Alarm 15, Hardware Mismatch
+ An installed option is not working with the current control card hardware or software.
- Record the values of the following parameters and contact your GE supplier: ID-40 Drive Type, ID-41 Power Section, ID-42 Voltage, ID-43 Software Version, ID-45 Actual Type Code Series, ID-49 SW ID Control Card, ID-50 SW ID Power Card, ID-60 Installed Option, ID-61 Option SW Version (for each option slot).
Alarm 16, Short Circuit
+ There is a short circuit in the motor or motor wiring.
- Cut the power to the drive and repair the short circuit.
Warning/Alarm 17, Control Word Timeout
+ There is no communication to the drive.
- Check the connections in the serial communication cable. Increase O-03 Control Word Timeout Time. Check the operation of the communication equipment. Verify a proper installation based on EMC requirements.
Alarm 18, Startup Failed
+ The speed did not exceed the AP-70 Compressor Start Maximum Speed [RPM] within the allowed time at startup (as set in AP-72 Compressor Start Maximum Time to Failure). This could be due to a blocked motor.
Warning 23, Internal Fan Failure
+ The fan warning function is an additional protective function that checks whether the fan is working/mounted. The fan warning can be disabled in SP-53 Fan Monitor ([0] Disabled).
- Check the correct operation of the fan. Cut the power to the drive and check if the fan operates briefly at startup. Check the heat insulation and sensors on the control card.
Warning 24, External Fan Failure
+ The fan warning function is an additional protective function that checks whether the fan is working/mounted. The fan warning can be disabled in SP-53 Fan Monitor ([0] Disabled).
- Check the correct operation of the fan. Cut the power to the drive and check if the fan operates briefly at startup. Check the heat insulation and sensors on the control card.
Alarm 29, Heat Insulation Temperature
+ The maximum temperature of the heat insulation has been exceeded. The temperature fault is not reset until the temperature drops below a certain heat insulation temperature. The disable and reset points differ according to the drive power size.
- Check the following conditions: Ambient temperature too high, Motor cable too long, Incorrect air gap above and below the drive, Blocked air flow around the drive, Damaged heat insulation fan, Dirty heat insulation.
Alarm 30, Motor Phase U Missing
+ Motor phase U is missing between the drive and the motor.
- Cut the power to the drive and check motor phase U.
Alarm 31, Motor Phase V Missing
+ Motor phase V is missing between the drive and the motor.
- Cut the power to the drive and check motor phase V.
Alarm 32, Motor Phase W Missing
+ Motor phase W is missing between the drive and the motor.
- Cut the power to the drive and check motor phase W.
Alarm 33, Sudden Current Fault
+ Too many trips have occurred in a short time. Wait for the unit to cool down to operating temperature.
Warning/Alarm 34, Communication Fault
+ The network in the communication option card is not working.
Warning/Alarm 36, Main Fault
+ This warning/alarm becomes active if the supply voltage to the drive is lost and SP-10 Line Fault [0] Function None is not set. Check the fuses to the drive and the main power supply to the unit.
Alarm 38, Internal Fault
+ When an internal fault occurs, a code number defined in the table below is displayed.
- Cut the power. Ensure the option is correctly installed. Check for loose or missing wiring. You may need to contact your GE supplier or service department. Note the code number for further troubleshooting instructions.
Alarm 39, Heat Insulation Sensor
+ There is no feedback from the heat insulation temperature sensor. The signal of the IGBT thermal sensor is not present in the power card. The problem could be in the power card, the gate driver card, or the ribbon cable between the power card and the gate driver card.
Warning 40, Overload of Digital Output Terminal 27
+ Check the load connected to terminal 27 or remove the short circuit connection. Check E-00 Digital I/O Mode and E-51 Terminal 27 Mode.
Warning 41, Overload of Digital Output Terminal 29
+ Check the load connected to terminal 29 or remove the short circuit connection. Check E-00 Digital I/O Mode and E-52 Terminal 29 Mode.
Warning 42, Overload of Digital Output at X30/6 or Overload of Digital Output at X30/7
+ For X30/6, check the load connected to X30/6 or remove the short circuit connection. Check E-56 Term X30/6 Digi Output (OPCGPIO). For X30/7, check the load connected to X30/7 or remove the short circuit connection. Check E-57 Term X30/7 Digi Output (OPCGPIO).