G110 Fault codes

Warnings:

- Only Siemens Service, authorized repair centers, or trained personnel should carry out repairs.
- Use only genuine Siemens parts for replacements.
- Be careful of electric shock. The DC link capacitors stay charged for five minutes after power is removed. Don't open the equipment until 5 minutes have passed.

Troubleshooting with the Standard Inverter LED:

- Inverter Off/No Supply: No LED lit.
- Power On/Ready: LED flashes briefly (200 ms On, 800 ms Off).
- Inverter Running OK: LED stays on steadily.
- General Warning: LED flashes slowly (800 ms On, 200 ms Off).
- Fault Condition: LED flashes evenly (500 ms On, 500 ms Off).

Troubleshooting with the BOP (Basic Operator Panel):

* If there's a fault or warning code, check the Faults and Warning section in the SINAMICS G110 Parameter List.
    If the motor doesn't start:
- Make sure P0010 = 0.
- Check for a valid ON signal.
- Ensure P0700 is set correctly for your control method (BOP, digital input, or USS input).
- Make sure the setpoint is present (0 to 10V on Terminal 9) or entered correctly in the parameters.
    If the motor doesn't run after changing parameters:
+ Set P0010 = 30.
+ Set P0970 = 1.
- Press the reset button to reset the inverter to factory defaults.
- Use a switch between terminals 3 and 6 on the control board.
- The inverter should now run according to the setpoint from the analogue input or USS serial link.

Checking for an ON Command:

* If you've set DIN0 on terminal 3 for an ON command:
- Connect the BOP to the inverter.
+ Set P0003 = 3.
+ Select parameter r0722.
- The display will show active bits. If the lower mark on the right-hand side is on, it means DIN0 is active high (ON command is present).
- If the active high bit is not present, check the hardware configuration to ensure DIN0 is set up for the ON command.
    For ON/OFF control via RS485 bus (USS protocol), check bit 02 of status word 1 (r0052) for the relevant bit.

Remember, always ensure motor data matches the inverter's power range and voltage. If you encounter any persistent issues, consider contacting Siemens Service for assistance.


 F0001 Overcurrent: Motor power does not match inverter power, short circuit, or earth faults.

 F0002 Overvoltage: Main supply voltage too high or motor in regenerative mode.

 F0003 Undervoltage: Main supply failed or shock load outside limits.

 F0004 Inverter Over Temperature: Inverter overloaded, inadequate ventilation, pulse frequency too high, or ambient temperature too high.

 F0005 Inverter I2T: Inverter overloaded or duty cycle too demanding.

 F0011 Motor Over Temperature I2T: Motor overloaded.

 F0051 Parameter EEPROM Fault: Read/write failure to EEPROM.

 F0052 Power Stack Fault: Read failure for power stack information.

 F0055 BOP-EEPROM Fault: Read/write failure to EEPROM on BOP during parameter cloning.

 F0056 BOP not fitted: Trying to initiate parameter cloning without BOP fitted.

 F0057 BOP fault: Parameter cloning with empty or invalid BOP.

 F0058 BOP contents incompatible: Parameter cloning with BOP created on another type of drive.

 F0060 Asic Timeout: Internal communications failure.

 F0072 USS Setpoint Fault: No setpoint values from USS during telegram off time.

 F0085 External Fault: External fault triggered via terminal inputs.

 F0100 Watchdog Reset: Short power dip or software error.

 F0101 Stack Overflow: Software error or processor failure.

Alarm Messages:

 A0501 Current Limit: Motor power does not match inverter power, leads are too long, or earth faults.

 A0502 Overvoltage Limit: Overvoltage limit reached, can occur during ramp down.

 A0503 Undervoltage Limit: Main supply failed or voltage below specified limit.

 A0505 Inverter I2T: Warning level exceeded, current may be reduced.

 A0511 Motor Over Temperature I2T: Motor overloaded or duty cycle too high.

 A0910 Vdc-max Controller de-activated: Main supply voltage permanently too high or motor driven by an active load.

 A0911 Vdc-max Controller active: Controller active to keep DC-link voltage within limits.

 A0920 ADC parameters not set properly: ADC parameters set to identical values.

 A0923 Both JOG Left and JOG Right are requested: Both JOG directions requested simultaneously.


+ G110 User Manuals 

+ G110 Error Index 

+ G110 Error Codes 2 

+ G110 Error Codes 3 

++ Siemens Homepage 


Reminder: Siemens G110 and other Siemens drive are available for sale at Otomasyon Mall. Please note that some devices are used products, so take this into consideration when purchasing. Once these products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. (04.09.2011)

Please Note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please feel free to share them with us!