6ES7 138-4HA00-0AB0

Siemens 6ES7 138-4HA00-0AB0 – ET 200S PROFIBUS-DP Master Interface Module

Siemens 6ES7 138-4HA00-0AB0 adds a PROFIBUS-DP master connection to an ET 200S station equipped with an IM151-7 CPU or IM151-8 PN/DP CPU. Its front-mounted 9-pin female D-sub connector connects the CPU to a PROFIBUS network containing DP slave devices.

In a CPU-based ET 200 system, the controller can process local I/O while exchanging data with additional field stations. This module provides the PROFIBUS-DP connection for that arrangement. The control program and data processing remain in the associated PLC CPU.

CPU compatibility and basic specifications

The Siemens data sheet identifies this product as a DP master interface for the IM151-7 CPU and IM151-8 PN/DP CPU. A maximum of one module per CPU is supported. Dimensions are 35 × 119.5 × 75 mm (width × height × depth), with an approximate weight of 100 g.

CPU examples covered by Siemens operating instructions for this module include 6ES7151-7AA21-0AB0 and 6ES7151-8AB01-0AB0. When extending an existing station, check the complete CPU order number, firmware version and engineering software support together. An “IM151” or “ET 200S” designation alone does not establish compatibility.

Communication capacity

The relevant CPU documentation specifies communication rates of up to 12 Mbit/s and support for up to 32 DP slaves. The IM151-8 PN/DP CPU manual lists a DP master address area of 2048 input bytes and 2048 output bytes, with a maximum of 244 input bytes and 244 output bytes per DP slave.

These limits do not mean that every connected device supports the same amount of process data. The actual configuration depends on the device’s supported data layout and the address space available in the project. Select the bus speed with cable length, connectors and physical network layout in mind; the highest available speed is not automatically the best setting for every installation.

Position within the ET 200S station

The 6ES7138-4HA00-0AB0 mounts on the rail immediately to the right of the CPU and connects through its side interface. Install it before fitting the terminal modules that continue along the station. It mounts directly on the rail and does not require a separate TM terminal base underneath.

Local I/O wiring continues through the appropriate ET 200 terminal modules. Allow space for the PROFIBUS connector and cable bend as well as the module’s 35 mm width when planning the cabinet layout.

PROFIBUS connector and wiring

The physical interface uses RS-485. Siemens identifies pin 3 as B / RxD-TxD-P and pin 8 as A / RxD-TxD-N. Use a suitable PROFIBUS bus connector and check shield contact, connector retention and bus termination as part of the same installation task.

RS-485 describes an electrical interface; it does not identify the communication protocol by itself. The same distinction matters when considering Modbus and RS-485 communication. The port on this module operates as a PROFIBUS-DP master. A standard Modbus RTU device cannot communicate with it simply by matching the A and B connections.

When investigating intermittent faults, consider cable routes alongside power wiring and the condition of shield connections. Understanding electromagnetic interference and EMC helps explain why cable routing matters in cabinets containing motors and drives.

An important STEP 7 configuration detail

In STEP 7 HW Config, the DP master is configured as an X2 submodule. The PROFIBUS network, master address, diagnostic address and connected DP slaves are then defined. The physical connector marked X1 on the front and the X2 submodule shown in HW Config use different naming contexts. Keep this distinction in mind when comparing the hardware with the project.

Installing the module does not complete the master configuration. Slave addresses, selected module arrangements and I/O data lengths must match the equipment on the network. The IM151-8 PN/DP CPU manual states that the PROFIBUS address is stored with the hardware configuration on the CPU’s Micro Memory Card.

What to check when the BF indicator is active

The red BF indicator reports a PROFIBUS bus fault. A steady or flashing indication can be associated with physical network problems, an inaccessible slave or a configuration mismatch. The indicator alone therefore does not establish that the master interface module has failed.

Start with the CPU diagnostic buffer to identify the reported station or event. Then check that device’s supply and address, the bus connector, cable continuity, termination settings and configured data lengths. Knowing whether the fault appears during machine movement, when a particular load starts, or when a cable is disturbed can make troubleshooting much more focused.

Application and power arrangements

For example, an ET 200S CPU can process local digital inputs and digital outputs while this interface exchanges data with another PROFIBUS I/O station. Keep local channel addresses and remote device data areas clearly identified in the project.

When sizing the power supply, assess the CPU, local modules and field loads according to their respective supply groups. The DIN rail power supply, ET 200 power modules and power distribution arrangement should be considered together. Loss of power at a remote slave can also appear as a communication fault at the master.

Replacement and technical documentation

Record the existing project and diagnostic information before replacement, and schedule the work during a planned shutdown. Siemens requires the associated CPU supply to be switched off when replacing the DP master module. This also affects communication managed by that CPU. Where the station is at the end of a bus segment, consider how removing power affects the bus termination.

Use the manual for the installed CPU when checking mounting, connector assignments, STEP 7 configuration and BF diagnostics. Visit the Siemens ET 200 manuals and PDF documentation page and refer to the IM151-7 CPU or IM151-8 PN/DP CPU documentation as appropriate.

Editor’s note: Correct selection depends on the module order number, the installed CPU and the project configuration. Recording the CPU label and existing hardware configuration before sourcing a replacement helps prevent mistakes caused by relying on appearance alone.