G110 Fault codes 2
F0001 Overcurrent: This message is related to an overcurrent fault in an electrical system, possibly in a motor or an inverter. The fault could be caused by several factors, including a mismatch between the motor power and the inverter power, a short circuit in the motor lead, or earth faults. To diagnose and remedy the fault, the following checks should be performed:
✔ Verify that the motor power and inverter power match
✔ Check that the cable length limits are not exceeded
✔ Ensure that the motor cable and motor are free of short-circuits and earth faults
✔ Confirm that the motor parameters match the motor in use
✔ Ensure that the value of the stator resistance is correct
✔ Check that the motor is not obstructed or overloaded
✔ Increase the ramp-up time
✔ Reduce the starting boost level
✔ Check the fault value r0949 to determine if the trip was hardware or software generated.
If the above steps do not resolve the issue, it may be necessary to consult with a qualified electrical engineer or technician for further diagnosis and repair.
F0002 Overvoltage: This message is related to an overvoltage fault in an electrical system. The fault could be caused by a main supply voltage that is too high, or if the motor is in regenerative mode. Regenerative mode can occur when the motor is driven by a fast ramp down or an active load. To diagnose and remedy the fault, the following checks should be performed:
✔ Verify that the supply voltage is within the limits indicated on the rating plate
✔ Ensure that the Vdc controller is enabled (P1240) and properly parameterized
✔ Confirm that the ramp-down time (P1121) matches the inertia of the load
✔ Ensure that the required braking power is within specified limits
✔ Check the fault value r0949 to determine if the trip was hardware or software generated.
It is important to note that a higher inertia requires a longer ramp time. If the above steps do not resolve the issue, it may be necessary to consult with a qualified electrical engineer or technician for further diagnosis and repair.
F0003 Undervoltage STOP II:
This fault is caused by either a main supply failure or a shock load outside specified limits. To diagnose and remedy the fault, the following checks should be performed:
✔ Check the supply voltage
✔ Check the fault value r0949 to determine if the trip was hardware or software generated.
F0004 Inverter Over Temperature STOP II:
This fault is caused by an overloaded inverter, inadequate ventilation, a pulse frequency that is too high, or an ambient temperature that is too high. To diagnose and remedy the fault, the following checks should be performed:
✔ Check if the load or load duty cycle is too high
✔ Ensure that the motor power and inverter power match
✔ Set the pulse frequency to the default value
✔ Check if the ambient temperature is too high
F0005 Inverter I2T STOP II:
This fault is caused by an overloaded inverter or a duty cycle that is too demanding. To diagnose and remedy the fault, the following checks should be performed:
✔ Ensure that the load duty cycle is within specified limits
✔ Ensure that the motor power and inverter power match
F0011 Motor Over Temperature I2T STOP II:
This fault is caused by a motor that is overloaded. To diagnose and remedy the fault, the following checks should be performed:
✔ Check if the load or load duty cycle is too high
✔ Ensure that the motor thermal time constant is correct
✔ Ensure that the motor I2t warning level matches
F0051 Parameter EEPROM Fault STOP II:
This fault is caused by a read or write failure while accessing the EEPROM. To diagnose and remedy the fault, the following steps should be performed:
✔ Perform a factory reset and new parameterization
✔ Change the drive
F0052 Power Stack Fault STOP II:
This fault is caused by a read failure for power stack information or invalid data. To diagnose and remedy the fault, change the drive.
If the above steps do not resolve the issue, it may be necessary to consult with a qualified electrical engineer or technician for further diagnosis and repair.
F0055 BOP-EEPROM Fault STOP II:
This fault is caused by a read or write failure while saving non-volatile parameters to the EEPROM on the BOP during parameter cloning. To diagnose and remedy the fault, the following steps should be performed:
✔ Perform a factory reset and new parameterization
✔ Change the BOP
F0056 BOP not fitted STOP II:
This fault is caused by attempting to initiate parameter cloning without a BOP fitted. To diagnose and remedy the fault, fit the BOP and try again.
F0057 BOP fault STOP II:
This fault is caused by attempting to initiate parameter cloning with an empty or invalid BOP. To diagnose and remedy the fault, download to the BOP or replace the BOP.
F0058 BOP contents incompatible STOP II:
This fault is caused by attempting to initiate parameter cloning with a BOP created on another type of drive. To diagnose and remedy the fault, download to the BOP from this type of drive.
F0060 Asic Timeout STOP II:
This fault is caused by an internal communications failure. To diagnose and remedy the fault, the following steps should be performed:
✔ If the fault persists, change the inverter
✔ Contact the Service Department
✔ Check the fault value r0949 to determine if the trip was hardware or software generated.
F0072 USS Setpoint Fault STOP II:
This fault is caused by a lack of setpoint values from the USS during the telegram off time. To diagnose and remedy the fault, check the USS master.
F0085 External Fault STOP II:
This fault is caused by an external fault triggered via terminal inputs. To diagnose and remedy the fault, disable the terminal input for the fault trigger.
If the above steps do not resolve the issue, it may be necessary to consult with a qualified electrical engineer or technician for further diagnosis and repair.
F0100 Watchdog Reset STOP II:
This fault is caused by a short power dip or a software error. To diagnose and remedy the fault, if the trip occurs after a short power dip, there is no problem with the inverter itself. However, if the trip occurs without a loss of power during normal operation, the Service Department should be contacted.
F0101 Stack Overflow STOP II:
This fault is caused by a software error or a processor failure. To diagnose and remedy the fault, run self-test routines.
If the above steps do not resolve the issue, it may be necessary to consult with a qualified electrical engineer or technician for further diagnosis and repair.
++ Siemens Homepage
Reminder: Siemens G110 and other Siemens drive are available for sale at Otomasyon Mall. Please note that some devices are used products, so take this into consideration when purchasing. Once these products are out of stock, new ones will not be restocked.
The information above is based on general knowledge and does not
guarantee accuracy. For more detailed and precise information, it is
recommended to refer to the relevant device’s user manual. (04.09.2011)