Delta VFD-V Fault Codes 3

E 30:  Internal EEPROM cannot be programmed.
+ Corrective Actions:
- Press the “RESET” key to the factory setting.
- Return to the factory if the problem persists.

E 31: Internal EEPROM cannot be read.
+ Corrective Actions:
- Press the “RESET” key to the factory setting.
- Return to the factory if the problem persists.

E 32: Hardware failure in current detection.
+ Corrective Actions:
- Re-power on to try it again.
- If the fault code is still displayed on the keypad, please return to the factory.

E 33: U-phase error.

+ Corrective Actions:
- Re-power on to try it again.
- If the fault code is still displayed on the keypad, please return to the factory.

E 34:  V-phase error.
+ Corrective Actions:
- Re-power on to try it again.
- If the fault code is still displayed on the keypad, please return to the factory.

E 35:  W-phase error.
+ Corrective Actions:
- Re-power on to try it again.
- If the fault code is still displayed on the keypad, please return to the factory.

E 36: CC (current clamp) error.
+ Corrective Actions:
- Re-power on to try it again.
- If the fault code is still displayed on the keypad, please return to the factory.

E 37:  OC hardware error.
+ Corrective Actions:
- Re-power on to try it again.
- If the fault code is still displayed on the keypad, please return to the factory.

E 38: OV hardware error.
+ Corrective Actions:
- Re-power on to try it again.
- If the fault code is still displayed on the keypad, please return to the factory.

E 39: GFF hardware error.
+ Corrective Actions:
- Re-power on to try it again.
- If the fault code is still displayed on the keypad, please return to the factory.

E 40: Auto-tuning error.
+ Corrective Actions:
- Check cabling between drive and motor.
- Check the motor capacity and parameters settings.
- Retry again.

E 41: PID loss (ACI).
+ Corrective Actions:
- Check the wiring of the PID feedback.
- Check the PID parameters settings.

E 42:  PG feedback error.
+ Corrective Actions:
- Check if Pr.10-01 is not set to 0 when it is PG feedback control.

E 43:  PG feedback loss.
+ Corrective Actions:
- Check the wiring of the PG feedback.

E 44:  PG feedback stall.
+ Corrective Actions:
- Check the wiring of the PG feedback.
- Check if the setting of PI gain and deceleration is suitable.
- Return to the factory if necessary.

E 45: PG slip error.
+ Corrective Actions:
- Check the wiring of the PG feedback.
- Check if the setting of PI gain and deceleration is suitable.
- Return to the factory if necessary.

E 46: Pulse input error.
+ Corrective Actions:
- Check the pulse wiring.
- Return to the factory if necessary.

E 47: Pulse input loss.
+ Corrective Actions:
- Check the pulse wiring.
- Return to the factory if necessary.

E 48: ACI loss.
+ Corrective Actions:
- Check the ACI wiring.
- Check if the ACI signal is less than 4mA.

E 49: External fault.
+ Corrective Actions:
- Input EF (N.O.) on the external terminal is closed to GND, output U, V, W will be turned off.
- Give the RESET command after the fault has been cleared.

E 50: Emergency stop.
+ Corrective Actions:
- When the multi-function input terminals MI1 to MI8 are set to emergency stop and the AC motor drive stops output.
- Press RESET after the fault has been cleared.

E 51: Base block.
+ Corrective Actions:
- When the multi-function input terminals MI1 to MI8 are set to base block and the AC motor drive stops output.
- Press RESET after the fault has been cleared.

E 52: Password is locked.
+ Corrective Actions:
- The keypad will be locked. Turn the power ON after power OFF to re-enter the correct password. See Pr.00-07 and 00-08.

E 54: Illegal function code.
+ Corrective Actions:
- Check if the function code is correct (function code must be 03, 06, 10, 63).

E 55: Illegal data length.
+ Corrective Actions:
- Check if the communication data length is correct.

E 56: Illegal data value.
+ Corrective Actions:
- Check if the data value exceeds the max./min. value.

E 57: Illegal communication address.
+ Corrective Actions:
- Check if the communication address is correct.

E 58: Communication time-out.
+ Corrective Actions:
- Check if the wiring for the communication is correct.

E 59: Keypad (KPVL-CC01) communication time-out.
+ Corrective Actions:
- Check if the wiring for the communication is correct.
- Check if there is any wrong with the keypad.

E 60: Brake chopper fail.
+ Corrective Actions:
- Press the RESET key to correct it. If the fault code is still displayed on the keypad, please return to the factory.

E 63: Safety loop error.
+ Corrective Actions:
- Check if the jumper JP18 is short circuit.
- Re-power on to try it. If the fault code is still displayed on the keypad, please return to the factory.

E 64: Mechanical brake error.
+ Corrective Actions:
- Check if the mechanical brake signal is correct.
- Check if the detection time setting of the mechanical brake (Pr.02-35) is correct.

E 65: PG hardware error.
+ Corrective Actions:
- Check if the wiring of PG feedback is correct.
- If the fault code is still displayed on the keypad with correct PG feedback, please return to the factory.

E 66: Electromagnetic valve error.
+ Corrective Actions:
- Check if the signal of the electromagnetic valve is correct.
- Check if the setting of Pr.02-36 is correct.

Reset Methods:
There are three methods to reset the AC motor drive after solving the fault:

1- Press the RESET key on KPVL-CC01.
2- Set the external terminal to “RESET” and then set it to be ON.
3- Send the “RESET” command by communication.

Summary of Corrective Actions

To ensure the AC motor drive functions properly and resolves any faults:

+ Check for correct wiring and connections.
+ Adjust settings as necessary (e.g., torque compensation, acceleration/deceleration times).
+ Monitor and adjust environmental conditions (e.g., temperature, humidity).
+ Use appropriate components (e.g., higher power models, brake resistors) as needed.
+ Consult with the manufacturer (DELTA) for persistent or complex issues.


+ Delta VFD-V (VE,VL)  User Manual 

+ Delta VFD-V Fault Codes >>

+ Delta VFD-V Fault Codes 2 >>

+ Delta VFD-V Fault Codes 3 >>

-----------------

++ Delta 2 main page

+ VFD main Page -

-

"* The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."  13.04.2013