Delta IFD9503 is a CANopen slave communication module connecting suitable RS-232 / RS-485 Modbus equipment to a CANopen network. Applications include PLCs, AC drives, servos, temperature controllers and operator panels. Evaluate the CANopen master, selected device profile and data mapping together.
CANopen connection and power
The CAN connection uses a removable connector with 5.08 mm pitch. Assignments are 1: V−, 2: CAN_L, 3: SHIELD, 4: CAN_H, 5: V+. Nominal power is 24 VDC, with specified CAN-channel isolation of 500 VDC. Verify permitted supply limits against the unit label and applicable hardware documentation.
CANopen speed options are 10, 20, 50, 125, 250, 500, 800 kbit/s and 1 Mbit/s. These are CAN bus rates, distinct from the serial Modbus device's communication speed. Review power and cabinet arrangements alongside Delta DVP power supplies.
PORT1 and PORT2 pin assignments
PORT1 supports RS-485 only: pin 2: GND, pin 3: DATA−, pin 4: DATA+. PORT2 uses a male DB9. In RS-232 mode it uses pin 2: RXD, pin 3: TXD, pin 5: GND; in RS-485 mode it uses pin 3: DATA−, pin 8: DATA+. Read assignments using the connector orientation shown in the manual.
Select Delta DVP communication cables for the actual port and electrical interface. Similar connectors do not establish identical wiring. Identify the complete connected model through Delta DVP PLC series, Delta HMI files and Delta servo communication units.
Node address and DIP selection
Two rotary switches select the CANopen node address in the hexadecimal 01–7F range. For example, 1A equals decimal 26. The SW3 DIP group selects device type, serial mode and CAN speed. DIP 4 and 5 both OFF select RS-485; both ON select RS-232. Mixed positions are not valid communication modes.
Address, mode and speed changes take effect after power is cycled. The selected device profile also affects serial communication requirements; do not apply one generic baud/parity setting to every profile. Record the machine's existing configuration before changing switches.
CANopen Builder and data mapping
For projects using a Delta CANopen master, review Delta CANopen Builder for network configuration. Related tools are under Delta PLC software, with description documents under Delta device description files. The device definition, object dictionary and PDO mapping in the master project must match the installed hardware.
IFD9503 supports PDO, SDO, NMT, SYNC and Emergency services. A visible CANopen node does not itself confirm correct data acquisition from the serial equipment. Review Delta COA02 and Delta DVP specialty communication modules when comparing different PLC-side solutions.
Differences from other IFD models
Delta IFD9502 serves DeviceNet, Delta IFD9506 serves Modbus TCP, and Delta IFD9507 serves Modbus TCP/EtherNet/IP connections. Delta IFD6503 is a USB-to-CAN interface. Their functions and network protocols should not be treated as identical to IFD9503's CANopen slave role.
Product status: Delta's global product page marks IFD9503 as discontinued in June 2024. When replacing a used unit, check the complete code, physical condition, switch positions and existing master project together.
Manual and connection documents
Start document selection at Delta PLC accessories files. In the 57-page IFD9503 Application Manual, printed pages 5–7 cover connections and switches, while page 35 explains LED states. These correspond to PDF pages 7–9 and 37. The two-page instruction sheet is also useful during installation.
Editor's Note
Begin by photographing the rotary switches and DIP group. Keep cable connections and the master project's node record together. Do not read a hexadecimal address as a decimal station number.
Check the CANopen node address and serial-device address separately. They belong to different address spaces. Find the serial format required by the selected device type in the manual, rather than changing speeds at random.
Evaluate RUN and SCAN indicators together. The CAN side may operate while the serial-device connection has a fault. Establish which side lacks communication before judging the module from one LED.
Start with one known read value. Compare PDO contents or the SDO response with the connected device's actual value. Do not send arbitrary commands to machine outputs before verifying the mapping.
Disconnect power before changing connections or switches. Check machine command states before restarting. For used equipment, inspect connectors, the rail clip, rotary switches and power contacts as well.