6ES7 138-4FD00-0AA0

Siemens 6ES7 138-4FD00-0AA0 – ET 200S 4POTDIS Potential Distribution Module

Siemens 6ES7 138-4FD00-0AA0 is the 4POTDIS potential distribution module for ET 200S, within the SIMATIC ET 200 family. It distributes the station's load supply potential to external circuits. Its 15 mm width allows supply connections to be organised within the I/O station. The product belongs to the ET 200 power distribution module range.

The four outputs are supply distribution points, rather than four channels individually switched by the PLC program. If a load must switch in response to a program command, select the appropriate digital output module and load-driving circuit separately.

Relationship with the PM-E Supply Group

The distributed voltage comes from the PM-E power module supplying the potential group. The documented nominal load-voltage range is 24–48 V DC or 24–230 V AC. The voltage usable in a particular installation depends on the selected PM-E and the other components within that group.

Check the power supply, ET 200 power module and field-device ratings together. 4POTDIS does not convert voltage. In a sensor group supplied from a 24 V DC DIN rail power supply, for example, it distributes that group's 24 V DC supply.

Output Current and the Group Load Budget

The limits are 5 A per output and 10 A total per module. Both limits apply simultaneously. Current drawn by modules positioned between PM-E and 4POTDIS reduces the total current available to the distribution module.

For example, if those intermediate modules consume 3 A from a 10 A group budget, no more than 7 A remains available to 4POTDIS. The power supply, PM-E, conductors and connections must also be checked for any lower limit. Include simultaneous starting conditions when evaluating loads, as well as their normal running current.

Recording individual sensor consumption helps with both design and maintenance. Where several inductive sensors and photoelectric sensors share a supply group, the wiring plan should make clear which devices could lose power following a fault on a common branch.

Compatible Terminal Modules

4POTDIS fits suitable 15 mm TM-E terminal modules. Examples in the Siemens manual include screw-terminal TM-E15S26-A1 / 6ES7 193-4CA40-0AA0, spring-terminal TM-E15C24-01 / 6ES7 193-4CB30-0AA0 and Fast Connect TM-E15N24-01 / 6ES7 193-4CB70-0AA0.

The electronics order number does not identify the field-connection method by itself. Read the fitted terminal base designation as well. Available connection points and the AUX arrangement depend on the terminal model. Conductor preparation and installation must suit the selected screw or spring terminal system.

L, M and AUX1 Connections

In the general assignment, terminals 1, 2, 5 and 6 carry L, while 3, 4, 7 and 8 carry M. Terminals 4 and 8, and the AUX connections, are not available on every terminal model. Confirm AUX1's function against the selected base and the actual station wiring.

Do not treat the M reference, protective conductor and AUX bus as interchangeable. Whether a connection serves as protective grounding must be established from the electrical drawings and wiring, rather than assumed from its position or conductor colour. This is particularly useful when inspecting a cabinet that has undergone previous modifications.

Protection and Electrical Isolation

The outputs have no internal short-circuit protection; suitable protection must be provided through the PM-E or an external circuit. Reverse-polarity protection is also absent. The output circuits are isolated from the backplane bus, but the outputs are not galvanically isolated from one another.

Select fuses and other protective devices with the connected conductor size and load requirements in mind, as well as the module's total current limit. For a supplied relay or contactor coil, verify its voltage and switching circuit separately. Taking power from a distribution output does not make that load program-controlled.

Dimensions and Hardware Configuration

The module dimensions are 15 × 81 × 52 mm, in width × height × depth order. Overall installed dimensions depend on the selected terminal base. Siemens lists a net product weight of 39 g. Parameter length is 1 byte; isochronous operation and diagnostic interrupts are not supported.

The parameter length should not be interpreted as four independent output commands. Compare the physical module sequence and hardware definition with the existing project. Our ET 200 system overview provides background on the station arrangement and its component roles.

Investigating a Loss of Field Power

If several field devices lose power together, trace their common supply path first. Measure at the power supply, PM-E input, relevant potential group and 4POTDIS connections in sequence. Continued communication with the station does not establish that load voltage is reaching every device. Compare indications on the HMI panel with voltage measurements at the affected circuits.

A voltage drop that appears only under load may indicate a loose connection, damaged contact, inadequate supply or excessive demand. Include field cables and connectors in the investigation. If terminals show overheating or discolouration, establish the cause before installing a replacement module.

Editor's Advice

Record three order numbers when preparing a replacement: the 4POTDIS module, its terminal base and the PM-E supplying the group. Together, they identify the essential voltage and connection requirements. Calculate individual output loads and the total group load separately. Siemens operating instructions require the load voltage to be switched off before inserting or removing 4POTDIS; placing the PLC in STOP does not, by itself, establish that the load supply has been disconnected.

Technical Documentation and PDF Manuals

Visit our Siemens ET 200 PDF manuals page for wiring and installation documentation. Use the 4POTDIS module manual, A5E01077612-01, together with the ET 200S system operating instructions. Also check the terminal base arrangement and the selected PM-E's permissible voltage and current ratings.

Related Topics

For station connection and auxiliary components, browse ET 200 connection modules and ET 200 additional modules. Verify each item's suitability for ET 200S and the existing station arrangement by its complete order number.

Siemens > SIMATIC S7 > Siemens ET 200 > Power Distribution Modules