Delta VFD-V Fault Codes 3
E 30: Internal EEPROM cannot be programmed.
+ Corrective Actions:
- Press the “RESET” key to the factory setting.
- Return to the factory if the problem persists.
E 31: Internal EEPROM cannot be read.
+ Corrective Actions:
- Press the “RESET” key to the factory setting.
- Return to the factory if the problem persists.
E 32: Hardware failure in current detection.
+ Corrective Actions:
- Re-power on to try it again.
- If the fault code is still displayed on the keypad, please return to the factory.
E 33: U-phase error.
+ Corrective Actions:
- Re-power on to try it again.
- If the fault code is still displayed on the keypad, please return to the factory.
E 34: V-phase error.
+ Corrective Actions:
- Re-power on to try it again.
- If the fault code is still displayed on the keypad, please return to the factory.
E 35: W-phase error.
+ Corrective Actions:
- Re-power on to try it again.
- If the fault code is still displayed on the keypad, please return to the factory.
E 36: CC (current clamp) error.
+ Corrective Actions:
- Re-power on to try it again.
- If the fault code is still displayed on the keypad, please return to the factory.
E 37: OC hardware error.
+ Corrective Actions:
- Re-power on to try it again.
- If the fault code is still displayed on the keypad, please return to the factory.
E 38: OV hardware error.
+ Corrective Actions:
- Re-power on to try it again.
- If the fault code is still displayed on the keypad, please return to the factory.
E 39: GFF hardware error.
+ Corrective Actions:
- Re-power on to try it again.
- If the fault code is still displayed on the keypad, please return to the factory.
E 40: Auto-tuning error.
+ Corrective Actions:
- Check cabling between drive and motor.
- Check the motor capacity and parameters settings.
- Retry again.
E 41: PID loss (ACI).
+ Corrective Actions:
- Check the wiring of the PID feedback.
- Check the PID parameters settings.
E 42: PG feedback error.
+ Corrective Actions:
- Check if Pr.10-01 is not set to 0 when it is PG feedback control.
E 43: PG feedback loss.
+ Corrective Actions:
- Check the wiring of the PG feedback.
E 44: PG feedback stall.
+ Corrective Actions:
- Check the wiring of the PG feedback.
- Check if the setting of PI gain and deceleration is suitable.
- Return to the factory if necessary.
E 45: PG slip error.
+ Corrective Actions:
- Check the wiring of the PG feedback.
- Check if the setting of PI gain and deceleration is suitable.
- Return to the factory if necessary.
E 46: Pulse input error.
+ Corrective Actions:
- Check the pulse wiring.
- Return to the factory if necessary.
E 47: Pulse input loss.
+ Corrective Actions:
- Check the pulse wiring.
- Return to the factory if necessary.
E 48: ACI loss.
+ Corrective Actions:
- Check the ACI wiring.
- Check if the ACI signal is less than 4mA.
E 49: External fault.
+ Corrective Actions:
- Input EF (N.O.) on the external terminal is closed to GND, output U, V, W will be turned off.
- Give the RESET command after the fault has been cleared.
E 50: Emergency stop.
+ Corrective Actions:
- When the multi-function input terminals MI1 to MI8 are set to emergency stop and the AC motor drive stops output.
- Press RESET after the fault has been cleared.
E 51: Base block.
+ Corrective Actions:
- When the multi-function input terminals MI1 to MI8 are set to base block and the AC motor drive stops output.
- Press RESET after the fault has been cleared.
E 52: Password is locked.
+ Corrective Actions:
- The keypad will be locked. Turn the power ON after power OFF to re-enter the correct password. See Pr.00-07 and 00-08.
E 54: Illegal function code.
+ Corrective Actions:
- Check if the function code is correct (function code must be 03, 06, 10, 63).
E 55: Illegal data length.
+ Corrective Actions:
- Check if the communication data length is correct.
E 56: Illegal data value.
+ Corrective Actions:
- Check if the data value exceeds the max./min. value.
E 57: Illegal communication address.
+ Corrective Actions:
- Check if the communication address is correct.
E 58: Communication time-out.
+ Corrective Actions:
- Check if the wiring for the communication is correct.
E 59: Keypad (KPVL-CC01) communication time-out.
+ Corrective Actions:
- Check if the wiring for the communication is correct.
- Check if there is any wrong with the keypad.
E 60: Brake chopper fail.
+ Corrective Actions:
- Press the RESET key to correct it. If the fault code is still displayed on the keypad, please return to the factory.
E 63: Safety loop error.
+ Corrective Actions:
- Check if the jumper JP18 is short circuit.
- Re-power on to try it. If the fault code is still displayed on the keypad, please return to the factory.
E 64: Mechanical brake error.
+ Corrective Actions:
- Check if the mechanical brake signal is correct.
- Check if the detection time setting of the mechanical brake (Pr.02-35) is correct.
E 65: PG hardware error.
+ Corrective Actions:
- Check if the wiring of PG feedback is correct.
- If the fault code is still displayed on the keypad with correct PG feedback, please return to the factory.
E 66: Electromagnetic valve error.
+ Corrective Actions:
- Check if the signal of the electromagnetic valve is correct.
- Check if the setting of Pr.02-36 is correct.
Reset Methods:
There are three methods to reset the AC motor drive after solving the fault:
1- Press the RESET key on KPVL-CC01.
2- Set the external terminal to “RESET” and then set it to be ON.
3- Send the “RESET” command by communication.
Summary of Corrective Actions
To ensure the AC motor drive functions properly and resolves any faults:
+ Check for correct wiring and connections.
+ Adjust settings as necessary (e.g., torque compensation, acceleration/deceleration times).
+ Monitor and adjust environmental conditions (e.g., temperature, humidity).
+ Use appropriate components (e.g., higher power models, brake resistors) as needed.
+ Consult with the manufacturer (DELTA) for persistent or complex issues.
+ Delta VFD-V (VE,VL) User Manual
+ Delta VFD-V Fault Codes 2 >>
+ Delta VFD-V Fault Codes 3 >>
-----------------