Delta DVP06XA-E2

Delta DVP06XA-E2 — 4 Analog Input / 2 Analog Output Module

The Delta DVP06XA-E2 adds four analog inputs and two analog outputs to a compatible DVP PLC main unit. CH1–CH4 are inputs and CH5–CH6 are outputs. The “06” designation does not mean six analog inputs. Select voltage/current operation through both channel parameters and terminal wiring.

Use our Delta DVP PLC files page for wiring and conversion curves. E2 belongs to the ES2/EX2 expansion family and is also listed in ES3 catalogues. Although DVP06XA-H2 has the same channel count, its scaling, control registers and CPU connection are different.

Input ranges, resolution and raw values

Input modes include ±10 V, ±5 V, 0–10 V, 0–5 V, ±20 mA, 0–20 mA and 4–20 mA. Standard bipolar scaling is −32000 to +32000; unipolar scaling is 0–32000. The stated hardware resolution is 14 bits for ±10 V / ±5 V and ±20 mA inputs, and 13 bits for 0/4–20 mA inputs. Transferring data in a 16-bit word does not make the ADC a 16-bit converter.

On the standard curve, 5 V = 16000 in 0–10 V mode. In 4–20 mA input Mode 6, 4 mA = 0, 12 mA = 16000 and 20 mA = 32000. Evaluate analog signals using the selected mode and scaling as well as the 0–10 V / 4–20 mA range. Convert raw pressure or temperature transmitter values into the required engineering units.

Voltage input impedance is at least 1 MΩ; current input impedance is 250 Ω. Conversion takes 400 µs per channel. CPU communication and averaging also affect the update rate observed by the application. Input averaging is adjustable from 1–100 samples, with a default of 10.

Output ranges and load limits

Each output supports Mode 0: −10 to +10 V, Mode 1: 0–20 mA and Mode 2: 4–20 mA. Output hardware resolution is 14 bits. Voltage commands use −32000 to +32000; normal current commands use 0–32000. On standard curves, K16000 produces +5 V in voltage mode or 12 mA in 4–20 mA mode.

Voltage loads require at least 1 kΩ; current-loop loads must be 500 Ω or less. Match the signal to the connected variable frequency drive or analog controller. Do not send negative commands to equipment accepting only 0–10 V. K0 produces 4 mA in 4–20 mA mode, rather than zero current.

Terminal wiring and isolation

Connect CH1 voltage input between V1+ and VI1−; subsequent channels follow the same numbering. For current input, bridge the corresponding V+ and I+ and complete the loop through VI−. Select active/passive transmitter wiring and external loop power according to the manufacturer's diagram.

CH5 uses VO1 / IO1 / AG; CH6 uses VO2 / IO2 / AG. Connect voltage outputs through VO–AG and current outputs through IO–AG. Do not transfer the input's V+–I+ bridge to output terminals. FE serves shielding/functional-earth connections; AG is the analog common.

The analog and digital circuits are isolated, but analog channels are not isolated from each other. A conventional switching-output inductive sensor or photoelectric sensor is not an analog measurement source. Separate analog wiring from contactor and relay load circuits, considering control panel layout and shielding together.

Power supply and CPU compatibility

The module requires an external 24 V DC supply, with an allowable range of 20.4–28.8 V DC and maximum consumption of 2.5 W. Include transmitter consumption separately when sizing a power supply or DIN rail supply, and provide appropriate fuse protection.

Match DVP E2 modules to the exact CPU, firmware and expansion arrangement. The ES2 sheet numbers special modules 0–7, starting with the module closest to the CPU. Count other special modules within the eight-module limit. This module exchanges data through control registers rather than occupying digital X/Y points.

Programming software and cable

No independent PLC application is downloaded to DVP06XA-E2. For an ES2/EX2 CPU, use WPLSoft or ISPSoft and manage parameters through CPU FROM/TO instructions. WPLSoft's ES_AIO configuration can also configure settings such as input averaging. Configure COMMGR for the CPU port when using ISPSoft.

A suitable ES2/EX2 RS232 programming port can use DVPACAB2A30. If the PC has no RS232 port, use a suitable USB-to-RS232 converter, its driver and the correct COM port. The Delta PLC cable connects to the CPU, rather than the analog module.

For ES3, select software and connection according to the CPU model: standard ES3 supports the applicable ISPSoft/DIADesigner tools; WPLSoft is not supported. Models such as ES300TEC specifically require DIADesigner. Use the appropriate data cable and driver for the CPU's USB connection; do not generalize the ES2 serial cable across CPU generations.

Control registers and ES2 data mapping

CR#0 = H00C4 identifies the model; CR#1 reports firmware. CR#2–CR#5 select input modes, while CR#6–CR#7 select output modes. CR#8–CR#11 set averaging; CR#12–CR#15 hold averaged inputs; CR#16–CR#17 hold output commands; CR#20–CR#23 hold present input values.

For module K0, FROM K0 K12 D100 K4 reads four averaged inputs into D100–D103. TO K0 K16 D200 K2 writes D200 and D201 to the two outputs. 4–20 mA uses input Mode 6 and output Mode 2; the mode numbers are different.

On DVP-ES2, module 0 averaged inputs map to D9900–D9903, with output values at D9904–D9905. Module 1 starts at D9910; each module's start address advances by 10. For example, MOV D9900 D100 reads the CH1 average and MOV D200 D9904 writes the CH5 output value. Verify mapping before transferring these ES2 addresses to another CPU family.

CR#43 reports errors; multiple bits can be set simultaneously. The sheet specifies writing H5678 to CR#41 to save settings. Do not repeat this on every scan. Back up parameters first, save deliberately and verify retention through a power cycle.

Results can be monitored on an HMI panel or SCADA system. External Modbus ASCII or Modbus RTU access operates through the CPU's communication arrangement; do not assume a standalone RS485 port on E2. CR numbers, D addresses and protocol addresses are different references; consult our Modbus communication guide.

Editor's Note

Confirm the E2 suffix on a used module. Copying an H2 or S2 program unchanged can produce incorrect values despite the same four-input/two-output count.

Start with one input and a known signal. Expect 16000 at 5 V in 0–10 V mode, or 0, 16000 and 32000 at 4, 12 and 20 mA in 4–20 mA mode. Check whether calibration has been altered.

Disconnect the actuator before initial output tests. Measure voltage with a voltmeter and current with a correctly arranged current measurement. Remember that K0 still produces 4 mA in 4–20 mA mode.

Distinguish a missing current-input bridge from incorrect VO/IO output wiring. If one channel affects another, investigate common wiring, shields and the lack of channel-to-channel isolation.

For unstable readings, check supply, cable routing and grounding first. Increased averaging must not conceal a broken or incorrectly wired circuit.

Record CR#43 error bits and the actual channel modes. Test output behaviour during CPU STOP, restart and communication loss using the installed CPU/module settings.