Delta DOP-H07

Delta DOP-H07 is a 7-inch, 800 × 480-pixel handheld HMI family for operating a machine while moving around it. The housing combines a touchscreen, 15 function keys, an emergency-stop button and a rear three-position enabling switch. The full model determines the handwheel, communication interface and cable termination.

This page separates eight standard models and two ZM variants. DOP-H07 is an operator interface; the PLC/motion-control functions of HMC07 or HMC08 must not be assumed. The connected PLC, robot controller or drive and the machine project determine how motion commands are processed.

Model identification: S/E, 42/46 and 5/A

S models provide one RS-422/RS-485 serial interface and no Ethernet. E models provide one 10/100 Mbps Ethernet interface and no serial COM port. An S model and an E model therefore require different communication arrangements. The S interface must not be wired as RS-232.

42 models have no handwheel; 46 models have an MPG handwheel. The standard model suffix 5 means a 5 m cable, while A means 10 m. Both groups support SD/SDHC cards; absence of an MPG does not mean absence of card support.

Standard DOP-H07 models

DOP-H07S425: RS-422/RS-485, no handwheel, 5 m cable. DOP-H07S42A: the same interface and control class with a 10 m cable. Neither is an Ethernet model.

DOP-H07S465: RS-422/RS-485, MPG handwheel, 5 m cable. DOP-H07S46A: the same serial interface and MPG equipment with a 10 m cable. The handwheel A/B pulse wiring is separate from serial communication.

DOP-H07E425: Ethernet, no handwheel, 5 m cable. DOP-H07E42A: the same Ethernet and control class with a 10 m cable. Neither provides an RS-422/RS-485 serial COM port.

DOP-H07E465: Ethernet, MPG handwheel, 5 m cable. DOP-H07E46A: the same Ethernet and MPG equipment with a 10 m cable. Network communication and the physical handwheel pulse outputs are separate signals.

DOP-H07E425ZM and DOP-H07E465ZM

DOP-H07E425ZM is the Ethernet variant without an MPG; DOP-H07E465ZM includes the MPG. Delta’s ASDA-MS catalogue lists both with 5 m cables. The EH03 instruction sheet provides a dedicated 25-pin D-SUB wiring table. The ZM suffix must be retained when identifying or replacing a unit.

In the ZM table, pin 25 is +24 V and pin 13 is 0 V; pins 22–23 are the three-position switch NO contact. These numbers apply specifically to the DOP-H07E4xxZM D-SUB table. They must not be mixed with the standard E model’s RJ45/separate-wire arrangement or an older quick-connector table. Read the complete connector view and verify the actual hardware revision before wiring.

Emergency stop, enabling switch and document differences

DOP-H07 documents describe the emergency stop, three-position switch and MPG outputs as physical cable connections. The three-position switch is specified with one NO contact. Do not substitute an on-screen button or a register-only function documented for a different HMC model when interpreting these connections.

Emergency-stop information differs between editions and within the EH03 sheet. The 2016 combined catalogue specifies two NC contacts. The 2015 EH00 sheet specifies one NO plus one NC. The 2016 EH03 standard S/E cable tables identify NC(A)/NC(B), whereas its common specification table and ZM wiring table show one NO plus one NC. A single universal contact arrangement cannot be inferred from these conflicting entries.

Match the full model, hardware revision and existing machine schematic. A competent person should verify actual contact behaviour on the isolated circuit and obtain revision-specific clarification from Delta where required. Working HMI communication does not verify the machine safety circuit. Bridging contacts or simulating a stop in HMI software is not a repair procedure.

MPG pulse output and cable checks

For 46 models, the documents specify 50 pulses/revolution, A/B-phase square-wave outputs and 200 Hz maximum frequency response. The dedicated EH03 output section gives 20 mA maximum at 5 V ±5% and 30 mA maximum at 24 V ±5%, with an external handwheel supply. Its general specification also uses “<24 V”; use the dedicated output section and the receiver’s electrical requirements to resolve the connection rather than relying on that abbreviated entry.

For standard 46 cable wiring, yellow is output A, white/yellow is output B, and white/red is the external handwheel supply. The panel’s 24 V supply alone does not determine the pulse receiver voltage. Check communication, supply, enabling-contact and MPG conductors separately when selecting programming and HMC cables or communication peripheral units.

