GE-AF-600 FP fault codes 4
Hi everyone,
Warning 66, Heat Sink Temperature Low
- Cause: The drive is too cold to operate. This warning is based on the temperature sensor in the IGBT module.
- Solution: Increase the ambient temperature of the unit. Additionally, a continuous amount of current can be provided to the drive when the motor is stopped, by setting B-00 DC Holding Current to 5% and setting the Function in H-80 Stop Function.
Alarm 67, Option Module Configuration Changed
- Cause: One or more options have been added or removed since the last power down.
- Solution: Ensure the configuration change was intentional and reset the unit.
Alarm 69, Power Card Temperature
- Cause: The temperature sensor on the power card is either too hot or too cold.
- Solution: Ensure the ambient operating temperature is within limits. Check for clogged filters. Check fan operation. Check the power card.
Alarm 70, Illegal Drive Configuration
- Cause: The control card and power card are incompatible. Contact your supplier to check compatibility with the type code on the unit plate and the part numbers of the cards.
Alarm 80, Unit Reset to Factory Settings
- Cause: Parameter settings were reset to factory settings after manual reset.
- Solution: Reset the unit and clear the alarm.
Alarm 92, No Flow
- Cause: A no-flow condition was detected in the system.
- Solution: AP-23 No Flow Function is set for the alarm. Troubleshoot the system and reset the drive after the fault is cleared.
Alarm 93, Dry Pump
- Cause: A no-flow condition while the drive is operating at high speed may indicate a dry pump.
- Solution: AP-26 Dry Pump Function is set for the alarm. Troubleshoot the system and reset the drive after the fault is cleared.
Alarm 94, End of Curve
- Cause: The feedback is lower than the setpoint. This may indicate a leak in the system.
- Solution: AP-50 End of Curve Function is set for the alarm. Troubleshoot the system and reset the drive after the fault is cleared.
Alarm 95, Broken Belt
- Cause: The torque is below the torque level set for no load, which may indicate a broken belt.
- Solution: AP-60 Broken Belt Function is set for the alarm. Troubleshoot the system and reset the drive after the fault is cleared.
Alarm 96, Start Delayed
- Cause: The start of the motor was delayed due to short circuit protection.
- Solution: AP-76 Time Between Starts is enabled. Troubleshoot the system and reset the drive after the fault is cleared.
Warning 97, Stop Delayed
- Cause: The stop of the motor was delayed due to short circuit protection.
- Solution: AP-76 Time Between Starts is enabled. Troubleshoot the system and reset the drive after the fault is cleared.
Warning 98, Clock Error
- Cause: Time not set or RTC clock is faulty.
- Solution: Reset the time in K-70 Date and Time.
Warning 200, Fire Mode
- Cause: This indicates that the drive is operating in fire mode. The warning is cleared when fire mode is removed. Look at fire mode data in the alarm log.
Warning 201, Fire Mode Active
- Cause: This indicates that the drive has entered fire mode.
- Solution: Remove the warning by cutting power to the unit. Look at fire mode data in the alarm log.
Warning 202, Fire Mode Limits Exceeded
- Cause: While operating in fire mode, one or more alarm conditions that would normally disable the unit are ignored. Operating in this condition voids the unit warranty.
- Solution: Remove the warning by cutting power to the unit. Look at fire mode data in the alarm log.
Warning 203, Missing Motor
- Cause: In a drive operating with multiple motors, a load condition has been detected. This may indicate a missing motor.
- Solution: Inspect to ensure the system is operating correctly.
Warning 204, Locked Rotor
- Cause: In a drive operating with multiple motors, an overload condition has been detected. This may indicate a locked rotor.
- Solution: Inspect to ensure the motor is operating correctly.
Warning 250, New Spare Part
- Cause: A component has been replaced in the drive.
- Solution: Reset the drive for normal operation.
Warning 251, New Type Code
- Cause: The power card or other components have been replaced and the type code has changed.
- Solution: Reset to remove the warning and continue normal operation.
+ Ge VFD User Manuals >>
+ Ge AF-6 (600,650..) Fault index >>
+ Ge AF-6 (600,650..) Fault Codes 1 >>
+ Ge AF-6 (600,650..) Fault Codes 2 >>
+ Ge AF-6 (600,650..) Fault Codes 3 >>
+ Ge AF-6 (600,650..) Fault Codes 4 >>
+ General Electric 2. Main page >
+ VFD Homepage >
"* The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us." 22.01.2013