FC51 fault codes 2
Hi everyone,
This passage describes how warnings and alarms are indicated and what actions can be taken to reset them. A warning is indicated by an LED and a code on the display, and remains active until the cause is resolved. An alarm results in the frequency converter tripping and requires resetting once the cause has been rectified. Alarms can be reset in four ways, including via a manual reset, digital input, or serial communication.
If
an alarm cannot be reset, it may be trip-locked, in which case the
mains supply must be switched off before it can be reset. Table 6.1
provides codes for warnings and alarms, and in some cases, it can
specify whether a warning or alarm is to be displayed. After an alarm or
trip, the motor coasts and both the warning and alarm flash. Once the
problem is resolved, only the alarm continues flashing.
AL 30: Motor phase U missing The error message you provided indicates a "Motor phase U missing" issue, which occurs when there is a missing phase in the motor circuit. This can be caused by a number of factors, such as a faulty connection, a damaged wire, or a malfunctioning component. To resolve this issue, you should first check the motor circuit and ensure that all connections are properly installed and secure. It may also be necessary to use a multimeter to test the continuity of the wires and identify any areas that may be damaged or compromised.
AL 31: Motor phase V missing The error message you provided indicates a "Motor phase V missing" issue, which occurs when there is a missing phase in the motor circuit. This can be caused by a number of factors, such as a faulty connection, a damaged wire, or a malfunctioning component. To resolve this issue, you should first check the motor circuit and ensure that all connections are properly installed and secure. It may also be necessary to use a multimeter to test the continuity of the wires and identify any areas that may be damaged or compromised.
AL 32: Motor phase W missing The error message you provided indicates a "Motor phase W missing" issue, which occurs when there is a missing phase in the motor circuit. This can be caused by a number of factors, such as a faulty connection, a damaged wire, or a malfunctioning component. To resolve this issue, you should first check the motor circuit and ensure that all connections are properly installed and secure. It may also be necessary to use a multimeter to test the continuity of the wires and identify any areas that may be damaged or compromised.
AL 38: Internal fault The error message you provided indicates an "Internal fault" issue, which could be caused by a number of factors related to the internal components or systems of the device. To resolve this issue, it is recommended to contact your local Danfoss supplier or technical support for further assistance. They may be able to provide guidance on how to troubleshoot the issue, or arrange for repair or replacement of the affected component or device.
AL 44: Ground fault The error message you provided indicates a "Ground fault" issue, which occurs when there is an unintended discharge of current from the output phases of the system to ground. This can be caused by a number of factors, such as a faulty insulation system, a damaged component, or improper wiring. To resolve this issue, you should first ensure that the wiring is properly grounded and that there are no loose connections or damaged components. It may also be necessary to inspect the insulation system and identify any areas that may be compromised.
AL 47: Control voltage fault The error message you provided indicates a "Control voltage fault" issue, which occurs when there is an overload in the 24 V DC control voltage system. This can be caused by a number of factors, such as a malfunctioning power supply, a short circuit, or an excessive load. To resolve this issue, you should first check the power supply and ensure that it is functioning correctly. It may also be necessary to check for any short circuits or faulty components in the control voltage system.
AL 51: AMA check Unom and Inom The error message you provided indicates an "AMA check Unom and Inom" issue, which occurs when there is an incorrect setting for the motor voltage and/or current in the control system. This can be caused by a number of factors, such as incorrect parameter settings, a mismatch between the motor and the control system, or a malfunctioning component. To resolve this issue, you should first review the parameter settings and ensure that they are correct for the motor being used. It may also be necessary to check the compatibility between the motor and the control system to ensure that they are a match.
AL 52: AMA low Inom The error message you provided indicates an "AMA low Inom" issue, which occurs when the motor current is too low in the control system. This can be caused by a number of factors, such as incorrect parameter settings, a malfunctioning component, or an inadequate power supply. To resolve this issue, you should first review the parameter settings and ensure that they are correct for the motor being used. It may also be necessary to check the power supply and ensure that it is providing adequate voltage and current to the motor.
AL 59: Current limit The error message you provided indicates a "Current limit" issue, which occurs when the frequency converter is overloaded and exceeds the specified current limit. This can be caused by a number of factors, such as an excessive load, improper parameter settings, or a malfunctioning component. To resolve this issue, you should first review the parameter settings and ensure that they are correct for the load being used. It may also be necessary to reduce the load or adjust the parameter settings to prevent future current limit issues.
AL 63: Mechanical brake low The error message you provided indicates a "Mechanical brake low" issue, which occurs when the actual motor current has not exceeded the release brake-current within the start delay-time window. This can be caused by a number of factors, such as a mechanical issue with the brake system, incorrect parameter settings, or a malfunctioning component. To resolve this issue, you should first review the parameter settings and ensure that they are correct for the brake system being used. It may also be necessary to check the mechanical components of the brake system, such as the brake pads and discs, to ensure that they are in good condition and functioning correctly.