Delta instructs users not to extend the integrated cable by adding other conductors. Check the S/E/ZM termination, shielding, strain relief, handle cable exit and every conductor function when replacing a cable. Connector similarity does not establish compatibility.

Power, housing, USB and project software

The 2016 DOP-H07 sheet specifies 24 V DC ±15%, 5.6 W panel consumption, 0–40 °C operation and IP55. Consumption excludes connected peripherals. Consider voltage drop along the cable and other loads when selecting shared power supplies; Delta recommends an isolated supply.

257.4 × 170.3 × 71.8 mm are external dimensions including the emergency-stop switch and hook. Weight is 750 g excluding the cable. These are not panel-cutout dimensions: the product is handheld. Review the hook, housing, cable exit and parking position under mounting and power connections. Do not assume an impact-damaged or poorly sealed used unit retains its original IP rating.

The unit provides one USB Client/Slave 2.0 connection and SD/SDHC support. Do not treat the USB connection as a Host socket. The sheet lists one CR2450 3 V lithium backup battery; preserve the project and required retained data before battery service.

Delta identifies DOPSoft as the DOP-H07 project editor. Record a release supporting the actual panel and project, its OS/firmware versions and the project target. Screen Editor, DOPSoft and newer HMI software cannot be assumed interchangeable. Preserve the original source project, communication settings, key functions, macros and recipes before conversion. Obtain installers through the official Delta download centre and manufacturer support where necessary.

Discontinuation and migration to DOP-107H

Delta’s global product list identifies DOP-H07 as discontinued in July 2019 and directs users to DOP-107H. This is a replacement-family reference, not a guarantee of direct mechanical, cable, safety-contact or project interchangeability. Compare the existing S/E/ZM connections and MPG requirements with the full replacement model.

Editor’s note

Start with label photographs and both cable ends. Distinguish E425 from E425ZM and S465 from E465. If a cable has been replaced previously, trace its actual conductors as well as reading the unit label.

If moving the handheld unit causes restarts, measure 24 V at the panel under load and inspect the cable exit, damaged insulation, loose connections and signs of broken conductors. Prevent machine movement during checks. Downloading a project should not be the first response to this symptom.

Check the emergency stop and rear enabling switch separately. Conflicting NO/NC document entries make memorised wire colours insufficient. Isolate power, verify the actual contacts and compare them with the approved machine schematic. Do not return the machine to service with a bridged contact.

If the MPG counts in only one direction or loses increments, check both A/B phases and the receiver voltage. Verify pulse generation with suitable measurement equipment. A working display and Ethernet connection do not establish MPG output condition.

On used units, test the touchscreen at the corners and edges and test all 15 keys. Record USB communication, card access, battery/clock condition, hook and cable mechanics separately. Appearance alone does not establish the condition of oil- or chemical-exposed key membranes.

Preserve the working original project. Convert a copy and test key assignments, recipes, alarms and communication-loss behaviour under controlled conditions. Recreating the same screen on DOP-107H does not complete validation of the machine functions.

Related HMI families and documents

Fixed-mount panel generations are covered separately under DOP-A, DOP-AE, DOP-AS, DOP-B, DOP-W and DOP-100. TP text panels, TP04P and TP70P are different panel/control groups.

Select remote I/O, digital I/O expansion, Ethernet expansion modules and starter kits against their own compatibility documents; these categories are not a list of accessories automatically supported by DOP-H07. See Delta HMI modules and accessories for the broader scope.

Use Delta HMI PDF files and Delta PLC and HMI manuals for document selection. Return to Delta HMI families or browse available used Delta products.

Manufacturer documents and external references

DOP-H07 EH03 instruction and wiring sheet — 11 April 2016, 5014009603-EH03 includes English and Turkish among four languages; Turkish is on PDF pp.3–4. The EH00 English sheet — 25 February 2015, 5014009600-EH00 preserves the earlier wiring description. Both links point to distributor-hosted manufacturer documents.

The 2016 DOP B/H/W combined catalogue provides the standard H07 table on PDF p.20; Delta’s ASDA-MS catalogue lists the ZM models. See the Delta regional DOP-H07 product record for general features and the Delta global HMI list for discontinuation. Catalogue issue dates alone do not establish a product generation’s start or end date.