6ES7 151-8FB00-0AB0

Siemens 6ES7151-8FB00-0AB0 – ET 200S IM151-8F PN/DP CPU

Siemens 6ES7151-8FB00-0AB0 is the IM151-8F PN/DP fail-safe CPU for SIMATIC ET 200S. It can execute standard automation and safety programs on the same controller. Within the Siemens ET 200 family, it is a CPU-equipped model that provides local control for an ET 200S station.

Work memory, power supply and memory card

The CPU provides 192 KB of work memory for programs and data. Its rated supply is 24 V DC, with a permissible range of 20.4–28.8 V DC. Housing dimensions are approximately 120 × 119.5 × 75 mm, stated as width, height and depth.

A SIMATIC Micro Memory Card (MMC) is required, and the CPU operates without a battery. The MMC serves as load memory; a larger card does not increase the CPU’s work memory. Before replacement, check card compatibility, the project backup and the existing hardware configuration together.

PROFINET and PROFIBUS connections

The integrated PROFINET interface has three RJ45 ports belonging to the same interface and its integrated switch. 6ES7151-8FB00-0AB0 operates as a PROFINET IO Controller; it does not support PROFINET IO Device / I-Device operation.

PROFIBUS DP master connectivity requires the additional 6ES7138-4HA00-0AB0 module. The “PN/DP” designation does not mean that a directly usable PROFIBUS socket is built into the CPU housing. For network information, see ET 200 PROFIBUS and PROFINET.

Safety programming and software requirements

Siemens product information specifies STEP 7 V5.4 SP4 or later for standard applications, with S7 Distributed Safety V5.4 SP4 or later additionally required for safety applications. Match the engineering software, hardware catalog and firmware to the existing project.

The availability of 64 KB of retentive memory does not mean that all safety data survives a restart. F-DB actual values are non-retentive: after power cycling or a STOP–RUN restart, initial values are taken from load memory.

When reviewing the safety architecture, consider ET 200 PROFIsafe together with the relevant ET 200 safety modules. Using an F-CPU alone does not validate the machine’s safety functions.

Commissioning and fault diagnosis

Before commissioning, check the complete order number, firmware, MMC contents, station module sequence, PROFINET device names and addressing. Read the STEP 7 diagnostic buffer alongside the LED indications when investigating faults. Replace the CPU or DP master module with the relevant supply switched off. Maintenance planning must account for the possible loss of network communication through the integrated switch when CPU power is removed.

Differences between FB00 and FB01

Siemens identifies 6ES7151-8FB01-0AB0 as the successor to 6ES7151-8FB00-0AB0. FB00 has 192 KB of work memory, while FB01 is specified with 256 KB. The IO Controller/I-Device capabilities of FB01 must not be attributed to FB00. Migration requires a separate review of the hardware configuration, engineering software and safety project.

PDF documentation and user manuals

For documentation references, visit the Siemens ET 200 user manuals and PDF documentation page. Select the product information for 6ES7151-8FB00-0AB0 and review it together with the applicable IM151-8 PN/DP operating instructions and safety software documentation.

Related topics

Input and output modules: Digital input modules, digital output modules, analog input modules, special input modules and special output modules.

Power and connections: Power supply modules, power distribution modules, terminal blocks and connection modules.

Functions and expansion: Functional and safety modules, counter modules, positioning modules, additional modules and other network interface modules. For a system overview, see About Siemens ET 200.

These sections may include different ET 200 subfamilies. Compatibility with this CPU must be verified using the complete module order number and version information.