6ES7 133-0BN10-0XB0
6ES7 133-0BN10-0XB0 — Siemens ET 200B 24DI/8DO, 0.2 ms
Series: Siemens SIMATIC DP. Category: ET 200B digital input/output electronics block in the ET 200 family.
6ES7 133-0BN10-0XB0 is an ET 200B electronics block with 24 digital inputs and 8 digital outputs, operating at 24 V DC. Its input delay is 0.2 ms. The digital inputs receive sensor and contact signals, while the digital outputs control suitable field loads. The station communicates with the controller over PROFIBUS DP.
Electrical ratings and load calculation
The permissible supply range is 18.5–30.2 V DC. Output limits are 0.5 A per channel and 2 A total across all eight outputs. Typical logic consumption from L5+ is 85 mA, the sensor supply limit is 1 A, and maximum power loss is 5.5 W.
Checking individual channel currents is only part of the load calculation. Eight outputs drawing 0.5 A each would require 4 A, exceeding the total limit. Review the power supply and power distribution against the loads that can operate simultaneously. When assessing a coil load, consider its initial current demand as well as its steady operating current.
Understanding the 0.2 ms input delay
The 0.2 ms figure describes the input circuit delay. To estimate the machine’s overall response, also consider PROFIBUS communication, the PLC program cycle and the response of the controlled device. Do not derive a counting frequency directly from this figure. For short pulses, define the required functions before selecting counter modules, function modules or positioning solutions.
The specified input delay for 6ES7 133-0BN00-0XB0 is 3 ms. Matching the channel count alone is therefore insufficient when choosing a replacement. Check the shortest sensor pulse and how the existing program uses that signal.
PROFIBUS connection and project checks
The manual specifies rates up to 12 Mbit/s, limited to 1.5 Mbit/s with an IM 308-B. The I/O data area occupies 3 input bytes and 1 output byte. When reviewing PROFIBUS and PROFINET equipment, use PROFIBUS DP as the interface requirement for this model.
Before commissioning, compare the configured station type, PROFIBUS address and I/O start addresses with the installed hardware. Keep a record of the device description used by the working project; a similar name is insufficient grounds for choosing another entry. Inspect the connection components, cable shielding and bus termination alongside the network diagnostics.
Terminal block and physical inspection
The electronics block and terminal block together measure 235 × 130 × 60 mm and weigh approximately 800 g. These figures describe the assembled unit. When comparing replacements, record the underlying terminal block type, contact condition and cable arrangement as well as the electronics block label.
If outputs fail to operate, check their load supply and field loads before concluding that the entire module has failed. Inputs remaining readable while outputs stay inactive is a useful reason to focus the investigation on the output side, but it is not a diagnosis by itself. Assess LED states, voltage measurements and master diagnostic records together.
Editor’s note: When selecting a spare, record the complete order number and 0.2 ms input delay alongside the “24 inputs, 8 outputs” description. Keep photographs of both the label and the terminal block. Testing one output alone is insufficient to assess the normal load pattern: include the simultaneous loads used during the machine’s operating sequence while staying within the total current limit.
PDF documentation and manuals
Section 7.3.10 and technical data page 7-73 of the Siemens ET 200B manual are the main references for this model. Also consult Appendix B for addressing. Visit the Siemens ET 200 PDF and user manuals page for documentation.
Related topics
Explore ET 200 system structure, other network interfaces and additional modules and accessories when reviewing an existing station or planning an upgrade. Functions requiring safety modules or PROFIsafe need a suitable system selected separately. These category links do not establish that the listed parts can be fitted directly to ET 200B.
Navigation: Siemens automation > Siemens S7 PLC > SIMATIC S7 > Siemens ET 200