Gemo AR2-A-230VAC-14D-RTC – Expandable Smart Relay / PLC with Relay Outputs and Real-Time Clock
Gemo AR2-A-230VAC-14D-RTC is a compact, expandable smart relay / PLC designed for machine automation, control panels, sequencing, timing and general-purpose logic applications. The controller operates directly from an AC mains supply and provides 14 digital inputs, 10 relay outputs, a dedicated PTC temperature input and a battery-backed real-time clock.
Gemo AR2 controllers have been available through our website since 2011.
Power supply and I/O
Power supply: 100–240 VAC, 50/60 Hz. Although the model designation includes 230VAC, the controller is designed for a wide AC supply range. Maximum power consumption is approximately 6 W.
Digital inputs: 14 DC digital inputs are provided. The inputs are interpreted as OFF at approximately 0–2 VDC and ON at approximately 10–32 VDC. Standard digital input filtering is at least 8 ms for both ON-to-OFF and OFF-to-ON transitions.
Auxiliary DC supply: The AC-powered version provides an internal 18 VDC / 50 mA auxiliary supply for use with the controller's digital-input circuitry. The AC mains supply of the controller should therefore not be confused with the voltage level used at its digital inputs.
Relay outputs: 10 digital relay outputs, rated up to 250 VAC / 2 A for resistive loads. Suitable protection and interface devices should be considered when switching inductive loads such as contactor coils, valves or similar equipment.
Analog input: This model has no general-purpose 0–10 V analog input.
Analog output: Not available.
PTC temperature input: One dedicated input is provided for a 2-wire PTC temperature sensor, covering approximately -50 to +150 °C.
Battery-backed real-time clock
The AR2-A-230VAC-14D-RTC includes a battery-backed real-time clock. Weekly and annual schedules can be created so that pumps, fans, lighting, ventilation systems and machine functions operate according to actual date and time.
For applications that do not require calendar-based scheduling, see the Gemo AR2-A-230VAC-14D version without RTC.
Ladder programming and internal functions
The AR2 series is programmed with GEMO Ladder Editor. The ladder workspace provides 256 program lines, 5 contact columns and 1 output column. Rising-edge and falling-edge functions can be assigned to contacts where required.
Programs are transferred through the controller's RS-232 programming interface.
Available logic resources include 32 timers, 32 16-bit up/down counters, 32 offset counter comparators and internal auxiliary relay functions.
Ladder scan time: Approximately 10 ms or less, depending on the application program.
Timer resolution: Minimum timing resolution is approximately 10 ms. Timer accuracy is specified as ±0.1% or 1 digit, whichever is greater.
High-speed counter inputs: Two high-speed counter functions are available. Minimum ON and OFF times are approximately 1.25 ms, with a maximum input frequency of approximately 400 Hz at 50% duty cycle.
Servo and step motor control
The relay-output AR2-A-230VAC-14D-RTC does not provide a high-speed pulse / direction output for positioning servo or step motor systems.
Applications requiring pulse-train positioning should use a PLC or motion controller specifically designed for high-speed motion control.
PID control
A built-in PID control algorithm is not provided. Closed-loop temperature, pressure, flow or similar process-control applications should use a suitable process controller or a PLC with integrated PID functionality.
Display and operator functions
The controller features a 2 × 16 character backlit LCD display, three programmable front-panel function keys and a three-level password-protected menu system. Machine status, counter values, timer information and operator messages can be displayed directly on the unit.
Can an external HMI be connected? Yes. A compatible operator panel / HMI can be integrated using the appropriate communication hardware.
For Modbus RTU communication, the appropriate AR2-S-24VDC-MB1 communication gateway and compatible software are required. The RS-485 expansion interface should not automatically be treated as a standard direct Modbus HMI port.
I/O expansion and RS-485
Compatible AR2 expansion modules can be connected through the controller's RS-485 expansion interface. Depending on the expansion configuration, the complete system can be extended to approximately 28 digital inputs and 20 digital outputs.
RS-485 cabling: Use twisted, shielded, 2-core 24 AWG communication cable. A-to-A and B-to-B polarity should be maintained, and line termination should follow the manufacturer's installation requirements.
Operating environment
Operating temperature: 0 to 50 °C.
Protection rating: IP20 according to EN 60529.
Relative humidity: Up to 80% at 30 °C, decreasing linearly to approximately 50% at 50 °C, non-condensing.
Installation altitude: Below approximately 2000 m above sea level.
Terminal tightening torque: Maximum 0.5 N·m.
EMC and panel layout: When the controller is installed alongside AC motor drives, frequency inverters, contactors or other sources of electrical noise, signal and communication wiring should be separated from power wiring wherever practical. Proper grounding and shielding should also be applied.
Because this version is powered directly from the AC mains, correct supply protection, neutral integrity and physical separation between mains wiring and low-voltage control wiring are particularly important.
Gemo AR2 programming software and documentation
Download GEMO Ladder Editor V2.4 programming software for AR2 programming and configuration.
For programming instructions, timer and counter functions and RTC configuration, refer to the Gemo AR2 PLC English user manual.
For additional models and pricing, visit the Gemo price list, Gemo Electronic main page or our PLC product group.
For technical information and product selection, use our Gemo contact page or contact us at gemo@otomasyonavm.com.
Installation notice: Installation, wiring and commissioning of the Gemo AR2 should be carried out only by qualified technical personnel. Disconnect the AC supply before wiring or servicing the controller. Suitable external isolation and overcurrent protection should be provided, and mains, control and communication wiring should be installed in accordance with the manufacturer's instructions and applicable electrical-safety requirements.
Gemo AR2-A-230VAC-14D-RTC
- Mağaza: Efes Otomasyon
- Store: Efes Automation
- Brands GEMO
- Product Code: Gemo AR2-A-230VAC-14D-RTC
- Availability: 12
-
110.00USD
- Ex Tax: 110.00USD
Related Products
DLC-R1410-R-A
DERELL DLC-R1410-R-A is a programmable logic relay. It is used in smaller automation applications re..
100.00USD Ex Tax: 100.00USD
DLC-R1410-R-B
DERELL DLC-R1410-R-B is a programmable logic relay. It is used in smaller automation applications re..
100.00USD Ex Tax: 100.00USD
DLC-R1410-GR-B
DERELL DLC-R1410-GR-B is a programmable logic relay. It is used in smaller automation applications r..
100.00USD Ex Tax: 100.00USD
DLC-R1410-GR-A
DERELL DLC-R1410-GR-A is a programmable logic relay. It is used in smaller automation applications r..
100.00USD Ex Tax: 100.00USD