6ES7 138-4CF00-0AB0
Siemens 6ES7 138-4CF00-0AB0 – ET 200S PM-E F PROFIsafe Power Module
6ES7 138-4CF00-0AB0 is a PM-E F DC24V PROFIsafe fail-safe power module for the ET 200S distributed I/O system within the Siemens SIMATIC ET200 family. It supports the de-energization of defined load groups under the control of the safety program and also provides two fail-safe digital outputs.
The compact article number is 6ES7138-4CF00-0AB0. When selecting this component from the ET 200S safety module range, account for its safety function and its differences from standard power supply modules.
Station function and output arrangement
The PM-E F combines switching of the P1 and P2 potential buses with two fail-safe digital outputs. The potential-group supply and directly connected loads can therefore be handled as distinct output functions within the project.
The modules included in a particular power distribution group depend on the terminal-module sequence and the station wiring diagram. Where standard digital outputs are shut down as a group, the boundaries of that group must be clearly identified.
Verified main technical details
Product family: SIMATIC ET 200S
Module designation: PM-E F DC24V PROFIsafe
Article number: 6ES7 138-4CF00-0AB0
Rated load supply: 24 V DC
Potential-bus switching: Two relays for P1/P2
Bus-group current designation: 10 A
Fail-safe digital outputs: 2 × 24 V DC / 2 A
Electronic output type: P/M switching
Safety communication: PROFIsafe
Diagnostics: Supported.
The 10 A and 2 A figures apply to different parts of the module. The 10 A bus-group designation does not give each electronic output a 10 A rating. Load calculations must consider the relevant output rating, total group load and installed terminal hardware together.
Understanding P/M switching
In a P/M output arrangement, switching elements on the positive and negative sides of the load are considered together. The load return is therefore part of the fail-safe output circuit. Connections must follow the wiring diagram for the specific module.
Check the grounding arrangement, common reference and any connection between the load and chassis. P/M and P/P switching versions should not be assumed to use the same wiring arrangement. This distinction matters when replacing a fail-safe power module in an existing machine.
Compatible terminal modules
Siemens documentation covering the CF00 generation identifies the 6ES7 193-4CK20-0AA0 screw-terminal base and the 6ES7 193-4CK30-0AA0 spring-terminal base for the fail-safe power module. Later documentation also lists these bases as TM-P30S44-A0 and TM-P30C44-A0.
The electronic power module and its terminal block are separate components. Check whether the base is already installed, its connection type and its mechanical condition. Similar appearance to other connection modules does not establish suitability.
PROFIsafe address and project configuration
The module operates within a suitable safety control system and safety program. Its PROFIsafe destination address requires the project value and the module's address-switch setting to match. This is a separate check from the station's network address.
Record the configured article number, safety parameters and connected-load functions in the existing PLC project. Addresses and timing values shown in example projects should not be treated as ready-made settings for every station.
Differences between CF00 and later versions
CF00 is an early version of this product family. Features documented for CF01, CF02 and CF03 should not automatically be attributed to it. For example, the CF01 manual dated 04/2004 identifies selectable readback time as a new feature.
Likewise, PROFINET application information and load-connection details published for later versions do not establish CF00 compatibility. Replacement planning should assess the installed interface, terminal base, safety software and the manufacturer's spare-part rules together.
Diagnostics and maintenance
A de-energized output may result from a safety-program command, missing supply, a communication problem or an output-circuit fault. Assess the power supply, terminal contacts, field wiring and connectors together with the project diagnostics.
After correcting a fault, verify the behaviour of the affected safety function. The achievable safety level depends on the complete arrangement, including the module, potential group, load wiring and safety program. Outputs within the same automation station should not all be assumed to provide identical safety characteristics.
PDF manuals and technical documentation
Browse our Siemens ET200 manuals and PDF documentation page for related documents. Check the article numbers covered by the ET 200S fail-safe module manual. Where a newer edition describes only CF02 or CF03, also consult documentation and product information applicable to CF00.
Editor's note: The key selection details are the distinction between the 10 A bus group and the two 2 A electronic outputs, and the correct terminal base. Reviewing the label, base article number and existing safety project together makes it easier to distinguish similar versions.