GE-AF-600 FP fault codes 3

Hi everybody,

Alarm 45, Ground Fault 2

- Cause: Ground (earth) fault at startup.
- Solution: Check correct grounding (earthing) and loose connections. Check correct wire size. Check for short circuits or leakage currents in motor cables.

Alarm 46, Power Card Supply

- Cause: The supply in the power card is out of range. There are three power supplies produced by the switching mode power supply (SMPS) in the power card: 24V, 5V, +/- 18V. When supplied with three-phase main voltage, all three sources are monitored.
- Solution: Check for a faulty power card. Check for a faulty control card. Check for a faulty option card. If a 24V DC power supply is used, verify the proper supply power.

Warning 47, 24V Supply Low

- Cause: 24 V DC is measured in the control card. The external 24V DC backup power supply may be overloaded, otherwise contact your GE supplier.

Warning 48, 1.8V Supply Low

- Cause: The 1.8V DC supply used in the control card is outside the allowed limits. The power supply is measured in the control card. Check for a faulty control card. If an option card is present, check for an overvoltage condition.

Warning 49, Speed Limit

- Cause: If the speed is not within the range specified in F-18 and F-17, the drive displays a warning. If the speed is below the specified limit in H-36 Low Speed Cruise [RPM] (other than startup or stopping), the drive is disabled.

Alarm 50, Auto Tuning Calibration Failed

- Solution: Contact your GE supplier or GE Service Department.

Alarm 51, Auto Tuning U nom and I nom Check

- Cause: The settings for motor voltage, motor current, and motor power are incorrect. Check the settings in parameters P-02, P-03, P-06, P-07, F-04, and F-05.

Alarm 52, Auto Tuning Low I nom

- Cause: The motor current is too low. Check the setting in F-43 Current Limit.

Alarm 53, Auto Tuning Motor Too Large

- Cause: The motor is too large for Auto Tuning to operate.

Alarm 54, Auto Tuning Motor Too Small

- Cause: The motor is too small for Auto Tuning to operate.

Alarm 55, Auto Tuning Parameter Out of Range

- Cause: The parameter values of the motor are outside the acceptable range. Auto tuning does not work.

Alarm 56, Auto Tuning Interrupted by User

- Cause: Auto tuning was interrupted by the user.

Alarm 57, Auto Tuning Timeout

- Solution: Try restarting the auto tuning. Repeated restarts can overheat the motor.

Alarm 58, Auto Tuning Internal Error

- Solution: Contact your GE supplier.

Warning 59, Current Limit

- Cause: The current is higher than the value in F-43 Current Limit. Ensure the Motor data in parameters P-02, P-03, P-06, P-07, F-04, and F-05 are correctly set. Possibly increase the current limit. Ensure the system can safely operate with a higher limit.

Warning 60, External Lockout

- Cause: A digital input signal indicates a fault condition outside the drive. An external lockout has ordered the drive to be disabled. Clear the external fault condition. To continue normal operation, apply 24V DC to the terminal programmed for external lockout. Reset the drive.

Warning 62, Output Frequency at Maximum Limit

- Cause: The output frequency has reached the value set in F-03 Max Output Frequency 1. Check the application and determine the cause. Possibly increase the output frequency limit. Ensure the system can safely operate at a higher output frequency. The warning is cleared when the output drops below the maximum limit.

Warning/Alarm 65, Control Card Over Temperature

- Cause: The cutoff temperature for the control card is 80° C.
- Solution: Ensure the ambient operating temperature is within limits. Check for clogged filters. Check fan operation. Check the control card.


+ Ge VFD User Manuals >>

+ Ge AF-6 (600,650..) Fault index >>

+ Ge AF-6 (600,650..) Fault Codes 1 >>

+ Ge AF-6 (600,650..) Fault Codes 2 >>

+ Ge AF-6 (600,650..) Fault Codes 3 >>

+ Ge AF-6 (600,650..) Fault Codes 4 >>

+ General Electric 2. Main page >

+ VFD Homepage > 


-

"* The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us." 22.01.2013