6ES7 131-4BD01-0AA0
Siemens 6ES7 131-4BD01-0AA0 – ET 200S 4 DI 24 V DC ST Digital Input Module
Siemens 6ES7 131-4BD01-0AA0 is a 4-channel, 24 V DC standard digital input module for SIMATIC ET 200S stations. It reads switching signals from pushbuttons, limit switches, auxiliary contacts and compatible proximity sensors. Part of the ET 200S platform within the Siemens ET 200 family, its 15 mm width allows small groups of inputs to be added to a station.
The designation 4DI DC24V ST identifies four digital inputs, a 24 V DC signal rating and the standard version. This member of the ET 200 digital input module range transfers field states to the PLC program. For example, it can report that a level switch is active, but it does not measure liquid level in centimetres. That distinction is fundamental when choosing between an analog input and a digital input.
Input levels and sensor compatibility
The inputs have an IEC 61131 Type 1 characteristic. The specified voltage range is −30 to +5 V for signal “0” and +15 to +30 V for signal “1”. Typical input current in the active state is 7 mA at 24 V. The region between +5 V and +15 V should not be used to establish a reliable logic state.
Suitable contacts and PNP-output sensors that apply a positive voltage to the input can be used with this arrangement. When replacing an inductive proximity sensor, check its output type and NO/NC behaviour as well as its supply voltage. Two sensors with identical housings may require different electrical connections.
The module also supports suitable two-wire BERO sensors, with a maximum permitted quiescent current of 1.5 mA. The sensor’s off-state residual current must be checked against this limit. Having two wires does not make a sensor electrically equivalent to a dry contact or a NAMUR device.
Input delay and PLC addressing
For both signal transitions, input delay is typically 3 ms, within a specified range of 2–4.5 ms. This delay is not parameterizable. The module can be used for pushbutton and position signals; applications involving short pulses require consideration of pulse duration, input delay and the PLC cycle together. A standard digital input should not be assumed to behave like a dedicated high-speed counter module.
The normal address space is 1 byte per module. With digital input packing supported by the station and its configuration, the module occupies 4 bits. After a replacement, checking the channel LEDs alone is therefore insufficient: the addresses in the hardware configuration must match the inputs monitored by the program.
Terminal base and power arrangement
The electronic module plugs into a compatible 15 mm ET 200S TM-E terminal module. Siemens lists several options, including the screw-terminal TM-E15S24-01 and spring-terminal TM-E15C24-01. Selection of terminal blocks should account for two-wire or three-wire sensors, required supply terminals and auxiliary potential arrangements. The connection module has a separate order number from the electronic module.
The 24 V DC supply is provided through the station’s appropriate power module. Maximum current drawn from the 3.3 V backplane supply is 10 mA, and typical module power loss is 0.7 W. Consumption from L+ depends on the connected sensors. The 500 mA sensor supply rating in the data sheet does not mean that each digital input draws this current or that the device is a digital output module.
The station’s power supply, ET 200 power modules and any required potential distribution components should be selected for the total load of the relevant group. The inputs are galvanically isolated from the backplane bus, but there is no individual isolation between input channels.
Dimensions, cable distance and installation
The electronic module measures 15 × 81 × 52 mm (width × height × depth) and weighs approximately 35 g. These figures refer to one electronic module. Siemens specifies an operating range of 0 to +55 °C for vertical installation for this version; cabinet layout must also follow the station’s general installation requirements.
Maximum specified cable length is 1,000 metres with shielded cable and 600 metres with unshielded cable. These limits do not guarantee identical performance with every conductor size or installation. Available sensor voltage, cable voltage drop and EMC conditions must also be considered.
Channel LEDs and fault finding
A green status LED is provided for each input. However, this ST version has no module SF fault LED and no built-in diagnostic function. Wire breaks or short circuits should not be expected to generate individual channel diagnostic reports. An unlit LED alone does not establish a module fault: the sensor may be inactive, its supply may be missing or the connection may be open.
A useful maintenance sequence is to compare the sensor supply and output, the voltage at the input terminal and then the PLC address. If the LED changes but the program input does not, check addressing, station communication and how the signal is used in the program. Terminal assignments and wiring examples are available through the Siemens ET 200 manuals and PDF documentation.
Editor’s note: Siemens specifies a standard packaging quantity of five electronic modules for this order number; each module has four inputs. Make clear whether a quotation is required for individual modules or complete packs. Siemens identifies this product as a spare part. When selecting a replacement, check the complete order code, existing terminal base and project addressing together.
Related topics
Data exchange with the control system takes place through the ET 200S station’s interface. For network arrangements, see ET 200 communication modules and the explanation of PROFIBUS and PROFINET. If the application also needs to switch a load, select an appropriate ET 200 digital output module separately.