6ES7 138-1XL00-0XB0
Siemens Main Menu › SIMATIC S7 › ET 200 Modules
Siemens 6ES7 138-1XL00-0XB0 — ET 200L-SC IM-SC PROFIBUS-DP Interface Module
6ES7 138-1XL00-0XB0 is the IM-SC PROFIBUS-DP interface module for the ET 200L-SC system within the Siemens ET 200 family. It provides communication for SIMATIC Smart Connect electronic submodules. It belongs among ET 200 communication interfaces; the “138” portion of an order number alone is insufficient to identify a module’s function.
Supply and communication characteristics
Electronics supply: 24 V DC. Maximum PROFIBUS-DP speed: 1.5 Mbit/s. Check the existing network speed against this limit. When assessing 24 V industrial power supplies, check the voltage at the device and the condition of its connections alongside the supply’s nameplate rating.
Document the interface supply separately from field load supplies in the maintenance record. Treating ET 200 power supply modules and communication interfaces as interchangeable functions can lead to an incorrect selection. Record the complete device code, installed base and missing components before ordering.
Compatible terminal base
The IM-SC uses a TB 16IM-SC base: 6ES7120-0AH50-0AA0 with screw terminals or 6ES7120-0BH50-0AA0 with spring terminals. When selecting ET 200 terminal blocks, match both the connection type and full order number. Compare the cabinet schematic when checking module connections and terminal arrangements; visual similarity does not establish mechanical or electrical compatibility.
Five checks before selection
1. System variant: Review the ET 200 system architecture and confirm an ET 200L-SC IM-SC arrangement. Use the complete device label when searching for a replacement.
2. Module layout: Record installed digital input modules, digital output modules and any analog input modules in slot order. These category links support further research; they do not imply that every listed module supports Smart Connect.
3. Project matching: Compare the station selected in the SIMATIC S7 hardware configuration, its PROFIBUS address and module order with the installed equipment. Back up the project and settings before replacement.
4. Bus wiring: Label incoming and outgoing PROFIBUS cables. Record the termination switch position and identify which stations could be affected by connections changed during maintenance.
5. Scope and condition: Inspect removable connectors, terminals, base contacts and locking points. Establish whether the supplied item includes the interface, terminal base or electronic submodules.
Editor’s Note
Removing the PROFIBUS terminal disconnects downstream DP stations from the bus. Plan maintenance around the affected network section. Bring the machine to a safe state and document connections before work; afterwards, check communication with both this station and the downstream devices.
PDF manual and wiring information: Visit the Siemens ET 200 manuals and PDF documents page. The manual ET 200L, ET 200L-SC and ET 200L-SC IM-SC, EWA 4NEB 780 6009-02c, section 9.1, pages 9-2 and 9-3, describes this interface.