GE-AF-600 FP fault codes 1
General Electric AF-600 FP Series Drive Error Messages
Warning 1, 10 Volt Low
- Cause: Control card voltage from terminal 50 is below 10 V. Remove some loads from terminal 50, as the 10 V source is overloaded. Max. 15 mA or minimum 590 Ω.
+ Solution: Remove wiring from terminal 50. If the warning clears, the problem is in the customer wiring. If the warning does not clear, replace the control card.
Warning/Alarm 2, Live Zero Error
- Cause: This warning or alarm appears only if programmed by the user in the AN-01 Live Zero Timeout Function. The signal in one of the analog inputs is less than 50% of the programmed minimum value for that input. This condition could be due to broken wiring or a faulty device sending the signal.
+ Solution: Check all connections at the analog input terminals. Control card terminals 53 and 54 for signals, terminal 55 for common. OPCGPIO terminals 11 and 12 for signals, terminal 10 for common. Ensure the drive programming and key settings match the type of analog signal. Perform an Input Terminal Signal Test.
Warning/Alarm 4, Main Phase Loss
- Cause: A phase is missing on the supply side, or the main voltage imbalance is too high. This message also appears for a fault in the input rectifier in the drive. Options are programmed in the SP-12 Function in Line Imbalance.
+ Solution: Check the supply voltage and supply currents to the drive.
Warning 5, DC Link Voltage High
- Cause: The intermediate circuit voltage (DC) is above the high voltage warning limit. The limit depends on the drive voltage rating. The unit is still active.
Warning 6, DC Link Voltage Low
- Cause: The intermediate circuit voltage (DC) is below the low voltage warning limit. The limit depends on the drive voltage rating. The unit is still active.
Warning/Alarm 7, DC Over Voltage
- Cause: If the intermediate circuit voltage limit is exceeded, the drive is disabled after a certain period.
+ Solution: Connect a braking resistor. Extend the ramp time. Change the ramp type. Activate functions in B-10 Brake Function. Increase the delay time in SP-26 Drive Fault.
Warning/Alarm 8, DC Under Voltage
- Cause: If the intermediate circuit voltage (DC link) falls below the under voltage limit, the drive checks if a 24V DC backup supply is connected. If the 24V DC backup supply is not connected, the drive is disabled after a fixed time delay. The time delay varies with the unit size.
+ Solution: Ensure the supply voltage matches the drive voltage. Perform an input voltage test. Perform a soft charge circuit test.
Warning/Alarm 9, Inverter Overload
- Cause: The drive is about to be cut off due to overload (too high current, too long duration). Electronics give a warning at 98% for thermal inverter protection and are disabled while giving an alarm at 100%. The drive cannot be reset until the counter drops below 90%. The fault is the drive being overloaded by more than 100%.
+ Solution: Compare the output current shown on the keypad with the drive's nominal current. Compare the output current shown on the keypad with the measured motor current. Display the Thermal Drive Load on the keypad and monitor the value. The counter should increase when the drive operates above the continuous current rating. The counter should decrease when the drive operates below the continuous current rating. If a high switching frequency is required, see the rating section in the Design Guide for more details.
Warning/Alarm 10, Motor Overload Temperature
- Cause: The motor is too hot according to electronic thermal protection. Select in F-10 Electronic Overload whether the drive will give a warning or an alarm when the counter reaches 100%. The fault is the motor being overloaded by more than 100%.
+ Solution: Check if the motor is overheating. Check if the motor is mechanically overloaded. Ensure the motor current set in P-03 Motor Current is correct. Ensure the Motor data in parameters P-02, P-03, P-06, P-07, F-04, and F-05 are correctly set. If an external fan is used, ensure it is selected in F-11 Motor External Fan. Running Auto Tuning in P-04 Auto Tuning can adjust the drive more accurately to the motor and reduce thermal load.
Warning/Alarm 11, Motor Thermistor Over Temperature
- Cause: The thermistor connection may be broken. Select in F-10 Electronic Overload whether the drive will give a warning or an alarm.
+ Solution: Check if the motor is overheating. Check if the motor is mechanically overloaded. If terminal 53 or 54 is used, ensure the thermistor is correctly connected between terminal 53 or 54 (analog voltage input) and terminal 50 (+10V source), and the terminal key is set to voltage for 53 or 54. Ensure F-12 Motor Thermistor Input selects terminal 53 or 54. If digital inputs 18 or 19 are used, ensure the thermistor is correctly connected between terminal 18 or 19 (digital input PNP only) and terminal 50, and F-12 Motor Thermistor Input selects terminal 18 or 19.
Warning/Alarm 12, Torque Limit
- Cause: The torque has exceeded the value in F-40 Torque Limiter (Driving) or F-41 Torque Limiter (Braking). SP-25 Torque Limit Delay Time can change this from just a warning condition to a warning followed by an alarm condition.
+ Solution: If the motor torque limit is exceeded during ramp up, extend the ramp up time. If the generator torque limit is exceeded during ramp down, extend the ramp down time. If the torque limit occurs while running, likely increase the torque limit. Ensure the system can safely operate at a higher torque. Check for applications pulling excessive current on the motor.
Warning/Alarm 13, Over Current
- Cause: The inverter's peak current limit (approximately 200% of nominal current) has been exceeded. The warning lasts for about 1.5 seconds, after which the drive is disabled and an alarm is given. This fault can occur due to shock loading or rapid acceleration with high inertial loads. If extended mechanical brake control is selected, the disable can be reset from outside.
+ Solution: Cut the power and check if the motor shaft can be turned. Ensure the motor size matches the drive. Check parameters P-02, P-03, P-06, P-07, F-04, and F-05 for correct motor data.
Alarm 14, Ground (Earth) Fault
- Cause: There is current from the output phases to the ground in the cable between the drive and the motor, or in the motor itself.
+ Solution: Cut the power to the drive and repair the ground fault. Check the motor for a ground fault by measuring the resistance between the motor ends and the motor to the ground with a megohmmeter.
+ Ge VFD User Manuals >>
+ Ge AF-6 (600,650..) Fault index >>
+ Ge AF-6 (600,650..) Fault Codes 1 >>
+ Ge AF-6 (600,650..) Fault Codes 2 >>
+ Ge AF-6 (600,650..) Fault Codes 3 >>
+ Ge AF-6 (600,650..) Fault Codes 4 >>