Motor Cannot Run:

+ Explanation: Motor cannot run.
+ Corrective Actions:
- Check if non-fuse breaker and magnetic contactor are ON.
- Reset after clearing fault and then RUN.
- Ensure input voltage is normal.
- Input "RUN" command by keypad.
- Use a jumper or DC reactor if necessary.
- Press RUN key to check if it can run.
- Check if input FWD or REV command is correct.
- Ensure the wiring of terminal MI1 and between MI2-DCM is correct.
- Correct connection if necessary.
- Check if the parameter setting and wiring of analog signal and multi-step speed are correct.
- Ensure there is no malfunction in the motor or AC motor drive.

Fault Code E 01: Over-current during acceleration.

- Check for short-circuits.
- Increase acceleration time.
- Replace the AC motor drive with a higher power model if necessary.

Fault Code E 02:  Over-current during deceleration.
 
- Check for short-circuits.
- Increase deceleration time.
- Replace the AC motor drive with a higher power model if necessary.

Fault Code E 03:   Over-current during steady state operation.
 
- Check for short-circuits.
- Check for sudden increases in motor loading.
- Replace the AC motor drive with a higher power model if necessary.

Fault Code E 04:  Ground fault.
 
- Check wiring connections for short circuits and poor insulation.
- Check IGBT power module.

Fault Code E 05: Short-circuit between upper and lower bridge of the IGBT module.
 
- Return to the factory.

Fault Code E 06: Over-current at stop.
 
- Return to the factory.

Fault Code E 07: DC BUS over-voltage during acceleration (230V: DC 450V; 460V: DC 900V).
 
- Check input voltage.
- Increase deceleration time.
- Add optional brake resistor if necessary.

Fault Code E 08: DC BUS over-voltage during deceleration (230V: DC 450V; 460V: DC 900V).
 
- Check input voltage.
- Increase deceleration time.
- Add optional brake resistor if necessary.

Fault Code E 09:  DC BUS over-voltage during constant speed (230V: DC 450V; 460V: DC 900V).
 
- Check input voltage.
- Increase deceleration time.
- Add optional brake resistor if necessary.

Fault Code E 10: DC BUS over-voltage at stop.
 
- Check input voltage.
- Check for voltage transients.

Fault Code E 11: DC BUS voltage is less than Pr.06-00 during acceleration.
 
- Check input voltage.
- Check for sudden load.

Fault Code E 12:  DC BUS voltage is less than Pr.06-00 during deceleration.
 
- Check input voltage.
- Check for sudden load.

Fault Code E 13: DC BUS voltage is less than Pr.06-00 during constant speed.
 
- Check input voltage.
- Check for sudden load.

Fault Code E 14: Low voltage at stop.
 
- Check input voltage.
- Check for sudden load.

Fault Code E 15: Phase loss.

- Check power source input.
- Ensure all three phases are connected properly.

Fault Code E 16:  IGBT overheating (IGBT temperature exceeds protection level: 1 to 15HP: 90°C; 20 to 100HP: 100°C).
 
- Ensure ambient temperature is within the specified range.
- Make sure ventilation holes are not obstructed.
- Remove foreign objects from heatsinks.
- Check and clean the fan.
- Provide adequate ventilation.

Fault Code E 17: Heatsink overheating.
 
- Return to the factory.

Fault Code E 18: IGBT hardware failure.
 
- Return to the factory.

Fault Code E 19: Heatsink overheating.
 
- Return to the factory.

Fault Code E 20: Fan failure.
 
- Ensure the fan is not obstructed.
- Return to the factory.

Fault Code E 21: Overload (the AC motor drive detects excessive drive output current).
 
- Check whether the motor is overloaded.
- Take a higher power AC motor drive model if necessary.

Fault Code E 22: Motor 1 overload.
 
- Check whether the motor is overloaded.
- Ensure the motor rated current setting (Pr.05-01) is suitable.
- Take a higher power AC motor drive model if necessary.

Fault Code E 24:  Motor overheating (internal temperature exceeds Pr.06-30).
 
- Ensure the motor is not obstructed.
- Ensure ambient temperature is within the specified range.
- Take a higher power AC motor drive model if necessary.

Fault Code E 26: Electronic Thermal Relay 1 Protection.
 
- Check whether the motor is overloaded.
- Ensure motor rated current setting (Pr.05-01) is suitable.
- Check electronic thermal relay function.
- Take the next higher power AC motor drive model if necessary.

Fault Code E 27: Electronic Thermal Relay 2 Protection.
 
- Check whether the motor is overloaded.
- Check whether motor rated current setting (Pr.05-01) is suitable.
- Check electronic thermal relay function.
- Take the next higher power AC motor drive model if necessary.


+ Delta VFD-V (VE,VL)  User Manual 

+ Delta VFD-V Fault Codes >>

+ Delta VFD-V Fault Codes 2 >>

+ Delta VFD-V Fault Codes 3 >>

-----------------

++ Delta 2 main page

+ VFD main Page -

-

"* The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."  13.04.2013