Delta DVP80ES300T

Delta DVP80ES300T ES3 PLC with 40 Inputs and 40 NPN Outputs

The Delta DVP80ES300T is a compact DVP-ES3 PLC with a 100–240 V AC CPU supply. It has 40 digital inputs, 40 NPN transistor outputs and 64K steps of program memory. It includes Ethernet, Mini USB-B, two RS-485 ports, a CAN interface and a microSD slot. It suits packaging, assembly and conveyor lines with many field signals in one control panel.

On a sorting line, photoelectric sensors detect passing products while an encoder tracks belt travel. The PLC can use these signals to command a sorting valve or a pulse-input servo drive. Assign the high-speed counter inputs and pulse outputs early in the design so the field terminals and program addresses are easy to trace during commissioning.

Power supply, field inputs and transistor outputs

CPU supply • 100–240 V AC, 50/60 Hz. Show the 24 V DC field input circuit and the DC supply for the output groups separately in the panel diagram. Size the 24 V DC field power supply for the sensors, output loads and expansion modules that share it.

Digital inputs • The forty 24 V DC inputs use octal addresses X0–X47. Connect the relevant S/S common to 0 V for PNP sensors and to +24 V for NPN sensors. When connecting an inductive sensor or photoelectric sensor, check the terminal diagram for the common group associated with the chosen X input.

NPN transistor outputs • The forty outputs are addressed Y0–Y47. When active, an NPN sinking output conducts load current toward 0 V. Delta specifies 5–30 V DC, 0.5 A per output and 4 A per common group for resistive loads. The UP/ZP terminals require a 24 V DC auxiliary supply. Wire each load according to its output group diagram.

High-speed pulses and expansion • The Y0–Y7 high-speed outputs support up to 200 kHz. With the appropriate pulse and direction assignments, the controller can position up to four pulse-controlled axes. Use compatible Delta DVP expansion modules when more digital points are required. Delta specifies up to 256 digital I/O points, including the built-in points, in a supported expansion configuration.

ISPSoft, DIADesigner and programming cables

Programming software • This standard ES3 CPU supports ISPSoft and DIADesigner. Verify the DVP-ES3 family and CPU model in the project. When using ISPSoft, select the USB or Ethernet channel in COMMGR to match the connection.

USB connection • Connect the PC’s USB-A port to the PLC using a USB-A to Mini USB-B data cable. See Delta PLC cables for connection options. On first use, check that the USB driver is installed and that the software detects the PLC.

Ethernet connection • Connect the PC and PLC with an RJ45 Cat 5e network cable. Use the controller’s current IP address for project transfer and confirm that the PC is on the same subnet. The built-in Ethernet interface can also exchange data with an HMI or SCADA system using Modbus TCP when configured for that purpose.

Field communication • Two RS-485 ports connect to serial Modbus HMIs, instruments or drives. When setting up a CANopen network, check device compatibility, node addresses and baud rate.

Editor’s Note

When buying a used CPU, check the full nameplate. The T in DVP80ES300T identifies the NPN output type. Verify that the removable terminal blocks are present and that the Ethernet and Mini USB sockets are intact.

If a group of Y LEDs is on and its loads stay off, start with the UP/ZP auxiliary supply for that group. Then trace the load return and verify the common group number against the wiring diagram.

If an input group fails to detect signals, check its S/S terminal. In panels with different sensor output types, trace the supply and common wiring at the terminal level.

If the servo does not respond to a pulse command, check the Y address, pulse and direction assignments, and the signal type at the drive. Test at low speed first to verify direction and limit inputs.

Before replacing the CPU, save the original project, hardware configuration, expansion module order and network parameters. If communication drops intermittently, inspect cable routing and panel grounding.

Related PLC models

DVP80ES300R • 40 inputs and 40 relay outputs. DVP64ES300T • 32 inputs and 32 NPN outputs. DVP48ES300T • 24 inputs and 24 NPN outputs. DVP32ES300T • 16 inputs and 16 NPN outputs. For a new panel, you can also review the I/O and communication options on Derell B Series PLCs.

Delta DVP files and used models

Delta DVP PLC PDF files · Delta DVP PLC series · Used Delta PLC models · Used PLCs and CPUs · Delta main page