• Gemo DZ304

Gemo DZ304 is a compact 48 × 48 mm programmable digital timer with separate START, RESET and GATE inputs. It offers 13 selectable output functions, so it can handle timing sequences that would normally require more than a basic timer relay. OtomasyonAVM has been supplying Gemo products since 2013.

Supply voltage: 100–240 VAC, 50–60 Hz.
A 24 VAC/DC version is available as an option.
Input: DC contact or sensor signal.
Output: Relay output as standard. An open-collector NPN output is available for SSR applications.

START / RESET / GATE inputs: Maximum 32 VDC. OFF level: 0–2 VDC. ON level: 7–32 VDC.

The GATE input is useful when timing needs to be paused without resetting the current value. While GATE is ON, counting stops. When the input is released, timing continues from the stored value.

Timing functions

The DZ304 has 13 selectable output functions. The behaviour of the START and RESET inputs changes according to the selected mode.

Delayed output with START ON: When START turns ON, the timer begins counting. OUT switches ON after t.SEt. If START turns OFF, OUT switches OFF. RESET also switches the output OFF.

Retriggerable timed output: A change at the START input, either OFF → ON or ON → OFF, switches OUT ON. OUT switches OFF after t.SEt. A new START trigger can restart the timing period while the output is still active.

Delayed output with reset requirement: Following an OFF → ON transition at START, OUT switches ON after t.SEt. A new START trigger is ignored until RESET is applied.

START-controlled Flasher: While START remains ON, OUT stays ON for t.On, then OFF for t.OFF. The cycle repeats until START turns OFF or RESET is activated.

Rising-edge timed output: An OFF → ON transition at START switches OUT ON. OUT switches OFF after t.SEt. A new START trigger can restart the timing period while OUT is active.

Triggered Flasher: An OFF → ON transition at START begins a repeating cycle. OUT remains ON for t.On and OFF for t.OFF.

Non-retriggerable timed output: START switches OUT ON and the output stays active for t.SEt. Additional START signals are ignored until the timing period has finished.

Falling-edge two-stage timing: After an ON → OFF transition at START, the timer waits for tA, then switches OUT ON. OUT switches OFF after tB. A new START trigger is not accepted until tB has finished.

Power-on delay: OUT switches ON after t.SEt following power-up. START is not used in this function. RESET switches the output OFF.

START-controlled count-up: While START is ON, OUT is active and the timer counts upward. When START turns OFF, counting stops and the current value remains on the display.

Delayed OFF after falling edge: OUT remains ON while START is active. After an ON → OFF transition, OUT switches OFF when t.SEt has elapsed.

Falling-edge timed output: An ON → OFF transition switches OUT ON. OUT switches OFF after t.SEt. If START returns to ON, OUT switches OFF.

Count-up with threshold output: The timer counts upward while START is ON. When START turns OFF, counting stops and the displayed value is held. Once the accumulated value exceeds t.SEt, OUT switches ON. RESET clears the display and switches OUT OFF.

RESET: Used to cancel the active output and reset the timing sequence.
GATE: Timing pauses while GATE is ON; the current value is retained.

Time ranges

99:59 hours
99:59 minutes
599.9 seconds

Resolution: 1 minute / 1 second / 0.1 second.
Accuracy: ±0.5% of full scale.

For Mode 1, the minimum t.On and t.OFF settings are 000.1 seconds, 00.01 minutes or 00.01 hours. Time counts upward in Modes 6 and 7; the other modes count down. In all output functions, timing pauses while GATE is ON.

Technical details

Front dimensions: 48 × 48 mm
Panel cut-out: 45.5 × 45.5 mm
Display: Dual 4-digit, 7-segment display.

Control inputs: START / RESET / GATE.
Maximum input voltage: 32 VDC.
OFF level: 0–2 VDC.
ON level: 7–32 VDC.

Sensor supply output: 12 VDC, maximum 50 mA, unregulated.

Relay output: NO – Common – NC, 250 VAC / 2 A resistive load.
SSR output: Open-collector NPN, maximum 30 V / 100 mA.

Selectable output functions: 13.
Supply voltage: 100–240 VAC, 50–60 Hz or optional 24 VAC/DC.
Power consumption: < 6 VA.

Relative humidity: Up to 80% at 30 °C, decreasing linearly to 50% at 50 °C, non-condensing.
Operating altitude: < 2000 m.

The DZ304 is a good fit when a 48 × 48 mm timer is needed and the timing sequence has to follow external START, RESET or GATE signals rather than simply starting with the supply voltage.

Gemo DZ304 User Manual (PDF)

Gemo price list
Gemo contact information
Gemo products

Installation: Wiring and commissioning should be carried out by qualified technical personnel.

Before powering the timer, check the supply voltage, START / RESET / GATE input levels and the relay or NPN output wiring against the product documentation.

Incorrect wiring or operation outside the specified electrical limits may damage the timer and may affect warranty coverage.

Write a review

Note: HTML is not translated!
Bad Good

Gemo DZ304

  • 27.00USD

  • Ex Tax: 27.00USD

Related Products

Omron H3CR-A

Omron H3CR-A

Hello,   Wellcome to our Omron H3CR-A / Timer, plug-in, 11-pin, DIN 48 x 48 mm, multifunct..

73.00USD Ex Tax: 73.00USD

DEZ-44-R-A -Easy timer

DEZ-44-R-A -Easy timer

The DERELL DEZ-44-R-A digital time relay is a compact and practical solution for timing operations i..

59.00USD Ex Tax: 59.00USD

DEZ-44-RS-A - With start timer

DEZ-44-RS-A - With start timer

Start input supported DERELL DEZ-44-RS-A model time relays belong to the basic time relay series com..

60.00USD Ex Tax: 60.00USD

DGZ-37-RS-A - Electronic timer

DGZ-37-RS-A - Electronic timer

The DGZ-37R-A advanced functional timer is a model that can be used for general time-based applica..

66.00USD Ex Tax: 66.00USD