Siemens 6ES7 138-4FA03-0AB0 — ET 200S 4/8 F-DI PROFIsafe Input Module
The 6ES7 138-4FA03-0AB0 is a 24 V DC, 4/8 F-DI PROFIsafe digital input module for ET 200S, part of the Siemens ET 200 family. It belongs to the ET 200 safety module range and handles safety-related input signals. When comparing it with standard ET 200 digital input modules, channel count alone is insufficient to establish interchangeability.
What does 4/8 F-DI mean?
The module supports eight single-channel or four dual-channel inputs. Its data sheet states maximum ratings of SIL 2 / Category 3 for single-channel operation and SIL 3 / Category 4 for dual-channel operation. Achievable safety performance depends on the sensor arrangement, supply, wiring and safety configuration.
Key dimensions: The housing measures 30 × 81 × 52 mm; the permitted supply range is 20.4–28.8 V DC. These dimensions refer to the electronic module. Allow additional installation space for the terminal base and wiring.
Why does the power module matter for FA03?
Siemens product information A5E36397089-AB specifies a limit of SIL 2 / Category 3 / PL d for FA03 and earlier F-DI versions supplied by PM-E DC24V modules up to 6ES7138-4CA01-0AA0. Therefore, verify the exact ET 200 power supply module before treating the station as suitable for SIL 3. Check the power distribution arrangement against the existing project and the manufacturer's module assignment table.
Terminal base and station configuration
Siemens' two-hand control and emergency-stop example uses this model with a CPU 315F-2 DP, an IM151 High Feature interface, a 6ES7138-4CB11-0AB0 power module and a TM-E30C46-A1 / 6ES7193-4CF50-0AA0 terminal base. This provides a useful reference when selecting ET 200 terminal blocks and ET 200 connection components; it does not establish interchangeability with every similar part.
Within the ET 200 station architecture, assess the F-CPU, interface and F-I/O together. Verify the exact PROFIBUS and PROFINET interface models and project support. Distinguish this input module from the ET 200 digital output modules that operate field loads; validate the complete safety function from input to output.
Five checks before selection or replacement
1. Complete order number: Confirm 6ES7138-4FA03-0AB0 on the label. Do not treat FA03, FA04 and FA05 as equivalent based on appearance.
2. Channel arrangement: Identify whether the existing project uses single-channel or dual-channel evaluation. Sensor contact arrangements and channel pairing must match the same design.
3. Supply and base: Record the PM-E order number, terminal base and field connections. Pay particular attention to the safety limit associated with the FA03 supply combination.
4. Project and address: Compare the F-CPU, interface version, hardware configuration and PROFIsafe address. Do not copy addresses and parameters from another station without checking the project requirements.
5. Functional test: Input LEDs alone do not establish successful replacement. Test stopping, fault response and restart behaviour of the affected safety function according to the plant's acceptance procedure.
Editor's note: Before ordering this model, photograph its label together with the adjacent power module and the terminal base underneath. “The same yellow module” or “eight inputs” is not a sufficient identification. Keep the safety project backup together with a record of the complete component order numbers.
Manuals and PDF documents
Visit the Siemens ET 200 PDF and user manuals page for ET 200S Fail-Safe Modules documentation. Read the FA03 data sheet alongside the power module assignment update A5E36397089-AB and two-hand control application example 21331100.
Related topics
Power and connections: Power supply modules · Terminal blocks · Connection modules · Power distribution modules
Explore the station: About ET 200 · Communication interfaces · ET 200 manuals
Otomasyon AVM | Siemens:
Siemens main menu |
Siemens S7 PLC |
SIMATIC S7 |
ET 200 modules