6ES7 138-4CB10-0AB0

Siemens 6ES7 138-4CB10-0AB0 – ET 200S PM-E Power Module with Fuse and Diagnostics

Siemens 6ES7 138-4CB10-0AB0 is a PM-E power module used to supply and monitor a potential group within a SIMATIC ET 200S station. It supervises the load voltage shared by the group’s electronic modules and provides diagnostics for a missing supply or blown fuse. Within the Siemens ET 200 family, it belongs to the power module range for ET 200S applications using AC or DC load voltages.

AC and DC Supply Options

The product designation specifies 24–48 V DC / 24–230 V AC. Siemens technical data lists 24–56.7 V DC and AC values of 24–48 V, 120 V and 230 V. The selected voltage must match the electronic modules within that potential group. The PM-E distributes the externally supplied load voltage; applications requiring voltage conversion need a suitable external power supply.

For a 24 V DC installation, selection of a DIN rail power supply should account for module consumption and connected field loads. The PM-E’s voltage range does not extend the voltage ratings of the individual I/O modules.

Current Capacity and Temperature Derating

Permitted group current depends on supply type and ambient temperature. For DC operation, the limits are 10 A up to 30 °C, 9 A up to 40 °C and 7 A up to 60 °C. For AC operation, the corresponding limits are 8 A, 7 A and 5 A. Load calculations should use the cabinet temperature expected during normal operation.

Simultaneous operation of relays, valves and contactor coils connected through digital output modules can increase the group load. Check individual output channel ratings alongside the PM-E’s total current limit.

Replaceable Fuse and Circuit Protection

The module incorporates a replaceable 5 × 20 mm, 250 V / 10 A fast-acting fuse. This provides supplementary protection; suitable external overcurrent protection is also required in the load supply circuit. When selecting fuses, consider rated current, operating characteristic and breaking capacity together. Repeated fuse failures call for investigation of the wiring and connected loads, with replacement specifications kept consistent with the manufacturer’s requirements.

PWR, FSG and SF Indicators

The green PWR LED indicates load voltage, the green FSG LED indicates fuse condition, and the red SF LED indicates a group fault. Diagnostics for missing load voltage and a blown fuse can be enabled through parameters. Evaluating this information in the PLC program helps maintenance personnel identify supply problems.

On an HMI or SCADA screen, including the station and potential group name makes the alarm more useful. A clearly identified supply group gives the technician a practical starting point, particularly in cabinets containing several PM-E modules.

TM-P Terminal Modules and Physical Dimensions

The supply connects through a suitable TM-P terminal module. Compatible options include the screw-terminal TM-P15S23-A1 and spring-terminal TM-P15C23-A1. Selection also depends on the required AUX1 arrangement and potential group layout. Related components can be reviewed under ET 200 terminal blocks and connection modules.

The PM-E measures 15 × 81 × 52 mm and weighs approximately 34 g. Overall installed dimensions depend on the terminal module. Allow space for cable access, fuse servicing and grounding connections when planning the cabinet layout.

Its Role Within the Station

A new TM-P starts a potential group extending to the next TM-P. This arrangement allows sensor supplies associated with digital input modules and output loads to be grouped according to the application. Communication between the station and its controller is handled by the selected ET 200 interface module.

AC/DC Parameters and Replacing the 4CB00

When replacing 6ES7138-4CB00-0AB0 with 6ES7138-4CB10-0AB0 in an AC application, update the hardware configuration and select AC as the load voltage type. The new parameter defaults to DC. Leaving that setting unchanged with an AC supply can keep the SF indicator illuminated and produce repeated missing-load-voltage diagnostics when enabled. Compare the complete order number and project settings before scheduling a replacement.

Editor's Advice

If several modules in the same group develop problems together, start with their shared supply. Compare the PM-E indicators, external voltage, fuse condition and AC/DC parameter. Record the cabinet’s operating temperature and simultaneous load current as well. These observations help distinguish a component failure from a load or configuration issue.

Technical Documents and Related Topics

Visit our Siemens ET 200 manuals and PDF documents section for connection and parameter information. Check both the 6ES7138-4CB10-0AB0 order number and the installed TM-P terminal type when reviewing the documentation.

Related topics: Siemens ET 200 system overview · ET 200 power distribution modules · ET 200 additional modules