Delta DVP-FEN01

Delta DVP-FEN01 Ethernet Communication Card

The Delta DVP-FEN01 is a function card that adds Ethernet to DVP-EH3 PLC CPUs with 32 or more I/O points. It has one RJ45 Ethernet port and one Mini-DIN RS-232 port (COM3). It supports Modbus TCP communication with HMI or SCADA systems and PLC program access through WPLSoft.

See Delta DVP PLC files for installation, network configuration and connection examples.

Which DVP-EH3 CPUs support the card?

Examples include the 32-point DVP32EH00R3 and DVP32EH00T3, the 40-point DVP40EH00R3 and DVP40EH00T3, and the 64-point DVP64EH00R3 and DVP64EH00T3. Delta’s operation manual specifies CPU firmware V1.12 or later. The Chinese section of the 2016 instruction sheet also includes V1.12. The English section says above V1.12, so verify the pairing on the bench before buying the card if your CPU is on V1.12 exactly.

Ports and network specifications

Ethernet · 1 × RJ45, automatic 10/100 Mbps speed selection and Auto MDI/MDI-X. Delta specifies a cable run of up to 100 m with Cat5e.

Modbus TCP · Up to 8 client and 4 server connections. The card supports static IP or DHCP. Factory network settings are IP 192.168.1.5, subnet mask 255.255.255.0, and gateway 192.168.1.1.

RS-232 COM3 · 1 × Mini-DIN, 19,200 bps, 8N1, Modbus ASCII. The CPU supplies 5 V DC through the card connector. Delta specifies 1 W power consumption.

Which software and cable do you need?

Use DCISoft to configure the card’s IP address, DHCP and data exchange settings. Use WPLSoft to upload, download or monitor the DVP-EH3 program. Connect over Ethernet with an RJ45 Cat5e cable. Delta’s 2016 instruction sheet lists UC-MS030-01A and UC-PRG020-12A for RS-232. See DVP programming cables for other cable options.

Card control registers

Read CR#0 to check the card model code H’6151 and CR#1 to check its firmware version. Use the PLC’s own firmware version when checking CPU compatibility.

Editor’s Note

Read the CPU label first. Check the EH3 order code, firmware version and function card slot. On a used card, inspect the RJ45 jack, the Mini-DIN pins and the connector that mates with the CPU.

Switch off power before fitting the card. Check that it is seated in the CPU slot before powering up. The CPU powers the card.

Run the first test on a separate network. If the factory IP is still set, assign your PC an address such as 192.168.1.33/24 and look for the card in DCISoft. A used card may retain its previous IP address.

Check link and data traffic separately. If the link LED stays dark, check the cable and switch port first. If the link is up, check the IP and subnet in DCISoft. Then try online monitoring in WPLSoft and read a known register from the HMI.

Record the existing settings before resetting the card. Note the IP address, data mappings and connected devices. After replacing a card, test reads first. Test writes with the machine in maintenance conditions.