series 90-30 baseplate, with the PTM Interface Module (PTMIM) mounted on a DIN-rail. The IC693CBL340 cable is 19 inches (0.5 meters) in length, while the IC693CBL341 is 39 inches (1 meter) long.
Preliminary Information:
At the time of documentation, this information was preliminary and subject to change. The PTM was expected to be released in late 1999, and it's recommended to check with distributors for up-to-date details.
Cable Details:
The cables feature straight-through connections, meaning that pin 1 connects to pin 1, pin 2 connects to pin 2, etc. However, some pins do not have connections.
Each cable has a male plastic DB-25 connector on one end and a female plastic DB-25 connector on the other.
The cable is twisted-pair to minimize electrical noise and crosstalk between signals.
Warning:
The PTMIM board operates with hazardous voltages. Before installing, testing, or troubleshooting, you must refer to the PTM User's Manual (GFK-1734). Failure to follow these guidelines may lead to personal injury or equipment damage.
Connector Pin Assignments:
Here are the pin assignments for the IC693CBL340/341 cables:
Pin Number Signal Name and Function
1 VG+, Voltage Generator positive lead
2 IN+, Current Neutral positive lead
3 VA+, Voltage phase A positive lead
4 IA+, Current phase A positive lead
5 No Connection
6 VB+, Voltage phase B positive lead
7 IB+, Current phase B positive lead
8 VC+, Voltage phase C positive lead
9 IC+, Current phase C positive lead
10 Cable shield
11 No Connection
12 Frame Ground
13 No Connection
14 VG–, Voltage Generator negative lead
15 IN–, Current Neutral negative lead
16 VA–, Voltage phase A negative lead
17 IA–, Current phase A negative lead
18 No Connection
19 VB–, Voltage phase B negative lead
20 IB–, Current phase B negative lead
21 VC–, Voltage phase C negative lead
22 IC–, Current phase C negative lead
23 No Connection
24 No Connection
25 Frame Ground
Important Safety Notice:
These cables connect to circuits carrying hazardous voltages, so it's essential to use only factory-built cables to ensure both user safety and the protection of associated equipment.
+ IC693CBL340 User manual (pdf)