Delta DCISoft

Delta DCISoft: Ethernet and serial module configuration

Delta DCISoft is Windows configuration software for discovering supported Delta network/communication modules, setting IP and communication parameters, and preparing supported data-exchange or gateway functions. DVPEN01-SL, RTU-EN01, IFD9506 and SCM modules have distinct roles. A configuration tab available on one module is not universal across Delta products.

The latest official central record checked on 14 November 2026 is DCISoft V1.31. It is dated 8 May 2026 and lists a 16.4 MB multilingual package. The official DCISoft V1.31 download opens Delta’s terms/verification page. The previous V1.30 record is dated 2 March 2026 and lists 16.2 MB.

Supported hardware · SCMSoft distinction · IP and data settings · PDF references

Distinct roles of DCISoft, COMMGR and PLC editors

DCISoft configures supported network/module parameters. COMMGR manages engineering-software communication channels on the PC. ISPSoft or WPLSoft edits logic for the appropriate CPU. Assigning a PLC IP address does not download a ladder program. Installing these tools together does not make their settings interchangeable.

Obtain the package from the DCISoft entry in Delta’s download centre. Back up PLC logic, module configurations, drive parameters and required device descriptions together. Device description files and EDS files are separate items; importing an EDS does not complete every IP or serial setting.

Which devices use DCISoft?

DVP Ethernet: DVPEN01-SL is an Ethernet expansion module, while suitable CPUs such as DVP-SE and DVP12SE11R have built-in Ethernet. DCISoft configures supported network and data-exchange functions. A DVP family name does not imply that every CPU has Ethernet. The Starter Kit manual covers DVP12SE, and the DVPEN01-SL manual covers the expansion module.

Remote I/O: RTU-EN01 provides remote I/O access over Modbus TCP. Configure its right-side digital/analogue modules, CR/RCR mapping and supported gateway tasks according to its own manual. It is not equivalent in role to a DVPEN01-SL PLC Ethernet module. The configured module sequence and mapping must match the installed hardware.

IFD gateways: Delta documents RS-232/RS-485-to-Ethernet conversion and DCISoft configuration through RS-232 or Ethernet for IFD9506. Check the model/firmware-specific scope of Modbus TCP, serial Modbus, EtherNet/IP and user-defined functions. IFD9507 is not assumed to share every protocol or operating mode merely because of its related name.

AH and AS: the download record includes AH Ethernet/serial modules and the AS SCM module. Check the exact module, function card and operating mode for AH10EN-5A, AH15EN-5A, AH10SCM-5A, AH15SCM-5A and AS00SCM-A. HWCONFIG, EIP Builder or DIADesigner may also be required for particular Ethernet/EtherNet/IP tasks; one tool chain cannot be assumed for every module.

Drive Ethernet cards: suitable CMC/CMM cards support network parameter setup. The C2000/C2000 Plus/CH2000 application demonstrates DCISoft IP configuration with CMC-EIP01/02. Match the card, drive family, firmware and control protocol separately. DCISoft alone is not a complete editor for every drive parameter or motion application.

SCMSoft and its relationship with DCISoft

SCMSoft is the serial-module configuration tool included in DCISoft. It prepares Modbus exchange functions for DVPSCM12-SL and DVPSCM52-SL. Delta documents BACnet MS/TP slave capability on DVPSCM52-SL in addition to its applicable other functions. Sharing a software package does not make these modules’ protocol coverage identical.

AS00SCM-A UD Link: PDF page 307 of the AS module manual specifies DCISoft V1.24 or later and its SCMSoft relationship. Serial expansion, CANopen remote-module and Ethernet remote-module roles can require different tools, including ISPSoft/HWCONFIG, CANopen Builder or EIP Builder. UD Link requires a send/receive structure matching the connected device’s frame format.

Keep version numbers separate: the AH manual mentions SCMSoft V1.24.06 together with DCISoft V1.20. These are different software components. Module firmware is a third version identifier. Record DCISoft, SCMSoft and device firmware separately in the project backup.

IP setup and module connection

1. Record the complete model, MAC address, current IP, subnet mask, gateway and connected devices. Before changing an address on a working network, identify the HMI, SCADA or other PLCs using it. Check the factory address and restart requirement in the model’s manual.