AL 80: Frequency converter initialized to default value The error message you provided indicates that the "Frequency converter initialized to default value" issue has occurred, which means that all parameter settings in the frequency converter have been reset to their default values. This can be caused by a number of factors, such as a power interruption, a firmware update, or a hardware failure. To resolve this issue, you will need to re-enter the correct parameter settings for your specific application. You can do this by accessing the parameter settings menu and adjusting the values to the appropriate settings. It may also be necessary to save the settings once they have been adjusted to prevent the issue from happening again in the future.
AL 84: The connection between frequency converter and LCP is lost The error message you provided indicates that there is a "Lost connection between frequency converter and LCP" issue, which occurs when there is a failure of communication between the local control panel (LCP) and the frequency converter. This can be caused by a number of factors, such as a faulty communication cable, a malfunctioning component, or incorrect parameter settings. To resolve this issue, you should first check the communication cable and ensure that it is properly connected and functioning correctly. It is also recommended to review the parameter settings and adjust them as necessary to ensure that the communication settings are correct.
AL 85: Key disabled The error message you provided indicates a "Key disabled" issue, which is related to the local control panel (LCP). This can occur when the access key or password is disabled in the LCP parameter settings. To resolve this issue, you should review the parameter settings in group 0-4* LCP and check that the access key or password settings are configured correctly.
AL 86: Copy fail The error message you provided indicates a "Copy fail" issue, which occurs when there is an error during the process of copying data from the frequency converter to the local control panel (LCP), or from the LCP to the frequency converter. This can be caused by a number of factors, such as a malfunctioning component, a communication failure, or incorrect parameter settings. To resolve this issue, you should first review the parameter settings and ensure that they are configured correctly for the data being copied. It may also be necessary to check the communication cable and ensure that it is properly connected and functioning correctly.
AL 87: LCP data invalid The error message you provided indicates an "LCP data invalid" issue, which occurs when there is erroneous data present in the local control panel (LCP), or if no data was uploaded to the LCP. This can be caused by a number of factors, such as a communication failure, a malfunctioning component, or incorrect parameter settings. To resolve this issue, you should first review the parameter settings and ensure that they are configured correctly for the data being uploaded to the LCP. It may also be necessary to check the communication cable and ensure that it is properly connected and functioning correctly.
AL 88: LCP data not compatible The error message you provided indicates an "LCP data not compatible" issue, which occurs when there is an attempt to copy data from one frequency converter to another, but the software versions are significantly different. This can cause incompatibility issues and lead to errors in the data transfer process. To resolve this issue, you should ensure that the software versions on both frequency converters are compatible before attempting to copy data between them. It is recommended to consult the user manual or contact technical support to verify the compatibility of the software versions.
AL 89: Parameter read only The error message you provided indicates a "Parameter read only" issue, which occurs when there is an attempt to write data to a parameter that is set to read-only. This can be caused by a number of factors, such as incorrect user permissions, a malfunctioning component, or a software bug. To resolve this issue, you should ensure that you have the appropriate permissions to write to the parameter in question. It may also be necessary to review the parameter settings and check if the read-only setting is appropriate for the data being entered.
AL 90: Parameter database busy The error message you provided indicates a "Parameter database busy" issue, which occurs when the local control panel (LCP) and RS485 connection are trying to update parameters simultaneously, causing conflicts in the parameter database. This can be caused by a number of factors, such as a communication failure, a malfunctioning component, or incorrect parameter settings. To resolve this issue, you should first review the parameter settings and ensure that they are configured correctly for the data being updated. It may also be necessary to check the communication cable and ensure that it is properly connected and functioning correctly.
AL 91: Parameter value is not valid in this mode The error message you provided indicates a "Parameter value is not valid in this mode" issue, which occurs when there is an attempt to write an illegal value to a parameter. This can be caused by a number of factors, such as incorrect user input, a malfunctioning component, or incompatible parameter settings. To resolve this issue, you should review the parameter settings and ensure that the values being entered are appropriate for the mode of operation. It may also be necessary to consult the user manual or contact technical support to verify the appropriate parameter settings for the mode of operation.
AL 92: Parameter value exceeds the minimum/maximum limits
The error message you provided has two parts:
"Parameter value exceeds the minimum/maximum limits": this occurs when there is an attempt to set a parameter value outside the acceptable range of values. To resolve this issue, you should ensure that the parameter value being entered is within the acceptable range. It may also be necessary to consult the user manual or contact technical support to verify the acceptable parameter range.
"Not while running": this occurs when there is an attempt to change parameters while the motor is running. To resolve this issue, you should ensure that the motor is stopped before attempting to change any parameters. It is important to note that changing parameters while the motor is running can be dangerous and can cause damage to the system.
Err: A wrong password was entered The error message you provided indicates that a wrong password was entered when attempting to change a password-protected parameter. To resolve this issue, you should ensure that the correct password is entered for the parameter being modified. If you have forgotten the password or are unsure what the correct password is, you may need to contact the manufacturer or technical support for assistance. It is important to note that password-protected parameters are designed to prevent unauthorized changes, and attempting to change these parameters without the correct password can potentially cause damage to the system.
+