Delta VFD-V Fault Codes


Hi everone,

Motor Cannot Run:

+ Explanation: Motor cannot run.
+ Corrective Actions:
- Check if non-fuse breaker and magnetic contactor are ON.
- Reset after clearing fault and then RUN.
- Ensure input voltage is normal.
- Input "RUN" command by keypad.
- Use a jumper or DC reactor if necessary.
- Press RUN key to check if it can run.
- Check if input FWD or REV command is correct.
- Ensure the wiring of terminal MI1 and between MI2-DCM is correct.
- Correct connection if necessary.
- Check if the parameter setting and wiring of analog signal and multi-step speed are correct.
- Ensure there is no malfunction in the motor or AC motor drive.


+ Explanation: Motor can run but cannot change speed.
+ Corrective Actions:
- Check if the setting of the max. frequency is too low.
- Modify the setting if the frequency is out of range.
- Ensure the wiring between MI1~MI8 to COM is correct.
- Adjust accel./decel. time by load inertia if necessary.
- If there is a malfunction or misoperation due to noise, contact DELTA.

+ Explanation: Motor stalls during acceleration.
+ Corrective Actions:
- Increase acceleration time if too short.
- Reduce load or increase the capacity of the AC motor drive.
- Check if the inertia of motor and load is very high.
- Increase torque compensation if necessary.
- Ensure suitable wiring between the motor or AC motor drive.

+ Explanation: Motor does not run as expected.
+ Corrective Actions:
- Adjust V/f characteristic and lower torque compensation if necessary.
- Ensure output voltage of U, V, W is balanced.
- If there is a malfunction or misoperation due to noise, contact DELTA.

+ Explanation: Electromagnetic/induction noise.
+ Corrective Actions:
- Add surge killer on the relay or contact to suppress switching surge between ON/OFF.
- Shorten the wiring length of the control circuit or serial circuit and separate from the main circuit wiring.
- Comply with the wiring regulation for those shielded wires and use an isolation amplifier for long wires.
- Ensure the grounding terminal complies with local regulation and ground independently.
- Connect a noise filter at the input terminal of the AC motor drive to prevent noise from the power circuit.

+ Explanation: Ensure compliance with environmental conditions.
+ Corrective Actions:
- Prevent vibration and ensure vibration tolerance is within specification.
- Store in a clean, dry location free from corrosive fumes/dust.
- Maintain suitable surrounding temperature and humidity.
- Ensure proper storage within a relative humidity range of 0% to 90% and non-condensing environment.

+ Explanation: High harmonic at power side.
+ Corrective Actions:
- Separate the power system or use a transformer for the AC motor drive.
- Use a reactor at the power input terminal of the AC motor drive.
- Use a serial reactor to prevent capacitor damage from high harmonic.


Error Codes and Explanations

 Over Current (OC):

+ Code: OC
+ Explanation: Over-current during acceleration.
+ Corrective Actions:
- Check if there are any short circuits or grounding issues between U, V, W and the motor.
- Remove short circuit or ground fault.
- Reduce the load or increase the power of the AC motor drive.
- Reduce torque compensation if needed.
- Ensure suitable torque compensation.
- If the problem persists, there may be a malfunction or error due to noise; contact DELTA.
- Consider extending acceleration or deceleration time.
- Check the braking method and contact DELTA if necessary.
- Assess whether the load changes suddenly.
- Increase accel/decel time if the load is too large.

Ground Fault:

+ Code: GFF

+ Explanation: Ground fault.
+ Corrective Actions:
- If the output circuit (cable or motor) of the AC motor drive is grounded, remove grounding.
- If the issue persists, the AC motor drive may have a malfunction or misoperation due to noise; contact DELTA.

Over Voltage (OV - Ou):

+ Code: OV / ou
+ Explanation: Over voltage.
+ Corrective Actions:
- Check if the input voltage is within the specification.
- Reduce voltage to be within spec.
- If over-voltage occurs without load, the AC motor drive may have a malfunction or misoperation due to noise; contact DELTA.
- When OV occurs, check if the voltage of DC BUS is greater than the protection value.
- Increase deceleration time if OV occurs during sudden acceleration stops.
- Use a braking unit or DC braking if necessary.
- Check control methods and contact DELTA if needed.

 Low Voltage (LV / Lu):

+ Code: Lv/ Lu
+ Explanation: Low voltage.
+ Corrective Actions:
- Check if there is any malfunction component in the power supply circuit or disconnection.
- Change defective components and check connections.
- Ensure voltage is within the specification.
- Change the power supply system if required.
- Check for heavy load with high start current in the same power system.
- Ensure suitable transformer power capacity.
- Check if voltage between +1/+2 and - is greater than Pr.06-00.
- If the control circuit has a malfunction due to noise, contact DELTA.

Over Heat (OH):

+ Code: OH
+ Explanation: AC motor drive overheats.
+ Corrective Actions:
- Check if the temperature of the heat sink is larger than 90°C.
- Reduce load if the temperature is too high.
- Ensure the cooling fan functions normally and is not jammed.
- Adjust surrounding temperature to specification.
- If the load is too large, reduce it or increase the power of the AC motor drive.
- If there is a malfunction due to noise, contact DELTA.

Overload (OL):

+ Code: OL
+ Explanation: Overload.
+ Corrective Actions:
- Reduce load or increase the power of the AC motor drive.
- Check if the setting of the electronic thermal relay is suitable.
- Modify the setting if necessary.
- If the load is too large, there may be a malfunction or misoperation due to noise; contact DELTA.

Abnormal Display of KPVL-CC01:

+ Code: N/A
+ Explanation: Abnormal display or no display.
+ Corrective Actions:
- Turn the power off and on again after the display is off.
- Check if all connectors are connected well and if there is no noise.
- If the AC motor drive has a malfunction, contact DELTA.

 Phase Loss (PHL):

+ Code: PHL
+ Explanation: Phase loss.
+ Corrective Actions:
- Check if the wiring of terminals R, S, and T is OK.
- Tighten all screws on the terminals.
- Check for abnormal power in the wiring and power system.
- Ensure the input voltage of R, S, and T is balanced.


+ Delta VFD-V (VE,VL)  User Manual 

+ Delta VFD-V Fault Codes >>

+ Delta VFD-V Fault Codes 2 >>

+ Delta VFD-V Fault Codes 3 >>

-----------------

++ Delta 2 main page

+ VFD main Page -

-

"* The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."  13.04.2013