Delta DVP16XP211R
Delta DVP16XP211R – Digital expansion module with 8 inputs and 8 relay outputs
The Delta DVP16XP211R adds eight 24 V DC digital inputs and eight relay outputs to a DVP-ES2 or DVP-EX2 CPU. It connects to the CPU’s right-side expansion bus. In packaging and assembly machinery, it can read signals from inductive sensors, photoelectric sensors, limit switches and pushbuttons, and switch suitable relays and contactor coils.
Input terminals and auxiliary supply
X0–X7 are rated at 24 V DC and 5 mA per input. Connect S/S to 0 V for PNP sensors or to +24 V for NPN sensors. All eight inputs share S/S. Leave the terminal marked NC open. Input response is approximately 10 ms from OFF to ON and 15 ms from ON to OFF.
Connect the 24 V DC auxiliary supply to 24V and 0V. Delta’s 2026 manual specifies an auxiliary supply range of 20.4–28.8 V DC and a current draw of approximately 5 mA per output. Connect the terminal marked with the ground symbol to panel protective earth.
Relay outputs and C0 common
C0 is the single common for Y0–Y7. Feed the load supply to the relay contacts through C0. Delta’s 2026 model wiring diagram specifies a contact voltage range of 10–240 V AC or 5–30 V DC. The resistive-load limits are 2 A per output and 5 A total at C0. Relay response is approximately 10 ms and the switching frequency is limited to 1 Hz. For inductive loads, check Delta’s contact life curve and select a suitable fuse and suppression device.
I/O addressing
X0–X7 and Y0–Y7 are local terminal labels. The CPU model and module order determine the addresses in the PLC program. In Delta’s example, the DVP08XP211R immediately after a DVP32ES200R reserves eight input addresses and eight output addresses for its four inputs and four outputs. The DVP16XP211R that follows uses X30–X37 and Y30–Y37 in this configuration.
Programming software and cable
The programming connection is made through the host CPU. For an ES2/EX2 CPU, use WPLSoft or a compatible version of ISPSoft. Configure ISPSoft’s RS-232 connection in COMMGR. To connect to the CPU’s COM1 RS-232 mini-DIN port, use the UC-PRG020-12A cable from a USB port or the UC-MS020-01A cable from an RS-232 port.
Delta also lists this module in its ES3/EX3 hardware manual. For these series, check ISPSoft or DIADesigner support and the connection port for the exact CPU model.
Related models
The DVP16XP211T has eight inputs and eight NPN transistor outputs. The DVP08XP211R has four inputs and four relay outputs. The DVP16XN211R has sixteen relay outputs. The DVP24XP200R has sixteen inputs, eight relay outputs and a 100–240 V AC module supply.
Editor’s Note
When buying a used module, check the R suffix on the rating label and make sure the removable terminal blocks are present.
On the bench, verify the 24V/0V supply and S/S connection first. Trigger each input in turn and watch its LED and the corresponding X address on the CPU.
Check each output with a 24 V DC test load. With the Y LED on, confirm that the contact between C0 and the relevant Y terminal switches the load. Check that the contact opens when the command is removed.
If all eight outputs draw 0.75 A at once, 6 A flows through C0 and exceeds its 5 A limit. Add up the current for the channels that will run at the same time.
Use a suitable flyback diode for a DC coil and a suitable suppressor for an AC coil. On a used module, look for discoloration around C0 and check for loose terminals.
PDF and wiring diagram
The model’s terminal diagram is in the DVP Series Module Manual, section 2.5.9, page 2-14. See the Delta DVP PLC files page for series documentation.