6ES7 142-1BD21-0XB0
Siemens automation › SIMATIC S7 › Siemens ET 200 › 6ES7142-1BD21-0XB0
Siemens 6ES7 142-1BD21-0XB0 — ET 200X BM 142 Basic Module
The 6ES7 142-1BD21-0XB0 is an ET 200X BM 142 basic module in the Siemens ET 200 family. It provides 4 digital outputs, 24 V DC, rated at 2 A per channel. Within the PROFIBUS and PROFINET interface range, this model uses PROFIBUS-DP at up to 12 Mbit/s.
Why does the basic-module role matter?
This product also handles the station's PROFIBUS connection. Comparing only the channel count of ET 200 digital output modules is insufficient when choosing a replacement. Check the BM designation, complete order number and ET 200 station configuration together; distinguish the basic module's role from that of an expansion module.
Total current and simultaneous loads
Total output current, all mounting positions: 6 A up to 20 °C; 4 A up to 55 °C. The 2 A channel rating does not permit a simultaneous total of 8 A across the four outputs.
When reviewing ET 200 power supply modules and ET 200 power distribution components, use the machine's actual operating sequence. Record simultaneous loads, coil starting currents and cable voltage drop. This helps establish whether a successful single-load test represents operating conditions with all required loads active.
Duplicated channel access on M12 connections
Channel 1: X1 pin 2 or X2. Channel 3: X3 pin 2 or X4. Use only one socket per channel. Check cable assignments accordingly when selecting ET 200 connection modules and accessories. A second signal at a socket does not create an additional output channel.
Do not match ET 200 terminal blocks or connection parts from different series by appearance alone. Show the cable identification, pin assignment and connected load on the same drawing. Keep feedback from ET 200 digital input modules and measurements from ET 200 analog input modules separate from the output list.
Considering the 1BD22 successor
Siemens' SIMOTION compatibility list identifies 6ES7142-1BD22-0XB0 as this model's successor. That listing does not guarantee replacement without configuration changes in every existing project. Compare the hardware configuration, GSD selection, connected expansion modules and application-specific compatibility notes.
Five checks before selection or replacement
1. Complete identity: Record the 6ES7142-1BD21-0XB0 order number and product release. Add a photograph of the complete station alongside the label photograph.
2. Network settings: Check the PROFIBUS address, configured device and bus termination. Verify that two devices on the network have not been assigned the same address.
3. Electrical loads: List each output's load and the simultaneous total. Record operating temperature as well; do not base the decision solely on the power supply's nameplate current.
4. Wiring and sealing: Inspect connector pins, seals and caps on unused connections. A damaged or loose connection can leave the original fault unresolved after module replacement.
5. Replacement and testing: Siemens' service checklist requires the 24 V supply to be switched off before module replacement. Removing modules while energized can damage the backplane bus. Test outputs in a controlled sequence after replacement.
Editor's note: If the PLC output is on but a valve does not operate, check the command, load supply and cable separately. When replacing the basic module, record the network address and station configuration as carefully as the output connections.
Manuals and PDF documents
Use the ET 200X documents on the Siemens ET 200 PDF and user manuals page. This model's technical data appears in A5E00158282-05, section 7.3. The supplementary document A5E00144646-02 also provides commissioning and service checks.
Related topics
Power and connections: Power supply modules · Terminal blocks · Connection modules · Power distribution modules
Explore the station: About ET 200 · Communication interfaces · ET 200 manuals
Otomasyon AVM | Siemens:
Siemens main menu | Siemens S7 PLC | SIMATIC S7 | ET 200 modules