2. Under Tools → Communication Setting, select the Ethernet or serial connection supported by the device. Verify the network interface and any COM parameters. Use the model’s specified programming/configuration cable; identical connector shapes do not establish identical electrical interfaces.

3. Run Auto Search / Search and compare the discovered MAC/model/IP with the physical label. In the correct device’s setup window, configure Static IP or supported DHCP, subnet and gateway values. Avoid a duplicate IP on the same network.

4. Use the model-specific Apply, OK or transfer/save operation to write settings to the device. Losing the old-IP connection can be expected after an address change; rediscover the new address and verify actual communication. If a restart is required, perform it when the machine state permits. Saving a PC configuration file is separate from transferring it to the device.

Data Exchange, I/O mapping and serial gateways

Data Exchange: define direction, master/slave data areas, start addresses and quantity together. A Delta D-register address is not automatically equivalent to another vendor’s raw Modbus address, 4xxxx notation or hexadecimal address. Begin with a small number of known registers. For 32-bit values, also check the order of the two 16-bit words.

RTU mapping: the analogue I/O or control-register list must match the physical module order and supported CR/RCR relationships. Adding or removing a module can affect data addresses. Consult the RTU-EN01 manual before copying another installation’s mapping simply because the RTU has the same name.

IFD serial side: in addition to Ethernet IP/port settings, match RS-232/RS-485, bit rate, parity, stop bits, ASCII/RTU, station address and operating mode. Gateway and virtual COM examples in the IFD9506 manual serve distinct purposes. Ethernet can be reachable while an incorrect serial address or cable prevents a downstream response.

Device discovery and configuration problems

First check supply power, LINK/ACT indicators and the selected network adapter. Wi-Fi, VPN or virtual adapters may differ from the interface connected to the device. Discovery can be limited to the local broadcast domain, so a device behind a router may not appear in a local scan. Evaluate a known-IP connection or a supported RS-232 alternative according to the device manual.

Discovery and Modbus TCP/EtherNet/IP data exchange are different stages. A ping response does not prove that the correct PLC register was read. Check IP filters, configuration passwords, operating mode and applicable application/local-network permissions separately. Use the model’s documented port requirements instead of one universal port number.

Do not use factory reset as the first response to a password or save problem. It can remove IP, serial, gateway, mapping and access settings. Export or record the existing configuration first. Firmware updating is a separate maintenance task requiring the exact model and manufacturer procedure.

Software versions and Windows support

Manufacturer bulletins document V1.0.1, V1.0.2, V1.04, V1.05 and V1.06. Later applications/manuals mention V1.09, V1.20, V1.21 and V1.24. The Turkey support entry names V1.27, while the current central records list V1.30 and V1.31. Bulletin dates are not automatically exact software release dates, and an example’s version is not a current installation recommendation. A complete official archive of every intermediate build was not found.

The V1.31 OS field reads Windows 7/8/10 (64-bit)/11 (64-bit). An old CD or V1.24 package cannot be assumed to carry the same support. A multilingual label does not independently establish a Turkish interface. Check the Windows compatibility of the engineering editor and USB/converter drivers separately.

PDF manuals and archive documents

The following English manufacturer documents describe model-specific settings and applications. They are not presented as a general DCISoft V1.31 interface manual. Preserve each module manual’s edition, firmware and functional limits. The older DVPEN01-SL application manual is identified separately at the end.

DVP Starter Kit: DCISoft installation and DVP12SE setup — Sections 1.5, 2.5 and application examples: interface, installation, DVP12SE discovery and IP setup. The central source filename says 20240812, while the internal revision table says 2024-07-09; this distinction is preserved. Language: EN; 2024-07-09 (second revision inside PDF); 170 pages; 8.00 MB.

DVPEN01-SL Ethernet module operation manual, Rev.04 — DCISoft communication selection, discovery, basic/IP settings, data exchange and configuration import/export. Distributor copy lists iLovePDF as PDF producer; its cover and 60 pages were checked. Byte equality with the inaccessible manufacturer file is not claimed. Language: EN; Rev.04; PDF created 2016-01-21; 60 pages; 1.97 MB.

