G110 Fault codes 3

A0501 Current Limit:
This warning is caused by a motor power that does not correspond to the inverter power, motor leads that are too long, or earth faults. To diagnose and remedy the warning, the following checks should be performed:

    Ensure that the motor power and inverter power match
    Confirm that the cable length limits are not exceeded
    Check for short-circuits or earth faults in the motor cable and motor
    Ensure that the motor parameters match the motor in use
    Check that the value of the stator resistance is correct
    Ensure that the motor is not obstructed or overloaded
    Increase the ramp-up time (P1120)
    Reduce the starting boost level (P1312)

A0502 Overvoltage Limit:
This warning is caused by an overvoltage limit that has been reached, which can occur during ramp down if the Vdc controller is disabled (P1240 = 0). To diagnose and remedy the warning, if the warning is displayed permanently, check the drive input voltage.

A0503 Undervoltage Limit:
This warning is caused by a main supply failure or a main supply and DC-link voltage (r0026) that are below the specified limit. To diagnose and remedy the warning, check the main supply voltage.

A0505 Inverter I2T:
This warning is caused by the warning level being exceeded, and the current will be reduced if parameterized (P0610 = 1). To diagnose and remedy the warning, check that the duty cycle is within specified limits.

A0511 Motor Over Temperature I2T:
This warning is caused by a motor that is overloaded or a load duty cycle that is too high. To diagnose and remedy the warning, the following checks should be performed:

    Ensure that the motor I2t time constant (P0611) is set to the appropriate value
    Ensure that the motor I2t overload warning level (P0614) is set to a suitable level

A0910 Vdc-max Controller de-activated:
This warning occurs if the main supply voltage is permanently too high, if the motor is driven by an active load and goes into regenerative mode, or at very high load inertias when ramping down. To diagnose and remedy the warning, the following checks should be performed:

    Ensure that the input voltage lies within the range
    Ensure that the load matches the specifications

If the above steps do not resolve the issue, it may be necessary to consult with a qualified electrical engineer or technician for further diagnosis and repair.


+ G110 User Manuals 

+ G110 Error Index 

+ G110 Error Codes 2 

+ G110 Error Codes 3 

++ Siemens Homepage 


Reminder: Siemens G110 and other Siemens drive are available for sale at Otomasyon Mall. Please note that some devices are used products, so take this into consideration when purchasing. Once these products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. (04.09.2011)

Please Note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please feel free to share them with us!