    Cable Length Limitation:
        The total length of the cable connecting all baseplates in a system using remote baseplates must not exceed 700 feet. This distance limitation ensures proper communication and power distribution across the system.

    CPU Dependency:
        A remote baseplate cannot function independently. It must be connected to a system that has a CPU. The CPU can reside in a PLC or a Personal Computer equipped with a Personal Computer Interface Card.

    Built-in Isolation for Stability:
        The remote baseplate includes built-in isolation between the +5V logic supply used by the I/O modules in the remote baseplate and the supply for the interface circuit associated with the I/O Bus Expansion Interface. This isolation helps prevent issues related to unbalanced ground conditions, which can cause communication problems.

    Maximum Number of Remote Baseplates:
        The maximum number of remote baseplates allowed per system depends on the type of CPU used:
            CPUs 331, 340, 341: Support up to 4 remote baseplates.
            CPUs 350 and higher: Support up to 7 remote baseplates.

    I/O Bus Expansion Connector:
        Each remote baseplate is equipped with a 25-pin female D-type Expansion Connector, located on the right side. This connector allows the baseplate to be connected to other remote or CPU baseplates, thus extending the system’s capacity.

    Available Sizes:
        Remote baseplates come in two sizes:
            5-slot version (IC693CHS398)
            10-slot version (IC693CHS393), as shown in the image.

    Intelligent Module Limitations:
        Remote baseplates do not support certain intelligent option modules, which must be installed in the CPU baseplate. These modules include:
            PCM (Programmable Coprocessor Module)
            ADC (Analog to Digital Converter)
            BEM330 (Bus Expansion Module)
            CMM (Communications Module)
        All other I/O and option modules can be installed in any baseplate, including remote baseplates.

    Physical Compatibility:
        Remote baseplates are the same physical size, use the same type of power supplies, and support the same I/O and option modules as Expansion baseplates, ensuring system compatibility.

    Rack Number Selection DIP Switch:
        Each remote baseplate includes a Rack Number Selection DIP switch, allowing you to assign a unique rack number to each baseplate within the system. This enables the CPU to correctly identify and communicate with the remote baseplates.

General Overview of Remote Baseplates:

The IC693CHS393 10-Slot Remote Baseplate extends the capacity of the Series 90-30 PLC system by providing additional slots for I/O and option modules in remote locations. However, the baseplate requires a connection to a CPU baseplate for communication. Its built-in isolation feature helps prevent ground imbalance problems, ensuring reliable performance in distributed systems.

>> IC693CHS393 User manual (pdf)

++ Other 90-30 PLC modules

----------

+ Ge-Fanuc 2 Homepage

+ Ge-Fanuc Contact (for Automation Mall)

+ About Ge-Fanuc

Reminder: IC693CHS393 and other Ge-Fanuc modules are available for sale at Otomasyon AVM. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 06.03.2013