RTU-EN01 Modbus TCP remote I/O manual, Rev.01 — Remote digital/analogue I/O, CR/RCR mapping, DCISoft settings and gateway functions. Historical edition; not assumed to cover every current firmware function. Language: EN; Rev.01; PDF created 2009-06-04; 52 pages; 3.39 MB.

IFD9506 Ethernet-to-serial gateway operation manual — DCISoft, Ethernet/serial settings, Modbus and user-defined communication, EtherNet/IP and virtual COM applications. Model/firmware-specific; not a replacement for the IFD9507 manual. Language: EN; Rev.03; source/metadata dated 2021-10-27; 64 pages; 4.47 MB.

AS module manual: AS00SCM-A and SCMSoft — Chapter 9, starting at PDF 305, covers AS00SCM-A. PDF 307 specifies DCISoft V1.24 or later for UD Link and explains SCMSoft. CANopen/serial expansion and Ethernet remote-module tasks are distinct. Language: EN; 2022-05-16 (11th revision); 724 pages; 25.62 MB.

AH500 module manual: AH10/15SCM and DCISoft — Chapter 8: AH10/15SCM and SCMSoft, PDF 266/333. PDF 796 relates SCMSoft V1.24.06 to DCISoft V1.20; these version numbers belong to separate software components. Preserves the name and bytes from the CANopen Builder package. Language: EN; 2020-12-25; 810 pages; 28.25 MB.

C2000/C2000 Plus/CH2000: Ethernet card and DCISoft application — Section 2.3.1 / PDF 9–10: CMC-EIP01/02 IP setup with DCISoft. The positioning example also requires the appropriate hardware/firmware and PLC configuration; setting an IP alone does not implement motion. Language: EN; First released June 2021; updated October 2023; 26 pages; 1.80 MB.

DVPEN01-SL older application manual — historical archive — Older 54-page Application Manual, distinct from the 60-page Rev.04. Preserved separately for historical screens and installations; not the current default selection reference. Language: EN; No printed date; PDF created 2009-01-14; 54 pages; 2.67 MB.

Editor’s note

Identify the intended module first. If several Delta devices share the network, compare MAC addresses and physical labels as well as IPs. Changing the wrong module can disconnect another working machine.

Record the existing subnet, gateway, HMI links and mapping before writing an IP. Do not immediately reset a device after losing the old-IP connection; it may have moved to the new address. Rediscover it and verify with a read operation.

For SCM modules, a matching bit rate alone is insufficient. Check RS-485 polarity, station address, parity and RTU/ASCII format. TX/RX indicators help identify polling activity but do not prove that the correct register value arrived.

Start Data Exchange with one or two registers. Address offsets, hexadecimal/decimal differences and 32-bit word order are common sources of wasted time. Expand the table after a small example works rather than changing every entry at once.

Check file saving separately from transferring settings to the module. Read settings back afterward and record the model and firmware alongside the file. Keep the SCMSoft version separate from the DCISoft version so the original installation can be reconstructed later.

Check supply power, cables, ports and recorded settings before considering reset or firmware changes. Account for machine state and connected devices when modifying a running installation. Make the required backups and change one item at a time.

Related topics

Delta PLC software · Delta ISPSoft · Delta WPLSoft · Delta COMMGR

Delta CANopen Builder · Delta DeviceNet Builder · Delta device description files · Delta EDS device description files

Delta DVP PLC series · Delta AS PLC series · Delta AH PLC series · Delta DVP-SE

Delta DVP12SE11R · Delta DVP12SE11T · Delta DVPEN01-SL · Delta DVPSCM12-SL

Delta DVPSCM52-SL · Delta RTU-EN01 · Delta AS00SCM-A · Delta AH10EN-5A

Delta AH15EN-5A · Delta AH10SCM-5A · Delta AH15SCM-5A · Delta IFD9506

Delta IFD9507 · Delta Plc Cables

External references

Official Delta DCISoft download centre · Delta Turkey DCISoft support entry · IFD9506 serial-to-Ethernet functions

RTU-EN01 CR/RCR mapping · DVPSCM12/52-SL and SCMSoft · DVP12SE data exchange example