IC693CBL328 Overview and Connection Details

    Faceplate Connector to Terminal Block Connector: This cable features a 24-pin connection.
    Connection Method: It connects to two male 24-pin connectors (Fujitsu FCN–365P024–AU) located on the front of the module.
    Wiring: The wiring to field devices is accomplished using a cable that has a female connector on one end and stripped and tinned wires on the other end.

You can purchase pre-wired cables under catalog numbers IC693CBL327 and IC693CBL328, or you can build your own cables. For more details, refer to Appendix B.

Installation Guidelines:

    TTL Wiring Practices: When installing this module, standard TTL wiring practices should be followed.
    Noise Immunity: The length of the I/O control lines connected to the module must not exceed 30 meters, as signal attenuation limits the wiring length.

Pin Layout and Connections:

The detailed pin layout looks like this:

    I25, I27, I29, I31, COM, NC, 5V OUT, NC, continuing with other pins like I24, I22, I20, I18 in a structured layout.
    Positive and negative terminals are represented by -- + and + --.

Isolation Specifications:

If the 24V OUT pin is used to connect input devices in the field, the isolation specification changes:

    Field to Backplane (optical) and frame ground: 50 VAC continuous, 500 VAC for 1 minute.

TTL Wiring and Logic Configuration:

For compatibility with TTL outputs, the negative logic configuration is recommended, as shown in the wiring diagram.


>> IC693CBL328 cables User manual (pdf)

++ Other 90-30 PLC modules

----------

+ Ge-Fanuc 2 Homepage

+ Ge-Fanuc Contact (for Automation Mall)

+ About Ge-Fanuc

Reminder: IC693CBL328 and other Ge-Fanuc modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 06.03.2013 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."