Delta TP Text Panels

Delta TP text panels display machine messages and values and accept operator commands through a monochrome LCD and physical keys. TP02G, TP04G, TP05G and TP08G do not identify one common display or interface arrangement. The name “text panel” also does not exclude bitmap or graphical objects on supported models; object availability depends on the selected target.

This page covers standalone TP text terminals. For local I/O and PLC functions, examine TP04P and TP70P separately. Migration to a touch HMI such as DOP-100 requires a review of the screen project, key behaviour, PLC addresses and enclosure opening.

TP02G and TP04G model distinctions

TP02G-AS1: a 160×32-pixel display, 16 keys in total and 256 KB flash suit compact message/value interfaces. RS-232 and RS-485 are available. The catalogue gives a nominal 136×85 mm panel opening. The two-line description must be read together with the selected font and character layout.

TP04G-AS2: a 128×64-pixel display and 12 keys in total. RS-232, RS-422 and RS-485 require the correct interface and operating mode. A nominal 136×85 mm opening shared with TP02G does not establish direct project or communication compatibility.

TP04G-AL-C: a 4.1-inch, 192×64-pixel display with 10 keys and an RS-232 interface. TP04G-AL2 adds RS-422/RS-485 options at the same display resolution. The catalogue lists a nominal 151×96 mm opening for both. Do not select an AL2 communication cable on the assumption that AL-C has the same additional interfaces.

TP04G-BL-C: a 4.1-inch, 192×64-pixel display, 17 keys including 0–9 numeric keys, 24 VDC supply and RS-232/RS-422/RS-485 interfaces. Its nominal panel opening is 163×96 mm. Equal resolution to an AL model does not mean the same mounting opening.

TP04G-BL-CU: this 192×64-pixel version uses USB for project transfers and RS-232 for the PLC connection. It receives 5 V through USB or the suitable PLC connection; do not apply the BL-C’s 24 V arrangement. The manual specifies DVPACAB2A30P and excludes DVP80ES200R/T because their COM1 does not supply the required 5 V.

TP05G and TP08G: distinguish historical editions

TP05G-BS2 / TP05G-BT2: the historical combined TP05/TP08 instruction sheet documents monochrome 160×80-pixel models. BS2 denotes a white case; BT2 a black case. Its RS-232/RS-422, RS-485 and 24 VDC information belongs to that edition. These are documented historical models rather than unspecified special variants.

TP08G-BS2 / TP08G-BT2: the same historical sheet specifies 240×128 pixels. Later manufacturer literature for TP08G-BT2 identifies 24 keys, 1 MB flash, RTC, recipe and macro functions. Keep BS2 as a distinct historical code, and match memory and functions to the actual hardware/firmware edition.

The TP08G-BT2 catalogue gives a nominal 196×108 mm opening. Rounded catalogue figures and the body/mounting dimensions in the old TP05/TP08 drawing serve different purposes. Measure the existing opening and consult the installation drawing for the replacement unit.

TP04G-AS1, TP04G-AF2 and TP04G-BL-CN: these codes appear in the model appendix of the Rev.10 declaration dated 8 June 2018. That list does not establish AS2 or BL-CU port, supply or project specifications for them. Obtain the exact model’s instruction sheet and check its label before substitution.

Engineering software and project backup

The established screen editing tool is Delta TPEditor. Check the target model, communication driver, objects and key assignments in the project. The 2022 BL-C and BL-CU sheets also mention DIAScreen; confirm exact-model and project support in the installed release before migration. Do not apply a generic DOPSoft or Screen Editor rule to every TP panel.

Official links: TPEditor download record · TP USB Driver for models with USB · DIAStudio / DIAScreen downloads. A USB driver applies to a panel with a USB interface; it does not turn an RS-232 panel into a USB model.

Back up the TP screen project and the connected PLC control program separately. WPLSoft or ISPSoft depends on the PLC. Installing COMMGR does not automatically establish TP cable, target-model or serial settings. Check transfer direction before reading from or writing to a panel.

Cables, supply and panel mounting

Distinguish the programming cable from the PLC communication cable. A fitting DB9 or Mini-DIN does not establish pin compatibility, RS-232/RS-422/RS-485 levels or power delivery. Compare full DVPACAB, UC-MS and UC-PRG suffixes. Preserve the P suffix on the powered cable specified for BL-CU.

Verify the PLC driver/protocol, station address, baud rate, data bits, parity and stop bits together. Use the exact model’s DIP-switch or menu arrangement when selecting RS-422/RS-485. Do not connect different electrical interfaces merely because their terminals or connectors appear similar.

The opening sizes above are nominal selection figures. Machining tolerances, panel thickness, rear depth and connector clearance come from the model-specific installation drawing. A front-panel IP rating depends on the gasket and clamps; do not extend it to the exposed rear of the unit.

Editor’s note

Read the complete label before buying a panel that only looks similar. AS1–AS2, AL-C–AL2 and BL-C–BL-CU differences can change both wiring and supply requirements. Photograph the front, rear and existing connections before removal.

While the original panel still works, back up the project and record its editor release and PLC settings. If source files are missing, establish whether the uploaded content can actually be edited. An uploaded file is not automatically a complete engineering source.

For a blank display, check the model-specific supply under load at the unit, followed by contrast and backlight settings. Separate loose connections and grounding faults from a failed LCD or electronic board.

Test numeric, direction and Enter/ESC keys individually. A stuck key may repeatedly issue a command. Use a bench arrangement that cannot cause machine movement; a visible startup screen alone is an incomplete test.

If USB is not detected, check a data-capable cable, the correct driver and the assigned COM port. For PLC communication faults, revisit the protocol, station and interface mode. Factory reset or firmware writing should not be the first diagnostic action because the application can be lost.

After replacement, read one known value before testing a write key, an alarm and any recipe functions. If the clock repeatedly resets, inspect that model’s RTC and battery arrangement. Gaskets, clamps and the enclosure opening matter alongside the electrical tests.

Documents and related topics

Use the Delta HMI PDF archive and Delta TP panel files pages to select documents. Use a model instruction sheet for interfaces and mounting, the TPEditor manual for projects and object support, and a declaration of conformity for its listed product scope.

Delta DOP-A · Delta DOP-AE · Delta DOP-AS · Delta DOP-B

Delta DOP-H07 · Delta DOP-W · Delta DOP-107H

Delta HMI Mounting and Power Connections · Delta HMI Programming and HMC Cables · Delta HMI Shared Power Supplies · Delta HMI Communication Peripheral Units

Delta PLC software

External references

Delta TP product family · TP02G-AS1 · TP04G-AS2 · TP04G-AL/AL2 · TP04G-BL-C · TP04G-BL-CU · TP08G-BT2