Delta IFD8500-A

Delta IFD8500-A

Delta IFD8500-A is an isolated converter providing electrical signal conversion between RS-232 and RS-485 / RS-422. It connects a computer, PLC or controller's RS-232 port to a differential serial line. It requires 9–48 VDC power, consumes 0.4 W and supports automatic communication speeds up to 115,200 bit/s.

Conversion function and automatic speed

IFD8500-A has a switchless, isolated design. Automatic speed handling does not reconcile different baud or parity settings at the endpoints. Application protocol, data format and serial parameters must be compatible. No PLC project is downloaded to the converter; configure the endpoint devices using their own engineering tools.

Identify the PLC under Delta DVP PLC series, the panel under Delta HMI files and servo connection options under Delta servo communication units. Review endpoint programming tools under Delta PLC software.

RS-232 DB9 connection

The RS-232 side uses a female DB9. The instruction sheet identifies pin 2: TX, pin 3: RX, pin 5: Signal GND; read these names from the converter's documented perspective. Check connector orientation and the other device's assignments when selecting the cable.

A cable under Delta DVP communication cables is not suitable merely because it has a DB9 connector. Distinguish straight-through and crossed wiring, and verify the connection beyond physical connector fit.

10-pin terminal functions

RS-485 uses pin 1 DATA+ and pin 2 DATA−. Pin 3 is unused. RS-422 uses pin 4 TX+, pin 5 TX−, pin 6 RX+, pin 7 RX−. Pin 8 is SHLD, pin 9 is +Vs and pin 10 is power GND.

For RS-422, connect each transmitting pair to the other device's receiving pair while maintaining polarity. On RS-485, match DATA+ and DATA− to the verified signal definitions of the connected equipment. Do not assume that A/B labels are equivalent across manufacturers.

The sheet's RS-485 diagram shows 120 Ω termination at both physical line ends. Account for resistors already installed in connected devices. Evaluate power and reference wiring alongside Delta DVP power supplies.

Mounting and replacing the earlier model

Drawings cover DIN-rail and panel mounting. The specified operating temperature is −20 to +65 °C, and weight is 122 g. Arrange cables so they do not strain the connectors or terminal block.

The manufacturer identifies IFD8500-A as the replacement for the earlier IFD8500. Preserve the A suffix when selecting a unit and check the actual specifications. Verify port standard, power and wiring before looking for switches or software settings.

Differences from other Delta interfaces

Delta IFD8510-A is a repeater, Delta IFD8520 is an addressable serial converter, and Delta IFD6500 is a USB-to-RS-485 interface. Delta ADP485-01 is an RS-485 connection adapter. Evaluate their functions and connection arrangements separately.

Delta IFD9506 and Delta IFD9507 provide Ethernet-side gateway functions, while Delta IFD9503 serves CANopen slave connections. CPU-associated options are under Delta DVP specialty communication modules. Select IFD8500-A for the machine's actual serial-interface requirement.

PDF and connection documents

Start document selection at Delta PLC accessories files. The 2022-05-16 IFD8500-A sheet, document 5014061302, includes Turkish and English. PDF page two provides pin assignments and wiring.

Editor's Note

First establish which conversion is actually required. Converting an RS-232 port to RS-485 and repeating an existing RS-485 line are different functions. Changing cables cannot correct selection of the wrong device.

Measure power at the converter's terminals. Correct voltage at the supply may not reach the unit through a loose terminal or broken cable. Measure under operating conditions and identify pins 9 and 10 from the drawing.

Do not transfer TX/RX assumptions from another device. Check DB9 assignments from both ends. Disconnect power and separate both cable ends before testing continuity.

Start with one device and a short known-good cable. Verify a known read operation, then add the existing line in stages. This helps distinguish converter, field-cable and endpoint faults.

For intermittent faults, inspect routing and termination. Check proximity to motor and drive power cables, shield connections and loose terminals. An illuminated power LED alone does not test data exchange.