6ES7 134-7TD00-0AB0
6ES7 134-7TD00-0AB0 is a Siemens 4-channel HART analog input module for the SIMATIC ET 200iSP distributed I/O system. Designated 4AI I 2WIRE HART, it processes 4–20 mA signals from two-wire transmitters and supports digital communication with compatible HART field devices. Related products are available in our ET200 analog input modules section.
Device Description
The module transfers process measurements through an ET 200iSP station to the control system. A two-wire transmitter receives its supply through the same conductors that carry the measurement signal. Compatible sensors and transmitters can provide measurements such as pressure, level, flow or temperature. For example, a pressure measurement requires the transmitter range and control-system scaling to agree.
ET 200iSP is designed for applications using intrinsically safe field circuits. Check the ET 200iSP designation, complete order number and transmitter connection type when selecting a module. Different ET200 subfamilies use different mechanical and electrical arrangements.
Technical Data
Manufacturer: Siemens
Order Number: 6ES7 134-7TD00-0AB0
Designation: 4AI I 2WIRE HART
System: SIMATIC ET 200iSP
Analog Inputs: 4
Transmitter Connection: Two-wire, loop-powered
Rated Measuring Range: 4–20 mA
HART Protocol: Version 6.0 specified by Siemens
Resolution: 13 bits including sign — 12 bits + sign
Measuring Principle: Sigma-Delta
Basic Conversion Time: 30 ms per channel
Four-Channel Cycle: Maximum 120 ms with 50/60 Hz suppression
Transmitter Supply Current: Maximum 23 mA per channel
Powerbus Current Consumption: Typically 280 mA; maximum 320 mA
Typical Power Loss: 2.7 W
Dimensions: 30 × 129 × 136.5 mm — width × height × depth
Approximate Weight: 230 g
Module Protection: IP30
HART Communication and Measured Values
HART provides access to device information and parameters alongside the analog current signal. With suitable engineering tools, SIMATIC PDM can identify and parameterize field devices. The installed communication interface determines the station's connection to the control system. Our PROFIBUS and PROFINET explanation provides additional network background.
Verify the analog measurement and HART access separately during commissioning. A value displayed by the control system does not by itself confirm access to the device's digital parameters. Record the transmitter model, device description, engineering unit and configured channel settings together.
Scaling example: For a transmitter configured linearly from 0 to 10 bar, 4 mA represents 0 bar, 12 mA represents 5 bar and 20 mA represents 10 bar. This relationship assumes matching transmitter settings and PLC program scaling. Applications using square-root extraction or other characteristics require separate consideration.
Terminal Module and Channel Connections
The electronic module plugs into a suitable TM-IM/EM or TM-EM/EM terminal module. Options include the screw-terminal TM-EM/EM60S — 6ES7 193-7CA00-0AA0 and spring-terminal TM-EM/EM60C — 6ES7 193-7CA10-0AA0. Confirm the delivery scope for the terminal base and electronic module separately.
Channel terminals shown in the manufacturer diagram:
Channel 0: 1 (+) and 2 (−)
Channel 1: 5 (+) and 6 (−)
Channel 2: 9 (+) and 10 (−)
Channel 3: 13 (+) and 14 (−)
Compare the markings on the installed base with the applicable wiring diagram. Identify connection components by their complete part numbers. Follow the transmitter supply arrangement and channel diagram before introducing any external supply into the measuring circuit.
Use in Hazardous Areas
The manufacturer documentation describes installation in Zone 1 under the applicable conditions and connection of suitable field devices from hazardous areas including Zone 0. The module installation area and the transmitter installation area must be assessed separately. The IP30 module rating alone does not determine the required hazardous-area enclosure.
Assess intrinsic-safety compatibility across the module, transmitter and cable. In addition to certified voltage, current and power limits, include cable capacitance and inductance in the assessment. The enclosure and cabinet connection components must suit the gas or dust environment. Use the certificates and manufacturer drawings corresponding to the actual product label.
Diagnostics and Commissioning Recommendations
The module provides diagnostic or alarm functions for wire breaks, short circuits and limit values. Review the required notifications together with the channel parameters. If the red SF indicator is active, use online diagnostics to identify the affected channel and fault type.
Check the complete measurement chain: Compare the transmitter's local indication, loop current and operator display. Finding where the discrepancy begins is more informative than immediately replacing the input module. Test equipment and measurement procedures must suit the installation area.
Identify the source of fluctuations: Examine the process, supply and cabling and connections before increasing measurement smoothing. Filtering can reduce visible fluctuations while also delaying the indication of genuine process changes.
Review station loading: Before adding modules, check total ET 200iSP consumption against the capacity of the installed power supply module. Products in the category may belong to different ET200 subfamilies.
Editor's Recommendations and Related Topics
Pay particular attention to the 7TD00 section when ordering a spare. 6ES7 134-7TD50-0AB0 is a different model intended for four-wire transmitters. Do not select these interchangeably without checking the transmitter arrangement, terminal base and project configuration.
Keep the module label, terminal code, transmitter model, measuring range and project backup in the maintenance record. These details make it easier to compare the installed equipment with the software configuration during subsequent troubleshooting.
For other station signals, browse our ET200 digital input modules, ET200 digital output modules and Siemens ET200 products.
Where functional safety is required, separately evaluate the appropriate safety modules and PROFIsafe products. This model's explosion-protection characteristics do not provide a SIL- or PL-rated safety function.
Manuals and Technical Documents
+ Siemens ET200 User Manuals — PDF archive page
+ Siemens 6ES7 134-7TD00-0AB0 Operating Information — ET 200iSP system manual, section 14.2; English PDF
+ 4AI I 2WIRE HART Product Information — English section of the multilingual document
+ ET 200iSP Intrinsic Safety Control Drawings — applicable model and installation conditions
+ Siemens ET200 Archive Catalogue — ET 200iSP Analog Modules — catalogue section
Technical source: Measurement and dimensional information is also available in the Siemens 6ES7 134-7TD00-0AB0 data sheet. This link is a manufacturer document hosted externally.
++ Siemens Automation Main Page >
++ Siemens Automation Contact — for Otomasyon AVM
++ About Siemens ET200 PLC >
Reminder: Please confirm current availability, condition and delivery scope for Siemens 6ES7 134-7TD00-0AB0 and other SIMATIC products with Otomasyon AVM. Some devices are used products; take this into account when purchasing. Products will not be restocked once sold out. This page provides general information; the product label, hardware revision and applicable manufacturer documentation should govern your application.
Note: Manuals, commissioning recommendations and troubleshooting explanations are non-binding and may be updated or improved. The Otomasyon AVM Community welcomes practical experience. You can share your operating and maintenance recommendations with us.