Delta HMI Shared Power Supplies
Delta HMI shared power supplies compares DVPPS01, DVPPS02 and DVPPS05 for supplying a panel and associated 24 V DC loads. These devices convert AC input power to 24 V DC. Selection must consider the panel’s voltage range, total current, startup demand and control cabinet conditions.
The products belong to the Delta DVP power supply family. Delta’s TP70P-211LC1T / TP04P-20EXL1T operation manual also names all three as DC supply options for those devices. This does not establish unrestricted compatibility with every Delta HMI. Retain the full device reference within the TP70P and TP04P families. Reference: 6 October 2022 manual, PDF p.48 / printed p.4-4.
DVPPS01, DVPPS02 and DVPPS05 differences
DVPPS01: 24 V DC, maximum 1 A. Voltage multiplied by current gives a nominal output capacity of 24 W. Assess it for smaller loads; the panel and all other consumers on the same supply share that 1 A total.
DVPPS02: 24 V DC, maximum 2 A, giving a calculated nominal capacity of 48 W. It provides more current than DVPPS01. Check the enclosure and mounting arrangement separately; an identical voltage rating does not establish an identical mechanical fit.
DVPPS05: 24 V DC, maximum 5 A, giving a calculated nominal capacity of 120 W. The source table additionally specifies overvoltage and overtemperature protection for this model. Do not assume those protections for DVPPS01/02. A 5 A capacity does not mean the panel must draw 5 A.
All three have a nominal input of 100–240 V AC, 50/60 Hz and a specified output of 24 V DC ±3%. Overcurrent/short-circuit protection is auto-recovery type, which does not permit operation with a persistent short circuit. Ratings were compared against the DVPPS instruction sheet and Delta’s 2023 document record; document dates do not establish a product generation’s start or end.
Calculating the panel and shared loads
Add the consumption of the HMI, PLC, I/O modules, sensors and auxiliary devices supplied by the same unit. Include current demand and switching effects from relay coils or valves sharing that circuit. Screen size alone is insufficient: consult the supply specifications for the exact DOP-100, DOP-B or DOP-W model.
Illustrative calculation: assuming 0.6 A for an HMI, 0.4 A for a PLC and 0.3 A for sensors gives a continuous load of 1.3 A. These are hypothetical figures. DVPPS01’s 1 A capacity is insufficient for this example. Assessing DVPPS02 also requires checking startup demand, temperature, other loads and design margin; the continuous total alone does not complete selection.
For digital I/O expansion and remote I/O modules, the electronics supply and field output supply may be separate. Check Ethernet expansion, printer modules and communication peripheral units against their individual wiring and power arrangements. Do not assume every accessory takes power directly from the shared 24 V circuit.
Installation, wiring and replacement
Distinguish the L/N AC input from the +24 V/0 V DC output, and connect protective earth as instructed for the device. Never apply mains voltage to the +24 V output. Review HMI mounting and power connections for terminal positions, polarity, conductor sizing, circuit protection and ventilation. Also assess voltage drop between the supply and panel under load.
The instruction sheet shows mounting on a 35 mm DIN rail. Preserve the required cooling clearances and check cabinet space when changing to a higher-current unit. Do not join supply outputs to increase available current without documented manufacturer support for parallel operation. Distinguish the purpose of the common 0 V connection from protective earth.
For HMC07 and HMC08 systems, also verify the power-carrying conductors and full pinout of the HMC connection assembly. A 24 V source does not make the wrong cable or pin connection suitable. These supplies do not receive HMI projects; panel software and communications settings are separate.
Editor’s note
Investigate the supply when a panel repeatedly restarts. A lit screen alone does not prove the supply is healthy. If the fault coincides with machine movement or valve operation, record the other loads sharing the circuit.
Do not stop at measuring the supply terminals. A competent technician should also check the panel input under load using a safe measurement arrangement. A loose terminal or a long, undersized conductor may cause a drop at the panel even when the source reading is normal.
Before changing connections to isolate load branches, put the machine in a safe state and isolate power. Distinguish a supply fault from a field short circuit. If the output returns after a branch is removed, investigate the affected branch.
A larger 5 A supply is not a universal repair. It does not correct a short circuit, reversed polarity or wrong mains connection. When supply capacity increases, branch wiring and protection must still match the design.
For used units, inspect for burning smells, discolouration, damaged terminals, loose rail clips and signs of overheating. A no-load 24 V reading is not a load test. Monitor voltage and stability with a controlled load; mains-side work requires competent personnel.
Record the working unit’s model, total load, output voltage and supplied devices in the machine file. A multimeter’s average reading may miss fast dips or ripple. Persistent faults require suitable equipment to examine supply behaviour over time.
Related HMI families and documents
For legacy panels, check the supply information in DOP-A, DOP-AE and DOP-AS documents. Do not assume TP text panels and graphical HMIs have the same consumption. Identify the role of each item in HMI starter kits and HMI modules and accessories.
Use Delta HMI PDF files and Delta PLC and HMI manuals to select documents. Return to Delta HMI families or browse available used Delta products.
Manufacturer documents and external references
DVPPS01/02/05 instruction sheet — 30 April 2014, 5011679805-S005 is a distributor-hosted copy of the manufacturer document, with four languages including English and Turkish. The official Delta DVPPS01/02/05 document address — DVP-0965530-01 has an internal issue date of 15 February 2023; this is distinguished from 20230213 in the filename.
The supply example in the TP70P-211LC1T / TP04P-20EXL1T operation manual — 6 October 2022 directly supports the named devices. Complete the circuit protection and load calculation according to the machine’s electrical design.