Delta VFD-V Fault Codes 2
Hi everyone,
Motor Cannot Run:
+ Explanation: Motor cannot run.
+ Corrective Actions:
- Check if non-fuse breaker and magnetic contactor are ON.
- Reset after clearing fault and then RUN.
- Ensure input voltage is normal.
- Input "RUN" command by keypad.
- Use a jumper or DC reactor if necessary.
- Press RUN key to check if it can run.
- Check if input FWD or REV command is correct.
- Ensure the wiring of terminal MI1 and between MI2-DCM is correct.
- Correct connection if necessary.
- Check if the parameter setting and wiring of analog signal and multi-step speed are correct.
- Ensure there is no malfunction in the motor or AC motor drive.
Fault Code E 01: Over-current during acceleration.
- Check for short-circuits.
- Increase acceleration time.
- Replace the AC motor drive with a higher power model if necessary.
Fault Code E 02: Over-current during deceleration.
- Check for short-circuits.
- Increase deceleration time.
- Replace the AC motor drive with a higher power model if necessary.
Fault Code E 03: Over-current during steady state operation.
- Check for short-circuits.
- Check for sudden increases in motor loading.
- Replace the AC motor drive with a higher power model if necessary.
Fault Code E 04: Ground fault.
- Check wiring connections for short circuits and poor insulation.
- Check IGBT power module.
Fault Code E 05: Short-circuit between upper and lower bridge of the IGBT module.
- Return to the factory.
Fault Code E 06: Over-current at stop.
- Return to the factory.
Fault Code E 07: DC BUS over-voltage during acceleration (230V: DC 450V; 460V: DC 900V).
- Check input voltage.
- Increase deceleration time.
- Add optional brake resistor if necessary.
Fault Code E 08: DC BUS over-voltage during deceleration (230V: DC 450V; 460V: DC 900V).
- Check input voltage.
- Increase deceleration time.
- Add optional brake resistor if necessary.
Fault Code E 09: DC BUS over-voltage during constant speed (230V: DC 450V; 460V: DC 900V).
- Check input voltage.
- Increase deceleration time.
- Add optional brake resistor if necessary.
Fault Code E 10: DC BUS over-voltage at stop.
- Check input voltage.
- Check for voltage transients.
Fault Code E 11: DC BUS voltage is less than Pr.06-00 during acceleration.
- Check input voltage.
- Check for sudden load.
Fault Code E 12: DC BUS voltage is less than Pr.06-00 during deceleration.
- Check input voltage.
- Check for sudden load.
Fault Code E 13: DC BUS voltage is less than Pr.06-00 during constant speed.
- Check input voltage.
- Check for sudden load.
Fault Code E 14: Low voltage at stop.
- Check input voltage.
- Check for sudden load.
Fault Code E 15: Phase loss.
- Check power source input.
- Ensure all three phases are connected properly.
Fault Code E 16: IGBT overheating (IGBT temperature exceeds protection level: 1 to 15HP: 90°C; 20 to 100HP: 100°C).
- Ensure ambient temperature is within the specified range.
- Make sure ventilation holes are not obstructed.
- Remove foreign objects from heatsinks.
- Check and clean the fan.
- Provide adequate ventilation.
Fault Code E 17: Heatsink overheating.
- Return to the factory.
Fault Code E 18: IGBT hardware failure.
- Return to the factory.
Fault Code E 19: Heatsink overheating.
- Return to the factory.
Fault Code E 20: Fan failure.
- Ensure the fan is not obstructed.
- Return to the factory.
Fault Code E 21: Overload (the AC motor drive detects excessive drive output current).
- Check whether the motor is overloaded.
- Take a higher power AC motor drive model if necessary.
Fault Code E 22: Motor 1 overload.
- Check whether the motor is overloaded.
- Ensure the motor rated current setting (Pr.05-01) is suitable.
- Take a higher power AC motor drive model if necessary.
Fault Code E 24: Motor overheating (internal temperature exceeds Pr.06-30).
- Ensure the motor is not obstructed.
- Ensure ambient temperature is within the specified range.
- Take a higher power AC motor drive model if necessary.
Fault Code E 26: Electronic Thermal Relay 1 Protection.
- Check whether the motor is overloaded.
- Ensure motor rated current setting (Pr.05-01) is suitable.
- Check electronic thermal relay function.
- Take the next higher power AC motor drive model if necessary.
Fault Code E 27: Electronic Thermal Relay 2 Protection.
- Check whether the motor is overloaded.
- Check whether motor rated current setting (Pr.05-01) is suitable.
- Check electronic thermal relay function.
- Take the next higher power AC motor drive model if necessary.