Delta DNA02

Delta DNA02 – DeviceNet Slave Communication Module

Delta DNA02 exchanges data between a DeviceNet scanner and field equipment connected to a serial port. It operates as a DeviceNet slave and supports polled I/O and explicit messaging. Delta documents examples for DVP PLCs, VFDs, ASDA-A servos, temperature controllers and DOP HMIs. The custom equipment profile supports compatible serial Modbus devices.

DeviceNet terminals and network settings

The module draws operating power from the DeviceNet V+ and V− terminals. Delta specifies 11–25 V DC at the input. The five pins are 1 V− (black), 2 CAN_L (blue), 3 SHIELD, 4 CAN_H (white), 5 V+ (red). Follow the network drawing for shield connections and grounding.

Use the two rotary switches to set a unique MAC ID from 00 to 63. SW3 DIP switches 6 and 7 select the network speed. In 6/7 order, OFF/OFF selects 125, ON/OFF 250, OFF/ON 500 kbit/s and ON/ON automatic detection. Switch 8 is reserved. Rotary and DIP changes take effect after cycling power to DNA02.

DVP PLC connection and serial settings

PORT1 is a six-contact modular RS-485 port. PORT2 is a DB9 port for RS-232 or RS-485. In Delta’s DVP diagram, PORT1 pin 3 (DATA−) and pin 4 (DATA+) connect to the matching COM2 RS-485 terminals on the CPU. Select the communication cable by its pin assignments.

Set DIP 1/2/3 to OFF/ON/OFF for the DVP profile and DIP 4/5 to OFF/OFF for RS-485. Delta’s DVP example specifies serial station 01 and a fixed format of 115,200 bit/s, 7E1 ASCII. These are PLC-side settings. Set DeviceNet’s MAC ID and network speed separately.

The default DVP mapping starts at D408 and M256 for data from the PLC to the scanner, and at D500 and M512 for data from the scanner to the PLC. Compare the actual project’s start addresses and I/O sizes with the scanner configuration.

Configuration software and cables

The switches set the DNA02 node and serial mode. Use the DNA02 EDS file and the scanner’s configuration software for the network project. With Delta’s DVPDNET-SL scanner, use DeviceNet Builder. Verify the DNA02 node, polled I/O connection and data sizes in both directions.

Edit the PLC program on the host CPU using WPLSoft or a compatible ISPSoft release, depending on the CPU model. For supported CPUs with a COM1 RS-232 mini-DIN port, the UC-PRG020-12A requires its USB serial driver. Select the CPU programming cable separately from the DNA02 PORT1-to-COM2 field cable.

Editor’s Note

Record the MAC ID, DIP positions and scanner I/O mapping before removing a used module. A spare with the same model number can have different settings.

Red NS points you to the network. Check for duplicate node addresses, mismatched speeds and trunk termination. DeviceNet calls for 121 Ω termination at each end of the trunk.

If NS looks normal but SP is red, troubleshoot the equipment link. Start with the COM2 station number, serial format and DATA+/DATA− wiring.

MS indicates module status. If the scanner sees the node but exchanges no data, verify the I/O connection and the produced and consumed byte counts.

Read a known value before testing any run commands. This lets you check the connection and data direction before enabling the load.

PDF manuals and related topics

Delta DVP PLC files · Chapter 12 of Delta’s application manual covers DNA02 DIP settings, serial wiring and LED diagnostics.

Related topics · Industrial communication · COA02 CANopen adapter · IFD9502 DeviceNet interface · DIN rail mounting

Navigation · Delta Automation · Delta PLC · DVP expansion modules · Specialty communication modules

External references

Delta DVP-PLC Application Manual – DNA02, Chapter 12 · Delta DNA02 instruction sheet, 24 May 2007 · ODVA DeviceNet cable guide · Delta PLC/HMI cable selection guide