6ES7 153-2AB01-0XB0
6ES7 153-2AB01-0XB0 — Siemens IM153-2 FO
Series: Siemens SIMATIC S7 / SIMATIC DP. Category: ET 200M fiber-optic PROFIBUS interface module.
6ES7 153-2AB01-0XB0 is the IM153-2 FO interface that connects an ET 200M station and its S7-300 modules to fiber-optic PROFIBUS DP. It handles station communication; it is not a CPU running the user program. The distinction between PROFIBUS and PROFINET interfaces matters here: this order number does not provide a PROFINET connection.
Technical data and station capacity
The interface supports up to 8 suitable S7-300 modules. Its supply is 24 V DC, with a permissible range of 20.4–28.8 V DC and maximum consumption of 500 mA at 24 V. The backplane output is rated 5 V DC, up to 1 A; typical power loss is 4.5 W. Dimensions are 40 × 125 × 117 mm, approximate weight is 360 g, and the protection rating is IP20.
The optical interface has two duplex sockets, operates at 660 nm and supports transmission rates up to 12 Mbit/s. When planning the power supply and power distribution, calculate interface consumption separately from the load current required by field devices.
Fiber connections and network layout
Devices are connected in sequence using duplex fiber cable. Suitable plastic fiber supports links up to 50 metres; PCF fiber supports up to 300 metres. These limits apply between adjacent devices, not to the total network length. Cable selection and the optical components at both ends must be checked together.
The transmitter at one end connects to the receiver at the other. Check the signal direction as well as the connection components and fiber ends. A break in a linear optical network can also disconnect downstream stations. Interface redundancy alone does not create a redundant optical ring.
Hardware revision, configuration and redundancy
The Siemens compatibility table specifies 96-byte extended diagnostics from E06 and DPV1 support from E08. Check the label’s E-Stand as well as the order number. In STEP 7 hardware configuration, or when configuring through the appropriate GSD, match the physical module order and PROFIBUS address to the project.
Redundant operation requires a suitable master system and active bus modules. Replacing I/O modules during operation also requires the appropriate active backplane and parameter settings; it is not a general feature of a standard bus connection. 6ES7 153-2AA02-0XB0 uses electrical RS-485. The shared “IM153-2” name does not make it a direct replacement for this optical interface.
Checks and fault assessment
For communication problems, measure the supply, inspect the fiber route and connectors, then compare the actual station against the project. Read the master diagnostics alongside the SF/BF indicators before deciding that the interface is faulty. Establish whether a digital input or digital output problem affects the whole station or only particular channels.
For function modules, counter modules and positioning modules, check the individual module’s ET 200M requirements. Likewise, compatibility with safety modules and PROFIsafe cannot be established from the interface name alone.
Editor’s note: Start by checking the optical sockets, the complete order number and the E-Stand. Two units carrying the same order number may have different hardware revisions. A front-view photograph is not enough to select a replacement: compare the label, the existing project and the other modules in the station.
PDF documentation and manuals
Use the product data sheet together with the IM153-2 / IM153-2 FO compatibility section of the ET 200M operating instructions and the PROFIBUS network manual for optical wiring. Visit the Siemens ET 200 PDF and user manuals page for documentation.