Delta DVP16SN11TS
Delta DVP16SN11TS — 16 PNP Transistor Output Expansion Module
Delta DVP16SN11TS is a right-side expansion module that adds 16 PNP sourcing digital outputs to supported DVP Slim PLC systems. All 16 points are outputs. An active Y point supplies positive voltage to its load. The DVP16SN11T has the same number of outputs and uses NPN sinking transistors with a different wiring arrangement.
Power, terminals and current limits
The CPU powers the module electronics. The output stage needs a separate 24 V DC supply (20.4–28.8 V). Delta’s diagram connects +24 V to UP0 and UP1 and 0 V to ZP. Connect the load between its Y terminal and 0 V. The module draws up to 25 mA from the auxiliary supply. Calculate load current separately.
UP0 feeds Y0–Y7 and UP1 feeds Y10–Y17. Delta gives an output voltage range of 5–30 V DC. For resistive loads, observe both 0.3 A per point and 2 A per common. Eight 0.25 A loads on one group add up to 2 A and reach the common limit. Account for simultaneous current when selecting the supply and wiring.
PNP wiring and load selection
The difference between NPN and PNP determines where the receiving input common connects. The DVP16SN11TS switches positive DC voltage. The receiver must accept a PNP signal and provide a 0 V return. For example, connect S/S to 0 V on a compatible DVP16SM11N wired for PNP signals. The Y output connects to the X input, with a shared 0 V reference.
A transistor output switches DC signals and suitable loads. When controlling a relay coil or contactor, check inrush as well as steady-state current. Use a suitable interface relay or driver for the load. For a DC coil, use the diode or suppression device recommended by the load manufacturer and suitable fuse protection on the supply line.
Host compatibility, Y addresses and programming
Check right-side expansion support and I/O capacity for the exact DVP-SS2, DVP-SA2, DVP-SX2, DVP-SV2 or DVP-SE CPU. Y0 through Y17 on the module are local terminal labels. The Y addresses in the program depend on the CPU and expansion order. For example, an allocation starting at Y20 uses Y20–Y27 and Y30–Y37 for the 16 outputs.
Control the outputs from the host CPU’s ladder program. Use WPLSoft or ISPSoft according to CPU support. On listed CPUs with a COM1 mini-DIN RS-232 port, use UC-PRG020-12A for USB or UC-MS020-01A for serial connection. Configure the ISPSoft connection in COMMGR.
Editor’s Note
Check the full model label and the TS suffix before ordering. The T and TS housings look similar, but their output polarity and commons differ.
If the CPU shows the output is ON and the load stays off, measure UP0 and UP1 separately against ZP. One group may be missing its auxiliary supply.
On a used module, inspect the removable terminals and side expansion connector. Use a suitable small 24 V DC test load and check each output in both groups.
If outputs work individually but fail together, measure the group current and supply voltage drop under load. Recheck the panel design if one group approaches 2 A.
For intermittent faults when a drive runs, check control cable routing, grounding and sources of electromagnetic interference.
PDF documents
See Delta DVP PLC files for the terminal diagram and CPU cable options. Section 7.4.11 of the 2026 module manual covers DVP16SN11TS wiring, and 7.5.2 covers transistor output circuits.
Related modules and topics
DVP08SN11TS provides eight PNP outputs. DVP16SP11TS provides eight inputs and eight PNP outputs. DVP16SN11T provides 16 NPN outputs and DVP32SN11TN provides 32 NPN outputs. DVP16SM11N adds 16 digital inputs.
DVP16SN11TS main page · DVP Slim digital modules · DVP expansion modules · Delta DVP PLC series · Second-hand Delta products