6ES7 120-0AH01-0AA0
Siemens 6ES7 120-0AH01-0AA0 – ET 200L-SC TB 16SC Screw Terminal Block
The 6ES7 120-0AH01-0AA0 is a screw-type TB 16SC expansion terminal block for Siemens ET 200L-SC / Smart Connect systems in the ET 200 family. It provides a base for compatible digital and analog SC electronic modules and their field wiring.
This part is not an input or output module by itself. The electronic modules that read sensors, switch outputs or process analog signals are installed separately. Communication with the main PLC is handled through a suitable ET 200L-SC electronics block or IM-SC interface.
Slots and basic specifications
The TB 16SC has 8 single-width module positions, labelled A to H. The manual gives dimensions of 145 × 100 × 40.5 mm and an approximate weight of 230 g. Allow additional installation space for the electronic modules, connection cable and any supplementary terminals.
The TB 16 designation does not mean that the terminal block itself contains 16 working inputs. The actual channel count depends on the installed modules. A two-channel digital input module can provide two inputs in one slot; single-channel and double-width modules change the calculation.
The specified current-carrying capacity through 1L+ and 2L+ is 8 A maximum. Siemens also gives a limit of 1.5 A per slot when supplied in parallel. These are terminal-block supply limits; they do not automatically give every output channel or connected load the same current rating. Check the individual module's current and temperature limits as well.
Which modules can be installed?
The TB 16SC can carry suitable SC digital input, digital output, analog input and analog output modules. For example, the 6ES7 121-1BB00-0AA0 is a two-channel 24 V DC digital input module, while the 6ES7 122-1BB00-0AA0 is a two-channel 24 V DC digital output module. They perform different functions even when installed on the same terminal block.
For analog signals, the 6ES7 123-1FB00-0AB0 is a two-channel voltage input module and the 6ES7 124-1FA00-0AB0 is a voltage output module. The latter is double-width and occupies two slots. Do not assume that every slot holds one module or that every module provides two channels. The distinction between analog and digital inputs is useful when planning the station.
The 6ES7 127-1BE00-0AB0 counter module and high-speed SC analog inputs have a special requirement: according to the Siemens manual, they can be used on a TB 16SC only when it is connected to a TB 16IM-SC station arrangement. Physical fit in the slot alone does not establish compatibility with every ET 200L-SC station.
Relationship to ET 200L-SC and IM-SC
The TB 16SC expands a compatible ET 200L-SC electronics block or a TB 16IM-SC / IM-SC arrangement through its SC connection. When used with TB 16IM-SC, it provides additional positions for SC modules. The usable module and channel count depends on module widths, station type and configuration limits.
There is no independent PROFIBUS DP socket or address switch on this terminal block. Communication and station addressing are handled by the connected ET 200L-SC electronics block or IM-SC interface. Related product groups include ET 200 connection modules and communication modules.
Siemens catalogues describe this terminal block with its ET 200L-SC connection cable. For a used item, check whether the connection cable and connector are present and in good condition before purchase.
Screw and spring terminal versions
The 6ES7 120-0AH01-0AA0 uses screw terminals. The 6ES7 120-0BH01-0AA0 is the spring-terminal version of the TB 16SC. The order-number difference identifies how the field wires are secured.
The 6ES7 120-0AH50-0AA0 is a different terminal arrangement: TB 16IM-SC, the main terminal block used with the IM-SC interface. Do not treat 0AH01 and 0AH50 as the same part simply because both descriptions contain “TB 16” and “screw terminal”. The general ET 200 terminal block category covers other terminal arrangements as well.
Terminals and supply connections
Each module position has assigned terminals: for example, slot A uses A1–A4 and slot B uses B1–B4. Their functions depend on the electronic module installed. The same A1 terminal may serve a different purpose with another module type, so use the wiring diagram of the actual electronic module.
Do not wire unused terminals. Siemens requires terminals not used by the module to remain unconnected so that the required insulation clearances are maintained. A visible terminal screw does not mean that the terminal is available for every module.
The manual identifies 2L+ and 2M as connections for looping through the 1L+ and 1M load supply. They should not be treated as two independent isolated supply groups. Select the 24 V DC supply, conductor size and protection for the requirements of the complete station.
Arranging AC, DC and analog modules
Each slot has a coding slide that must be set for the installed module type. Siemens identifies the DC position for DC and analog modules and the appropriate AC position for AC and relay modules. Do not force the slide or install a module before checking its position.
The slot immediately to the right of an AC or relay module must contain another AC / relay module or remain empty. A DC or analog module must not be placed directly in that position. When AC modules are used, Siemens also requires a screw-type supplementary terminal connected to the appropriate protective conductor. The manual further warns against connecting different phases of a three-phase system to the same terminal block.
These rules matter when 24 V DC modules and 115 / 230 V AC modules share a block. Plan the arrangement using the terminal block instructions together with each installed module's wiring diagram.
Mounting, cables and supplementary terminals
The terminal block mounts on a 35 mm DIN rail. Siemens requires a low-resistance connection from the block's local ground point to the rail, with the rail connected to the installation grounding arrangement. For the local connection, the manual specifies a conductor of at least 4 mm² and a maximum length of 0.5 m. The general meaning of L, N and PE markings is explained separately.
The Siemens wiring table generally specifies 0.14–1.5 mm² signal conductors and a screw-terminal tightening torque of 0.4–0.7 Nm; its wiring example uses 0.5 Nm. For conductor-end preparation, see wire ferrules, cable lugs and crimping tools.
The block provides a basic two-wire connection arrangement. Suitable supplementary terminals add connection points for three- and four-wire arrangements. The 6ES7 120-1AH00-0AA0 is a single-row screw supplementary terminal, and the 6ES7 120-2AH00-0AA0 is a double-row screw version. See the ET 200 additional modules group for related parts.
Replacement and used-item checks
Field wiring can remain on the terminal block when electronic modules are removed. Before replacement, safely isolate the relevant station and load supplies, and identify the module positions and wires. Compare coding-slide positions and module order with the existing installation.
On a used TB 16SC, inspect the screw threads, plastic housing, module-slot contacts, coding slides, grounding point and SC connection cable. Siemens specifies a maximum of 20 electronic-module insertions per terminal-block slot. A used item's insertion history may be unknown, so the physical condition of the slots and contacts matters.
Editor's Note: Do not select this part by slot count alone. First establish whether the station uses ET 200L-SC or the IM-SC arrangement, then check module widths and any AC / DC positioning rules. The TB 16IM-SC requirement is particularly important for counter and high-speed analog input modules. When buying used equipment, the SC connection cable matters as much as the condition of the terminal screws.
Manuals and related topics
For wiring diagrams, coding slides, AC module placement and supplementary terminals, visit Siemens ET 200 manuals and PDF files. The general station arrangement is explained on About Siemens ET 200.
Related topics: Industrial sensors · Analog signal devices · High-speed modules · Siemens S7-300
Navigation: Siemens automation · SIMATIC S7 · Siemens ET 200 · OtomasyonAVM homepage