6ES7 193-0CB20-0XA0

Siemens 6ES7 193-0CB20-0XA0 – ET 200B TB2-4/DC Terminal Block

Siemens 6ES7 193-0CB20-0XA0 is the TB2-4/DC terminal block for ET 200B within the SIMATIC ET 200 family. Designed for 24 V DC electronics blocks, it has a 32-channel, four-tier screw-terminal arrangement and a 235 mm width.

When selecting a replacement, identify both the terminal base and the electronics block fitted to it. Appearance alone does not establish the input/output function or the correct field connections. Comparing ET 200 terminal blocks also requires checking the terminal tiers and the wiring already used in the cabinet.

What is the fourth terminal tier for?

The fourth tier provides PE connections. These terminals are interconnected, but they are not internally connected to the terminal block’s PE screw. Their presence does not, by itself, establish a completed protective earth connection.

This distinction matters when replacing a base in an existing cabinet. Check the grounding arrangement and continuity against the installation drawings. Protective earth and the M/0 V circuit reference have different functions; wire colour and physical proximity should not be used to decide how they are connected.

Compatible electronics blocks

32 digital inputs: ET 200B-32DI / 6ES7131-0BL00-0XB0 and ET 200B-32DI 0.2ms / 6ES7131-0BL10-0XB0. Browse the ET 200 digital input modules category for related products.

32 digital outputs: ET 200B-32DO / 6ES7132-0BL01-0XB0. 16 outputs, 2 A: ET 200B-16DO/2A / 6ES7132-0BH11-0XB0. These belong to the digital output module range.

Mixed inputs/outputs: ET 200B-16DI/16DO / 6ES7133-0BL00-0XB0; ET 200B-24DI/8DO / 6ES7133-0BN01-0XB0; ET 200B-24DI/8DO 0.2ms / 6ES7133-0BN11-0XB0.

These combinations explain why the base should not simply be described as a “32-input module.” Use the function, connection diagram and load limits of the installed electronics block. An output current rating from one block must not be applied to another merely because both use the same terminal base.

Supply and field wiring

Terminal assignments depend on the electronics block. When servicing an installation, follow the diagram for the fitted block before adding or changing links between terminals.

For an input circuit using an inductive sensor, check the sensor supply, output type and common reference together. Understanding sink/source wiring helps establish how the circuit operates instead of relying on conductor colours alone.

For outputs, consider the connected load current, starting behaviour and supply group. Even when the cabinet’s power supply appears adequate, loose connections, voltage drop or an incorrect common connection can cause operating problems. Measurements taken under the actual load conditions are more informative than an unloaded voltage reading alone.

PROFIBUS, address selection and STOP/RUN

The base includes a PROFIBUS-DP socket, station address selectors, coding slide and STOP/RUN switch.

When investigating communication problems, check the PROFIBUS connection, station address and PLC hardware configuration together. Record selector positions and cable labels before replacement to make recommissioning the existing automation system easier.

STOP must not be treated as isolation of every field circuit. Disconnect the relevant supplies and verify the absence of voltage at the work location before touching the wiring.

Conductor sizes and fuse information

Supply and signal wiring permits up to 1.5 mm² with ferrules or 0.14–2.5 mm² without ferrules. The PE terminal limit is 2.5 mm² with ferrules.

The specified fuse is TR5-T 2.5 A / 250 V, order number 6ES7193-0DB00-0XA0. The fuse’s 250 V marking does not make this terminal block suitable for a 230 V AC application, and its current rating must not be interpreted as the output capacity of each channel.

Inspect screw connections for crushed ferrules, exposed strands, discoloured clamping points and cracked insulation. Include field cables and connectors in the same inspection. Repeated fuse operation calls for fault investigation rather than a higher current fuse.

Information to include in a replacement enquiry

Provide the complete 6ES7 193-0CB20-0XA0 reference, the electronics block label and clear photographs of the terminals. Show how the fourth tier is used in the existing installation. If a three-tier base is being considered, the protective earth wiring must be addressed before proceeding with the change.

Describe whether the fault affects one channel, a channel group or the complete station. A poor connection and a damaged electronic output can produce similar symptoms. Recorded measurements and observations help identify the required part without relying on appearance alone.

Editor’s note: The fourth tier deserves more attention than a simple terminal count. Check the electronics block reference when selecting the base, and verify the protective earth connection during maintenance. These checks provide a much stronger basis for replacement than comparing two similar-looking housings.

Technical manual and wiring diagrams

Reference: Siemens ET 200B Distributed I/O Station, EWA 4NEB 812 6089-02c; section 7.2.5 and the relevant electronics block subsection under 7.3. Visit our Siemens ET 200 manuals and PDF documentation page to explore the documentation.